| 2008-06-24 16:58:26 | RESIDENTIAL (R3) BUILDINGG REVIEWREVISION CHECKLIST: |
| | |
| | 1- PROVIDE SOIL TEST REPORT (2 COPIES) AFTER HOUSE AND |
| | POOL ARE REMOVED. ENGINEER OF RECORD TO REVIEW SOIL |
| | TEST REPORT TO VERIFY IF SOILS WILL MEET HIS DESIGN |
| | CRITERIA PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | |
| | 2- IF BBQ GRILL IS NOT GOING TO BE INSTALLED, THEN, |
| | REVISE ORIGINAL DRAWINGS. |
| | |
| | 3- PROVIDE CLEAR DETAILS AND SPECS FOR STAIRS TO SHOW |
| | COMPLIANCE WITH WINDERS DIMENSIONS OF SEC. R311.5.3.2 |
| | OF 2004 FLORIDA RESIDENTIAL CODE AND LIVE LOADS AS |
| | REQUIRED BY TABLE R301.5. (REPEAT COMMENT). PROVIDE |
| | DETAILS WITHWRITTEN DIMENSIONS. ALSO,FLOOR PLANS |
| | SHOW 17 RISERS, WHILE STAIR SECTIONCALLS FOR 18 |
| | RISERS.REVISE AS REQUIRED,ALSO, STAIRS ON 2ND FLOOR |
| | PLAN ARE SHOWN AS DOTTED LINES INSTEAD OF SOLID LINES. |
| | REVISE AS REQUIRED. |
| | |
| | REVISE SPECIFICATIONS FOR RAILING PICKETS AND MINIMUM |
| | TREAD SIZES SHOWN ON TYPICAL STAIR DETAIL ON SHEET D-1. |
| | SEE COMMENTS ON REVIEWED SET.EG: SPECS FOR PICKET |
| | SPACING SAYS THAT 4" SPHERE MAY PASS THRU INSTEAD OF |
| | MAY NOT PASS THRU.AND, SPECS FOR MINIMUM TREAD SIZE |
| | ARE NOT CLEAR. REVISE AS REQUIRED. |
| | |
| | 4- SURVEY TO HAVE ORIGINAL SIGNATURE, NOT COPY AS |
| | REQUIRED BY SEC. 61G17-7.0025 FLORIDA ADMINISTRATIVE |
| | CODE. |
| | |
| | 5-ENGINEER TO REVISE RAS 117 CALCULATIONS. |
| | FASTENERS CAN'T BE SPACED LESS THAN 4". O.C..SEE SEC. |
| | 8.1 OF RAS 117 AND REVISE AS REQUIRED. |
| | |
| | 6-ENERGY CALCULATIONS: |
| | A) REVISE CEILING INSULATION R-VALUE TO MATCH PLANS. |
| | NEED R-30. SEE PLANS. |
| | |
| | B) PROVIDE COMPLETE ENERGY CALCULATIONS. ONLY 2 |
| | SHEETS WERE SUBMITTED. |
| | |
| | 7- ENGINEER NEEDS TO REVISE DESIGN CRITERIA.ACCORDING |
| | TO SEC. R301.2.1.4(3) THIS BUILDING IS CONSIDERED TO BE |
| | EXPOSURE "C", NOT "B".REVISEINFORMATION ON SHEET |
| | S-2 AND WHERE THE DESIGN PRESSURES FOR OPENINGS ARE |
| | PROVIDED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |