| 2007-01-14 13:26:49 | |
| | **** UNSAT2ND REVIEW**** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN QUESTION. PLEASE SEE SOME ARE NEW BASED ON THE |
| | REVISED PLANS SUBMITTED. |
| | |
| | PLEASE SEE THE COMMENTS BELOW ARE TAKEN DIRECTLY FROM |
| | THE PREVIOUS REVIEW WITH AN ANSWERS OF OK, NO OR OK/NO. |
| | |
| | OK, WILL SHOW THE PREVIOUS NOTE REMOVED. |
| | NO, WILL CONTAIN FURTHER EXPLANATION OF THE PREVIOUS |
| | NOTE. |
| | NO/OK, IS THAT PART OF THE COMMENT MAY NOT HAVE BEEN |
| | ADDRESSED FULLY AND WILL BE FOLLOWED BY FURTHER |
| | EXPLANATION. |
| | |
| | ** PLEASE SEE THAT ANY NEW NOTES WILL BE ADDED TO THE |
| | END OF THESE REVIEW NOTES AND WILL BE SEPARATED WITH |
| | *** NEW NOTES 2ND REVIEW ***. |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: NO, PLEASE SEE RESPONSE ON PLANS MENTIONS THIS |
| | IS MOVEABLE FURNITURE AND TO SEE ARCHITECTURAL PLANS, |
| | HOWEVER THE A SHEETS DO NOT SHOW THIS TYPE OF |
| | FURNITURE. PLEASE KNOW IN EITHER CASE THESE PANELS MUST |
| | HAVE READY ACCESS FOR A MULTITUDE OF REASONS FOR |
| | SAFETY. |
| | PLEASE RELOCATE PANELS OR REMOVE FURNITURE. |
| | 110.26, 408.7, 240.24D ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE LUNCH ROOM ON FIRST FLOOR WHICH APPEARS TO |
| | SHOW COUNTER SPACE IN FRONT OF ALL THE ELECTRICAL |
| | PANELS ON THE FIRST FLOOR? PLEASE SEE 110.26, IF THIS |
| | CONDITION EXISTS THESE WILL BE REQUIRED TO BE REMOVED. |
| | 110.26 |
| | |
| | 3) NOTE: OK/NO. PLEASE SEE THE ELECTRICAL SEEMS TO BE |
| | NOTED AND CODE COMPLIANCE SEEMS TO HAVE BEEN MET FOR |
| | DISCONNECTING MEANS ETC, HOWEVER PLEASE SEE THE RATING |
| | OF THE ROOM ON ARCHITECTURAL PLANS COULD NOT BE |
| | LOCATED. PLEASE SEE 1HR MIN SHALL BE INSTALLED PER |
| | NFPA-75 IF NOT ALREADY EXISTING. |
| | PLEASE SEE NO INFORMATION WAS SUBMITTED FOR THE |
| | MANUFACTURES SPEC/CUT SHEETS WHICH WAS REQUESTED ON |
| | PREVIOUS REVIEW. |
| | 110.3, 90.7. |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE VERIFY ROOMS BEING SHOWN AS SERVER/IT ROOMS? |
| | PLEASE SEE NFPA-75 AND PLEASE SEE NEC 645.10 ETC. |
| | PLEASE PROVIDE A BREAK DOWN OF ROOM AND EQUIPMENT BEING |
| | INSTALLED. PLEASE SUBMIT ALL MANUFACTURE SPECS/CUT |
| | SHEETS FOR THE EQUIPMENT BEING INSTALLED IN THESE |
| | ROOMS. |
| | 110.3, 90.7. |
| | |
| | 4) NOTE:NO, PLANS MENTION THIS IS AN EXISTING |
| | CONDITION/ROOM HOWEVER DUE TO THE AMOUNT OF WORK FOR |
| | THIS BUILD-OUT/ REMODEL, VERIFICATION OF THIS IS |
| | REQUIRED. 620.23, 620.24 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE VERIFY NEW OR EXISTING REQUIRED CIRCUITS PER |
| | 620.23, 620.24 |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: NO/OK. PLEASE SEE MUCH OF CHAPTER 13 IS SHOWN; |
| | HOWEVER PLEASE SEE SOME NEW NOTES FOR THIS REVIEW |
| | ALSO. |
| | PLEASE SEE THE AREA WHICH SHOW ONE DEVICE AS A MOTION |
