2006-11-21 09:05:54BUILDING PLAN REVIEW
 PERMIT: 06101134
 ADD: 717 S. OLIVE AVE
 CONT: SUPERIOR POOL & SPAS
 TEL: (954) 578-1011
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 2) DEPTH MARKINGS, THE PLAN DOES NOT MENTION THE
 REQUIREMENTS FOR
 DEPTH MARKINGS AS STATEDIN 424.1.2.3.1. (2).
  
 3) PLANS ALSO FAIL TO MENTION THE SIZE OF THE STAIR
 TREADS
 NOR RISERS OR THE REQUIREMENTS FOR THE LEADING EDGE OF
 THE STAIR TO BE DARK IN COLOR, CONTRASTING WITH THE
 INTERIOR
 OF THE INTERIOR OF THE POOL. 424.1.2.5.3.
  
 4)SHEET 4 BENCHES FAIL TO PROVIDE THE DEPTH THAT THE
 BENCHES WILL BE LOCATED AT?
 ALSO NO MENTION TO THE CONTRASTING COLORED TILE ON THE
 LEADING EDGE.
 424.1.2.6. OBSTRUCTIONS(2).UNDERWATER SEAT BENCHES
 MAY BE INSTALLED IN AREAS LESS THAN 5 FEET (1524 MM)
 DEEP. BENCH SEATS MUST BE 14 TO 18 INCHES (356 TO 457
 MM) WIDE AND MUST HAVE A DARK CONTRASTING MARKING ON
 THE SEAT EDGE EXTENDING 2 INCHES (51 MM) ON THE
 HORIZONTAL AND VERTICAL SURFACE. IF TILE IS USED IT
 MUST BE SLIP RESISTANT, EXCEPT THAT BULLNOSE TILE MAY
 BE SUBSTITUTED AND INSTALLED IN ACCORDANCE WITH SECTION
 424.1.2.5.3 .
  
 5)SHEET 8 DOESN'T INDICATE A HOSE BIB WITH VACUUM
 BREAKER IN THE EQUIPMENT ROOM OR AREA, 424.1.5.9.
  
 6) 13-412.1.ABC.2.6.2 POOL COVERS.
 HEATED POOLS SHALL BE EQUIPPED WITH A VAPOR RETARDANT
 POOL COVER ON OR AT THE WATER SURFACE. POOLS HEATED TO
 MORE THAN 90?F (32?C) SHALL HAVE A POOL COVER WITH A
 MINIMUM INSULATION VALUE OF R -12.
 EXCEPTION: POOLS DERIVING OVER 60 PERCENT OF THE ENERGY
 FOR HEATING FROM SITE-RECOVERED ENERGY OR SOLAR ENERGY
 SOURCE.
  
 7) PLANS DO NOT SHOW AN ACCESSIBLE ROUTE TO THE POOL
 DECK AND POOL, ONLY STAIRS ARE EVIDENT? PLEASE INDICATE
 THE
 ACCESSIBLE PATH? 11-4.1.2.
  
 8) PERMIT FEES ARE TO BE PAID AT TIME OF
 APPLICATION.!!!
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026