| 2007-07-09 17:04:49 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB |
| | FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | |
| | COMMENTS FROM PREVIOUS LIST: |
| | |
| | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| | PERMIT PICKUP, FS713.13. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| | PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.THE PLANS |
| | MUST BE STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.PLEASE CALL 561-233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3.)INCLUDE FBC EB IN GOVERNING CODE.DECLARE LEVEL |
| | OF ALTERATION, FBC EB CHAPTER 3. |
| | |
| | 4.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| | OF RECORD, FBC*106.3.3. |
| | |
| | 2ND REVIEW - THIS MAY BE DONE WITH A SHOP DRAWING |
| | REVIEW STAMP OR A LETTER. |
| | |
| | 5.)FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED |
| | IN ADDITION TO THE NOAS SUBMITTED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG.THE FLORIDA STATE PRODUCT |
| | APPROVALS PROVIDED ARE EXPIRED; FBC2001 RATHER THAN |
| | FBC2004.PLEASE PRINT CURRENT APPROVALS. |
| | |
| | 2001 APPROVALS WERE SUBMITTED FOR PGT PW701, WINDSOR |
| | DOOR (2004 REQUIRED).NONE PROVIDED FOR THE PGT |
| | MULLION. |
| | |
| | 6.)ADDRESSED. |
| | |
| | 7.)SHOW REQUIRED HEAD CLEARANCE FOR THE ATTIC ACCESS, |
| | R807.IT DOES NOT APPEAR TO BE COMPLIANT IN THIS |
| | LOCATION. |
| | |
| | 2ND REVIEW -IT IS NOT CLEAR HOW THIS WAS ADDRESSED. |
| | |
| | 8-10.)ADDRESSED. |
| | |
| | 11.)SHOW DRAINAGE TO COMPLY WITH FBC R401. |
| | |
| | 12.)DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3. |
| | |
| | 13.)PROVIDE A SOILS INVESTIGATION REPORT, FBC |
| | R401.4. |
| | |
| | 2ND REVIEW - THIS WAS NOT SUBMITTED.THE SOILS REPORT |
| | SHOULD ALSO ADDRESS THE EXISTING POOL AREA. |
| | |
| | 14-15.)ADDRESSED. |
| | |
| | 16.)DOES THE GARAGE DOOR HAVE GLAZING?NOTE THAT |
| | GLAZING IS AN OPTION ON THE PRODUCT APPROVAL SUBMITTED |
| | BUT REQUIRES IMPACT PROTECTION. |
| | |
| | THIS MAY BE ADDRESSED BY WRITING "NO GLAZING" ON THE |
| | PRODUCT APPROVAL.IF YOU ARE USING THE GLAZING OPTION, |
| | IMPACT PROTECTION REQUIRED (WITH PRODUCT APPROVALS AND |
| | ATTACHED INSTALLATION SCHEDULE COMPLETED). |
| | |
| | 17.)ADDRESSED. |
| | |
| | 18.)CHANGES TO THE PLAN MUST BE DONE BY THE DESIGNER |
| | OF RECORD, CLOUDED, INITIALLED AND DATED.REVISIONS |
| | WERE DONE ON A1 AND A3 APPARENTLY BY SOMEONE OTHER THAN |
| | THE ENGINEER. |
| | |
| | 2ND REVIEW - CHANGES WERE NOT CLOUDED.THIS REQUIRES |
| | AN ENTIRELY NEW PLAN REVIEW AND WILL CAUSE DELAYS. ALL |
| | REVISIONS/CHANGES TO THE PLAN ARE TO BE CLOUDED AND |
| | NUMBERED. |
| | |
| | 19.)ELEVATIONS ON A1 SHOULD NOTE EXISTING AND |
| | ADDITION AREAS. |
| | |
| | 20.)THE ADDING STRAP DETAIL S2 DOES NOT COMPLY WITH |
| | THE SIMPSON CATALOG.ADDRESS.CHECK ALL CONNECTORS. |
| | |
| | 21.)SHEET D-2, HIB-91 HAS BEEN REPLACED BY TPI/WTCA |
| | BCSI 1-03.CHECK ALL REFERENCES.FOR INSTANCE, |
| | CONCRETE NOTE REFERS TO ACI 544.1R-82.THERE ARE OTHER |
| | EXPIRED REFERENCES.SEE FBC35. |
| | |
| | 22.)GARAGE/RESIDENCE SEPARATION TO COMPLY WITH FBC |
| | R309. |
| | |
| | NEW COMMENT: |
| | |
| | 23.)SEE ATTACHED FS553.80(2)9B). |