| 2008-12-29 13:04:49 | BUILDING SUBMITTAL CHECKLIST: | | | | | | 1- ENGINEER'S NAIL ENHANCING LETTER SUBMITTED FOR | | | POLYGLASS MODIFIED BITUMEN ROOFING SYSTEM DOESN'T WORK | | | FOR ZONE #3. ENGINEER TO PROVIDE THE CALCULATED DESIGN | | | PRESSURES FOR ALL ZONES IN EXPOSURE "C" AS SPECIFIED ON | | | LETTER SUBMITTED. AND, PROVIDE ACTUAL RAS 117 | | | CALCULATIONS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 | | | TO VERIFY COMPLIANCE WITH RAS 117 CALCULATIONS AND | | | DESIGN PRESSURES OF SEC. R301 OF 2004 FLORIDA | | | RESIDENTIAL CODE. | | | NOTE: ENGINEER TO REVIEW SEC. 8.1 OF RAS 117 FOR | | | MINIMUM FASTENER SEPARATION SPACING ALLOWED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|