| Plan Review Notes For Permit 06101137 |
| Permit Number |
06101137 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-05 14:51:01 | BUILDING PLAN REVIEW | | | PERMIT: 06101137 | | | ADD: 717 S OLIVE AVE | | | CONT: SUPERIOR POOL & SPA | | | TEL: (954) 578-1011 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1STREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)COMPLIED. | | | | | | 3) 13-412.1.ABC.2.6.2 POOL COVERS. | | | HEATED POOLS SHALL BE EQUIPPED WITH A VAPOR RETARDANT | | | POOL COVER ON OR AT THE WATER SURFACE. POOLS HEATED TO | | | MORE THAN 90?F (32?C) SHALL HAVE A POOL COVER WITH A | | | MINIMUM INSULATION VALUE OF R -12. | | | EXCEPTION: POOLS DERIVING OVER 60 PERCENT OF THE ENERGY | | | FOR HEATING FROM SITE-RECOVERED ENERGY OR SOLAR ENERGY | | | SOURCE. | | | | | | 4) PLANS DO NOT SHOW AN ACCESSIBLE ROUTE TO THE | | | POOL/SPA DECK AND POOL, ONLY STAIRS ARE EVIDENT? PLEASE | | | INDICATE THE | | | ACCESSIBLE PATH? 11-4.1.2. | | | | | | 5 ) COMPLIED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|