2006-11-21 09:34:16BUILDING PLAN REVIEW
 PERMIT: 06101137
 ADD: 717 S OLIVE AVE
 CONT: SUPERIOR POOL & SPA
 TEL: (954) 578-1011
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) DISCREPANCY, PLEASE CORRECT THE ADDRESS OF THE
 PERMIT APPLICATION.
  
 3) 13-412.1.ABC.2.6.2 POOL COVERS.
 HEATED POOLS SHALL BE EQUIPPED WITH A VAPOR RETARDANT
 POOL COVER ON OR AT THE WATER SURFACE. POOLS HEATED TO
 MORE THAN 90?F (32?C) SHALL HAVE A POOL COVER WITH A
 MINIMUM INSULATION VALUE OF R -12.
 EXCEPTION: POOLS DERIVING OVER 60 PERCENT OF THE ENERGY
 FOR HEATING FROM SITE-RECOVERED ENERGY OR SOLAR ENERGY
 SOURCE.
  
 4) PLANS DO NOT SHOW AN ACCESSIBLE ROUTE TO THE
 POOL/SPA DECK AND POOL, ONLY STAIRS ARE EVIDENT? PLEASE
 INDICATE THE
 ACCESSIBLE PATH? 11-4.1.2.
  
 5) PERMIT FEES ARE TO BE PAID AT TIME OF
 APPLICATION.!!!
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026