| | DEVICE FOR OVER RIDE AS PREVIOUSLY MENTIONED FOR |
| | WAREHOUSE DOES NOT SEEM TO MEET COVERAGE BASED ON THE |
| | TYPE OF DEVICE BEING SHOWN ON PLANS. |
| | PLEASE SEE NOTES ON PLANS MENTIONS DEVICES ARE |
| | PERMITTED AT 4HRS AND TIMES WILL BE 15MINS, HOWEVER |
| | PLEASE SEE SECTIONS GIVEN AS ONLY TIMER TYPE OVER RIDES |
| | ARE PERMITTED TO BE 4HOURS AND ANY OCCUPANCY SENSOR |
| | TYPE DEVICES IS 30MINS MAX. |
| | PLEASE SEE THERE ARE MANY ROOMS WHICH DO NOT SHOW ANY |
| | CONTROL DEVICES AS REQUIRED PER 13-415.1.ABC.1.2. ? |
| | PLEASE INDICATE THE DEVICES WHICH ARE SHOWN ON THE E-8 |
| | WITH THEIR TIMES DETAILS ETC. |
| | PLEASE PROVIDE TIMES ON SCHEDULING (7AM-6PM?). |
| | PLEASE SEE THAT A NOTE WAS PLACED ON PLANS THAT |
| | COMPLIANCE MUST BE MET FOR LIGHTING PERFORMANCE LEVELS, |
| | HOWEVER STATING THIS NOTE IN LIEU OF SUBMITTING THE |
| | REQUIRED CALCULATIONS AND PERFORMANCE LEVELS PERMITTED |
| | CAN NOT BE ACCEPTED. PLEASE SUBMIT THE ENERGY |
| | CALCULATIONS AS REQUIRED AND LIGHTING POWER DENSITIES. |
| | 13-415.1.AB.1, 13-415.2. |
| | METHOD B / C? |
| | ** PLEASE SEE NEW NOTES AND PLEASE CLARIFY HOW THE |
| | LIGHTING CONTROL PANELS/CIRCUITS ARE FED. PLEASE SEE |
| | THE TWO NEW PANELS. |
| | |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE NOTES ON PLANS MENTIONS COMPLIANCE WITH |
| | CHAPTER 13, PLEASE SUBMIT THE SPECS AND SHOW DETAIL ON |
| | THE PROPOSED SYSTEM WHICH IS BEING INSTALLED. PLEASE |
| | SEE SOME LARGER AREAS SEEM TO BE USING AN M SWITCH |
| | (WAREHOUSE ETC) WHICH DOES NOT SEEM TO PROVIDE |
| | COVERAGE? PLEASE ALSO INDICATE OVER RIDE TIMES ON THE |
| | TYPE OF DEVICES BEING INSTALLED. (MOTION/OCCUPANT TYPE |
| | SENSORS 30MINS MAX, TIMER TYPE 4HRS MAX ON OVER RIDES.) |
| | 13-415.1.ABC.1.1, .1.2, .1.3. |
| | PLEASE SEE NOTE MENTIONS TO MEET WATTAGE USAGE HOWEVER |
| | THIS WOULD NEED TO BE SHOWN AT THIS TIME. |
| | PLEASE SEE 13-415.2.ABC.1, TABLES 415.2.C.1 |
| | |
| | 7) NOTE: OK, HOWEVER SEE NEW NOTES FOR REVISED RISER. |
| | |
| | 8) NOTE:OK, HOWEVER SEE NEW NOTES DUE TO REVISED |
| | RISER. |
| | |
| | 9) NOTE: NO, PLEASE SEE LOADS ARE BEING SHOWN FOR SOME |
| | OF THE EXISTING AS NOTE ON E-7, HOWEVER PLEASE SEE ALL |
| | NEW LOADS ARE SHOWN BEING ADDED TO EXISTING. PLEASE SEE |
| | MISSING LIGHTING ETC. PLEASE SEE NEW NOTES DUE TO |
| | REVISED PLANS AND RISER SUBMITTED. |
| | 215.5, 220.10, 220.3, 220.11, 220.13, CONTINUOUS LOADS |
| | PER 215.3, 230.42 ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT AND COMPLETE LOAD CALCULATIONS. PLEASE |
| | SEE MDP WHICH DOES NOT INDICATE ALL LOADS, ONLY THE TWO |
| | NEW PANELS. THE LOAD SUMMARY ON THE RISER SHEET WAS |
| | NOTED, HOWEVER ALL LOADS FOR NEW AND EXISTING SHOULD BE |
| | INCLUDE ON THE NEW PROPOSED MDP. |
| | 220, 215.3, 230.42 ETC. |
| | |
| | 10) NOTE: NO, SAME AS NOTED IN NOTE #9 ABOVE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42 ETC. |
