| 2008-12-20 13:52:08 | |
| | ACTION: DENIED |
| | |
| | REVIEWED FOR COMPLIANCE WITH THE FOLLOWING: |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | TWO COPIES OF REVISED "A-2" WERE SUBMITTED FOR REVIEW. |
| | A REVIEW OF THESE PLANS CAN NOT BE COMPLETED AT THIS |
| | TIME FOR THE FOLLOWING REASONS: |
| | |
| | 1. THE TWO COPIES SHOW DUCT DESIGNS WHICH DO NOT MATCH. |
| | EXAMPLE: ONE COPY SHOWS TWO SUPPLY DROPS IN THE KITCHEN |
| | WHILE THE OTHER COPY SHOWS NONE. EXAMPLE: THE HALF-BATH |
| | NEAR BEDROOM #3 SHOWS AN EXHAUST FAN ON ONE COPY BUT |
| | NOT THE OTHER. THESE ARE GIVEN AS EXAMPLES AND ARE NOT |
| | INTENDED TO BE AN EXHAUSTIVE LIST. CHECK ALL ASPECTS OF |
| | BOTH COPIES AND MAKE NECESSARY CORRECTIONS PRIOR TO |
| | RESUBMITTING (PERHAPS DRAWING THE PLAN ONCE AND COPYING |
| | IT RATHER THAN DRAWING IT TWICE WILL RESOLVE THIS |
| | PROBLEM). PLEASE PROVIDED TWO IDENTICAL PLANS SO ONE |
| | CAN BE INCORPORATED INTO THE PERMIT SET OF PLANS AND |
| | THE OTHER CAN BE USED IN THE FIELD FOR INSPECTIONS. |
| | FBCB 106.1.3. |
| | |
| | 2. SEVERAL DUCTS ARE MISSING SIZES ON PLANS. THIS |
| | CONDITION VARIES FROM ONE PLAN TO THE OTHER. PLEASE |
| | PROVIDED TWO IDENTICAL PLANS SO ONE CAN BE INCORPORATED |
| | INTO THE PERMIT SET OF PLANS AND THE OTHER CAN BE USED |
| | IN THE FIELD FOR INSPECTIONS. FBCB 106.1.3. |
| | |
| | 3. SOME OF THE DUCT SIZES ARE NOT LEGIBLE. PROVIDE |
| | PLANS OF SUFFICIENT CLARITY TO DESCRIBE THE SCOPE AND |
| | NATURE OF WORK PROPOSED IN ACCORDANCE WITH FBCB |
| | 106.1.1. |
| | |