Plan Review Notes
Plan Review Notes For Permit 06101118
Permit Number 06101118
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-02-15 10:15:03*****DENIED*****
  
  
  
 1.THE ADDRESS SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.SEE SHEETS M-1 AND M-2.
  
 2.NFPA 101-2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE-2004 EDITION CODE SHALL BE REFERENCED.
 PLEASE INDICATE WHERE THIS HAS BEEN ADDRESSED
  
 3.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.COMBUSTIBLE WASTE, DUST ,
 AND DEBRIS SHALL BE REMOVED FROM THE SITE DAILY OR MORE
 FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.PLEASE
 INDICATE WHERE THIS HAS BEEN ADDRESSED
  
 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEROF.PLEASE INDICATE WHERE
 THIS HAS BEEN ADDRESSED
  
 5.IN ORDER TO CONDUCT A COMPLETE FIRE PLAN REVIEW,
 THE FOLLOWING INFORMATION IS NEEDED:A) BUILDING
 CONSTRUCTION, B) TYPE OF OCCUPANCY, C) NUMBER OF
 FLOORS, D) INTERIOR FINISH CLASSIFICATION, E)THE
 BUILDING'S FIRE PROTECTION SYSTEMS I.E. FIRE ALARM
 AND/OR FIRE SPRINKLER SYSTEMANDF) ANY OTHER
 PERTINENT INFORMATIONPLEASE INDICATE WHERE THIS HAS
 BEEN ADDRESSED
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722