| 2007-06-09 06:54:37 | DENIED |
| | REFERENCE: FBC-2004 CHAPTER 4 SECTION 424.1 |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. SHT 7 OF 10. INDICATE THE LOCATION OF THE SPA JETS. |
| | (6 INDICATED ON THE SCHEDULE). SECTION 106.1.1. |
| | ****NO RESPONSE/NOT ADDRESSED |
| | |
| | 2. SHT 8 OF 10. INDICATE THE LOCATION OF THE HOSE BIBB |
| | REQUIRED IN THE EQUIPMENT ROOM. SECTION 424.1.5.9. |
| | ****NO RESPONSE/NOT ADDRESSED |
| | |
| | 3. SHT 8A OF 10. OVERFLOW FROM THE POOL AND SPA |
| | COLLECTING TANKS SHALL CONNECT TO THE STORM SYSTEM, NOT |
| | THE SANITARY. PLEASE INDICATE ON THE PLANS. |
| | ****NO RESPONSE/NOT ADDRESSED |
| | |
| | 4. A SOLAR BLANKET WILL BE REQUIRED PER SECTION |
| | 13-612.1.ABC.2.3.2. - MANUF. SPECIFICATION SHEETS DO |
| | NOT INDICATE IF THE REQUIREMENT CAN BE EXEMPT FROM THIS |
| | REQUIREMENT. (SEE SECTION BELOW). |
| | |
| | 13-612.1.ABC.2.3.2 COVERS REQUIRED. |
| | SPAS AND HEATED SWIMMING POOLS SHALL BE EQUIPPED WITH A |
| | COVER DESIGNED TO MINIMIZE HEAT LOSS. |
| | EXCEPTION : OUTDOOR POOLS DERIVING OVER 70 PERCENT OF |
| | THE ENERGY FOR HEATING FROM NONDEPLETABLE ON |
| | SITE-RECOVERED SOURCES COMPUTED OVER AN OPERATING |
| | SEASON ARE EXEMPT FROM THIS REQUIREMENT. |
| | ****NO RESPONSE/NOT ADDRESSED |
| | |