| Plan Review Notes For Permit 06101118 |
| Permit Number |
06101118 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-02-15 10:15:03 | *****DENIED***** | | | | | | | | | | | | 1.THE ADDRESS SHALL BE IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET.SEE SHEETS M-1 AND M-2. | | | | | | 2.NFPA 101-2003 EDITION AND THE FLORIDA FIRE | | | PREVENTION CODE-2004 EDITION CODE SHALL BE REFERENCED. | | | PLEASE INDICATE WHERE THIS HAS BEEN ADDRESSED | | | | | | 3.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS | | | SHALL COMPLY WITH NFPA 241.COMBUSTIBLE WASTE, DUST , | | | AND DEBRIS SHALL BE REMOVED FROM THE SITE DAILY OR MORE | | | FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS.PLEASE | | | INDICATE WHERE THIS HAS BEEN ADDRESSED | | | | | | 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT | | | INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID | | | PROPERTY OR VICINITY THEROF.PLEASE INDICATE WHERE | | | THIS HAS BEEN ADDRESSED | | | | | | 5.IN ORDER TO CONDUCT A COMPLETE FIRE PLAN REVIEW, | | | THE FOLLOWING INFORMATION IS NEEDED:A) BUILDING | | | CONSTRUCTION, B) TYPE OF OCCUPANCY, C) NUMBER OF | | | FLOORS, D) INTERIOR FINISH CLASSIFICATION, E)THE | | | BUILDING'S FIRE PROTECTION SYSTEMS I.E. FIRE ALARM | | | AND/OR FIRE SPRINKLER SYSTEMANDF) ANY OTHER | | | PERTINENT INFORMATIONPLEASE INDICATE WHERE THIS HAS | | | BEEN ADDRESSED | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|