| | |
| | 11) NOTE: OK, SEE NEW NOTES. |
| | |
| | 12) NOTE:NO, PLEASE SEE ALL ROOMS AND AREAS WITH |
| | DESIGNATIONS SHOULD CORRELATE TO THE CIRCUIT |
| | DESIGNATIONS AND PANEL SCHEDULE(S). |
| | WAREHOUSE/LUNCHROOM, KITCHEN ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE ALL ROOM AND AREA DESIGNATIONS ON |
| | ELECTRICAL PLANS. PLEASE CORRELATE WITH CIRCUITING ON |
| | PANEL SCHEDULES. ROOM "X", CIRCUIT # 23, ETC. FCB |
| | 106.1.2, NEC 408.4, ETC |
| | |
| | 13) NOTE: OK/NO, PLEASE SEE THE PANEL SCHEDULES WERE |
| | REVISED HOWEVER PLEASE CLARIFY IF ALL THESE WILL BE |
| | FEEDING NON-LINEAR LOADS. |
| | PLEASE SEE AS AN IT/SERVER ROOM IS SHOWN PLEASE |
| | CLARIFY THE SIZING OF THE NEUTRAL CONDUCTORS. |
| | A) PLEASE PROVIDE CALCULATIONS ON NEUTRAL CONDUCTORS |
| | FOR ALL NON-LINEAR CIRCUITS. PLEASE SEE ALL CIRCUITS |
| | WHICH CONTAIN THESE LOADS SHALL MEET THE SIZING |
| | REQUIREMENTS TO HANDLE AND ALLEVIATE THE OVER LOADING |
| | OF THE NEUTRAL ON A 3-PHASE 4-WIRE SYSTEM WITH |
| | PREDOMINATELY OR ACTUALLY IN MANY CASES ALL NON-LINEAR |
| | LOADS. PLEASE SEE THIS CAN BE DONE BY USING MANY |
| | METHODS. THE K-RATED TRANSFORMERS WERE REMOVED FROM THE |
| | DESIGN AS ON PREVIOUS PLANS, SO PLEASE SEE THE REQUEST |
| | FOR FULL NEUTRAL LOAD CALCULATION OR THE SIZING OF THE |
| | NEUTRAL AT 200%. |
| | PLEASE SEE THE RISK OF FIRE AND CAUSE TO PROPERTY |
| | DAMAGE IS OF CONCERN PLEASE SEE STUDIES IN WHITE PAPERS |
| | WHICH INDICATE AS MUCH AS 1.7 TIMES THE RATED LOAD OF |
| | THE CONDUCTOR. |
| | PLEASE SEE THE FOLLOWING CODES: THIS OFFICE IS AWARE OF |
| | WHAT A FPN MEANS, HOWEVER SEE SECTIONS GIVEN WHICH DO |
| | NOT CONTAIN FPN.PLEASE SEE 210.4A (FPN), 220.22 |
| | (FPN(2), 310.10, 310.15B4(C), 400.5, 520.44, 408.16, |
| | AND FBC 104.6 ADMINISTRATIVE SECTION AS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE VERIFY MODULAR FURNITURE BEING SHOWN WITH |
| | 50A OCP ON #6 AWG?? PLEASE SUPPLY MANUFACTURE SPECS/CUT |
| | SHEETS FOR THESE AS THIS TYPE OF FURNITURE AT THIS SIZE |
| | AND LOAD AHS NOT BEEN SEEN BEFORE. PLEASE SEE |
| | 210.21(B)3. |
| | |
| | 14) NOTE: OK, NO FA SYSTEM IS BEING SHOWN, HOWEVER IF |
| | ONE IS REQUIRED THE PREVIOUS NOTES WILL APPLY. |
| | |
| | 15) NOTE: OK, SEE NEW NOTES. |
| | |
| | 16) NOTE: NO, PLEASE SEE THE VALUE FOR COMPLETE SCOPE |
| | OF WORK HAS NOT BEEN CHANGED OR ADJUSTED ON PERMIT |
| | APPLICATION. PLEASE KNOW BASED ON THE SQ FT, THE |
| | ELECTRICAL EQUIPMENT AND SYSTEMS BEING INSTALLED A |
| | VALUE WILL BE ASSESSED ON THE NEXT REVIEW IF ONE IS NOT |
| | ADJUSTED. |
| | PLEASE ADDRESS THIS COMMENT AS THE VALUE ON APPLICATION |
| | IS LOW. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK SEEMS LOW. |
| | THIS VALUE SHALL BE BASED ON ALL LABOR AND MATERIALS |
| | EVEN IF ANY MATERIALS OR EQUIPMENT IS BEING OWNER |
