| 2008-02-05 13:50:08 | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1- REVISE SOIL TEST REPORT TO REFLECT REVISED PROPOSED |
| | SCOPE OF WORK. |
| | 2- PROVIDE MANUFACTURER SPECS FOR BBQ GRILL TO BE |
| | INSTALLED IN PORCH.PAGE III OF SPECSSUBMITTED DON'T |
| | ALLOWBBQ GRILL ON PORCH. |
| | 3- PROVIDE CLEAR DETAILS AND SPECS FOR STAIRS TO SHOW |
| | COMPLIANCE WITH WINDERS DIMENSIONS OF SEC. R311.5.3.2 |
| | OF 2004 FLORIDA RESIDENTIAL CODE AND LIVE LOADS AS |
| | REQUIRED BY TABLE R301.5. |
| | ALSO, REVISE CODE REFERENCES SHOWN ON TYPICAL STAIR |
| | DETAIL ON SHEET D-1. SEE SEC. R311.5 OF 2004 FLORIDA |
| | RESIDENTIAL CODE FOR PROPER CODE SECTIONS TO BE |
| | REFERENCED. |
| | 4- SPECIFY DRAFSTOPPING ON SECOND FLOOR PLANAS |
| | REQUIRED BY SEC. R502.1.2 OF 2004 FLORIDA RESIDENTIAL |
| | CODE. |
| | 5- THIS PROPERTY IS LOCATED ON FLOOD ZONE "C", NOT "B". |
| | REVISE SURVEY AS REQUIRED. |
| | 6- PROVIDE COMPLETE WALL SECTION THRU BALCONY |
| | PROVIDINGCOMPLETE SPECSFOR FLOOR (INCLUDING BALCONY |
| | DECK)AND CEILINGS AS REQ'DBY SEC. 106.3.5.4 OF CITY |
| | AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH SEC. |
| | R301 OF 2004FLORIDA RESIDENTIAL CODE. |
| | 7- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| | PERIMETER AND CORNER AREAS FOR POLYGLASS MODIFIED |
| | BITUMEN AS REQ'DBY GENERAL LIMITATION #7.SEE |
| | GENERAL LIMITATION #7 TO SEE WHO CAN PREPARE SUCH |
| | CALCULATIONS. |
| | 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) PRODUCT APPROVAL FOR |
| | POLYGLASS MODIFIED BITUMEN AS REQ'DBY SEC. 106.3.3 |
| | CITY AMENDMENTS TO FBC 2004. |
| | 9- REVISE TYPO ON ENERGY CALCULATIONS ITEM 9(B).THERE |
| | IS NOT INSULATION R-219. |
| | |
| | ***NOTE: PROVIDE ABOVE INFORMATION PRIOR TO INSPECTIONS |
| | TO AVOID CONFLICTS ORDELAYS. |