| | SUPPLIED. PLEASE KNOW, IF AN APPROPRIATE VALUE IS NOT |
| | ADJUSTED, ONE WILL BE ADJUSTED BY THE TABLES FROM THE |
| | FBC. |
| | FBC 108.3 ADMIN SECTION AS ADOPTED BY THE CITY OF WEST |
| | PALM BEACH USING THE MARSHAL'S & SWIFT GUIDE AT A MIN |
| | AND TABLES AS SET-FORTH IN THE BLDG CODE. |
| | |
| | 17) NOTE: OK, SEE NEW NOTES. |
| | |
| | 18) NOTE: OK, SIX BREAKERS SHOWN. |
| | |
| | |
| | *** NEW NOTES 2ND REVIEW *** |
| | |
| | 19) NOTE: PLEASE SEE NEW MDP WHICH INDICATES AIC |
| | RATINGS AT 100K. IS THIS FOR ALL BREAKERS AS SHOWN AS |
| | NO MCB IS BEING SHOWN ON THIS MLO EQUIPMENT? PLEASE SEE |
| | THE COST RELATE TO EACH OF THESE AT 100K MAY OUTWEIGH |
| | THE COST OF A SINGLE MAIN AND SERIES RATED BRANCH |
| | BREAKERS? |
| | THIS IS ONLY BEING NOTED, IF SHOWN AT 100K THEN, 100K |
| | RATED BREAKERS WILL BE REQUIRED. |
| | |
| | 20) NOTE: PLEASE CLARIFY HOW THE LIGHTING PANELS ARE |
| | FED. PLEASE SEE RISER DOES NOT INDICATE HOW AND WHERE |
| | THESE ARE FED FROM. PLEASE SEE PANELS 1F AND 2F DO NOT |
| | INDICATE ANY CIRCUITS TO THESE PANELS. ?? |
| | PLEASE CLARIFY WHERE THE LOADS ARE BEING ASSIGNED AS |
| | THE LOADS ON THE MDP DO NOT INDICATE ANY OF THE |
| | LIGHTING. |
| | 220/215/215.3/230.42 ETC. |
| | PLEASE SEE THIS IS EXPANDED FROM PREVIOUS NOTE ABOVE |
| | NOTE #9. |
| | |
| | 21) NOTE: PLEASE SEE SUBMITTED ELECTRICAL PLANS ARE |
| | ALSO IN SETS WHICH ARE DONE BY THIS ARCHITECT? PLEASE |
| | CLARIFY WHICH PLANS ARE TO BE REVIEWED AS THESE ARE NOT |
| | THE SAME AND ONLY THE DESIGNER OF RECORD FOR ELECTRICAL |
| | SHOULD BE SUBMITTING THESE. |
| | FBC 106.1 |
| | |
| | 22) NOTE: PLEASE SEE 210.8B3 WHICH WAS NOT NOTED ON |
| | PREVIOUS REVIEW; HOWEVER PREVIOUS REVIEWED PLANS WERE |
| | NOT SUBMITTED BACK FOR REVIEW OF REFERENCE AS |
| | PREVIOUSLY REQUESTED ON THE FIRST REVIEW, SO IT IS NOT |
| | KNOW IF THE PREVIOUS PLANS SHOWED COMPLIANCE WITH THIS. |
| | PLEASE SEE AND OUTLET IS BEING SHOWN AS 220V WHICH |
| | APPEARS TO BE FOR A STOVE. |
| | PLEASE INDICATE IF THE EXISTING RECEPTACLES IN THIS |
| | ROOM MEET THE REQUIREMENTS FOR GFI PROTECTION OR IF NEW |
| | DEVICES WILL BE INSTALLED. |
| | |
| | 23) NOTE: PLEASE SEE AS NOTE ABOVE IN PREVIOUS REVIEW |
| | NOTE #9, PLEASE SEE THE NEW MDP, SHOW LOADS FOR THE |
| | 600A MLO, HOUSE PANEL AND "? PANEL" AS BLANK FOR THE |
| | LOADS. THE LOADS ON THE MDP DIFFER FROM THE LOADS ON |
| | E-7 |
| | 106.1.2, 106.3.5.1.2 ADMIN SECTION OF THE FBC FOR |
| | ADDITIONAL INFORMATION NEEDED. |
| | |
| | 24) NOTE: PLESE SEEFS 553.80(2)(B), THIS IS ONLY |
| | GIVEN AS A NOTICE AT THIS TIME. |
| | |
| | ** ONCE AGAIN, PLEASE KNOW AT THIS TIME, THERE ARE |
| | ITEMS NOT YET SHOWN WHICH CAN NOT BE REVIEWED AT THIS |
| | TIME WHICH MAY CREATE NEW COMMENTS ON NEXT REVIEW. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |