Plan Review Notes
Plan Review Notes For Permit 06101118
Permit Number 06101118
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-14 13:26:49 
 **** UNSAT2ND REVIEW****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN QUESTION. PLEASE SEE SOME ARE NEW BASED ON THE
 REVISED PLANS SUBMITTED.
  
 PLEASE SEE THE COMMENTS BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH AN ANSWERS OF OK, NO OR OK/NO.
  
 OK, WILL SHOW THE PREVIOUS NOTE REMOVED.
 NO, WILL CONTAIN FURTHER EXPLANATION OF THE PREVIOUS
 NOTE.
 NO/OK, IS THAT PART OF THE COMMENT MAY NOT HAVE BEEN
 ADDRESSED FULLY AND WILL BE FOLLOWED BY FURTHER
 EXPLANATION.
  
 ** PLEASE SEE THAT ANY NEW NOTES WILL BE ADDED TO THE
 END OF THESE REVIEW NOTES AND WILL BE SEPARATED WITH
 *** NEW NOTES 2ND REVIEW ***.
  
 1) NOTE: OK.
  
 2) NOTE: NO, PLEASE SEE RESPONSE ON PLANS MENTIONS THIS
 IS MOVEABLE FURNITURE AND TO SEE ARCHITECTURAL PLANS,
 HOWEVER THE A SHEETS DO NOT SHOW THIS TYPE OF
 FURNITURE. PLEASE KNOW IN EITHER CASE THESE PANELS MUST
 HAVE READY ACCESS FOR A MULTITUDE OF REASONS FOR
 SAFETY.
 PLEASE RELOCATE PANELS OR REMOVE FURNITURE.
 110.26, 408.7, 240.24D ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE LUNCH ROOM ON FIRST FLOOR WHICH APPEARS TO
 SHOW COUNTER SPACE IN FRONT OF ALL THE ELECTRICAL
 PANELS ON THE FIRST FLOOR? PLEASE SEE 110.26, IF THIS
 CONDITION EXISTS THESE WILL BE REQUIRED TO BE REMOVED.
 110.26
  
 3) NOTE: OK/NO. PLEASE SEE THE ELECTRICAL SEEMS TO BE
 NOTED AND CODE COMPLIANCE SEEMS TO HAVE BEEN MET FOR
 DISCONNECTING MEANS ETC, HOWEVER PLEASE SEE THE RATING
 OF THE ROOM ON ARCHITECTURAL PLANS COULD NOT BE
 LOCATED. PLEASE SEE 1HR MIN SHALL BE INSTALLED PER
 NFPA-75 IF NOT ALREADY EXISTING.
 PLEASE SEE NO INFORMATION WAS SUBMITTED FOR THE
 MANUFACTURES SPEC/CUT SHEETS WHICH WAS REQUESTED ON
 PREVIOUS REVIEW.
 110.3, 90.7.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY ROOMS BEING SHOWN AS SERVER/IT ROOMS?
 PLEASE SEE NFPA-75 AND PLEASE SEE NEC 645.10 ETC.
 PLEASE PROVIDE A BREAK DOWN OF ROOM AND EQUIPMENT BEING
 INSTALLED. PLEASE SUBMIT ALL MANUFACTURE SPECS/CUT
 SHEETS FOR THE EQUIPMENT BEING INSTALLED IN THESE
 ROOMS.
 110.3, 90.7.
  
 4) NOTE:NO, PLANS MENTION THIS IS AN EXISTING
 CONDITION/ROOM HOWEVER DUE TO THE AMOUNT OF WORK FOR
 THIS BUILD-OUT/ REMODEL, VERIFICATION OF THIS IS
 REQUIRED. 620.23, 620.24
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY NEW OR EXISTING REQUIRED CIRCUITS PER
 620.23, 620.24
  
 5) NOTE: OK.
  
 6) NOTE: NO/OK. PLEASE SEE MUCH OF CHAPTER 13 IS SHOWN;
 HOWEVER PLEASE SEE SOME NEW NOTES FOR THIS REVIEW
 ALSO.
 PLEASE SEE THE AREA WHICH SHOW ONE DEVICE AS A MOTION
 DEVICE FOR OVER RIDE AS PREVIOUSLY MENTIONED FOR
 WAREHOUSE DOES NOT SEEM TO MEET COVERAGE BASED ON THE
 TYPE OF DEVICE BEING SHOWN ON PLANS.
 PLEASE SEE NOTES ON PLANS MENTIONS DEVICES ARE
 PERMITTED AT 4HRS AND TIMES WILL BE 15MINS, HOWEVER
 PLEASE SEE SECTIONS GIVEN AS ONLY TIMER TYPE OVER RIDES
 ARE PERMITTED TO BE 4HOURS AND ANY OCCUPANCY SENSOR
 TYPE DEVICES IS 30MINS MAX.
 PLEASE SEE THERE ARE MANY ROOMS WHICH DO NOT SHOW ANY
 CONTROL DEVICES AS REQUIRED PER 13-415.1.ABC.1.2. ?
 PLEASE INDICATE THE DEVICES WHICH ARE SHOWN ON THE E-8
 WITH THEIR TIMES DETAILS ETC.
 PLEASE PROVIDE TIMES ON SCHEDULING (7AM-6PM?).
 PLEASE SEE THAT A NOTE WAS PLACED ON PLANS THAT
 COMPLIANCE MUST BE MET FOR LIGHTING PERFORMANCE LEVELS,
 HOWEVER STATING THIS NOTE IN LIEU OF SUBMITTING THE
 REQUIRED CALCULATIONS AND PERFORMANCE LEVELS PERMITTED
 CAN NOT BE ACCEPTED. PLEASE SUBMIT THE ENERGY
 CALCULATIONS AS REQUIRED AND LIGHTING POWER DENSITIES.
 13-415.1.AB.1, 13-415.2.
 METHOD B / C?
 ** PLEASE SEE NEW NOTES AND PLEASE CLARIFY HOW THE
 LIGHTING CONTROL PANELS/CIRCUITS ARE FED. PLEASE SEE
 THE TWO NEW PANELS.
  
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE NOTES ON PLANS MENTIONS COMPLIANCE WITH
 CHAPTER 13, PLEASE SUBMIT THE SPECS AND SHOW DETAIL ON
 THE PROPOSED SYSTEM WHICH IS BEING INSTALLED. PLEASE
 SEE SOME LARGER AREAS SEEM TO BE USING AN M SWITCH
 (WAREHOUSE ETC) WHICH DOES NOT SEEM TO PROVIDE
 COVERAGE? PLEASE ALSO INDICATE OVER RIDE TIMES ON THE
 TYPE OF DEVICES BEING INSTALLED. (MOTION/OCCUPANT TYPE
 SENSORS 30MINS MAX, TIMER TYPE 4HRS MAX ON OVER RIDES.)
 13-415.1.ABC.1.1, .1.2, .1.3.
 PLEASE SEE NOTE MENTIONS TO MEET WATTAGE USAGE HOWEVER
 THIS WOULD NEED TO BE SHOWN AT THIS TIME.
 PLEASE SEE 13-415.2.ABC.1, TABLES 415.2.C.1
  
 7) NOTE: OK, HOWEVER SEE NEW NOTES FOR REVISED RISER.
  
 8) NOTE:OK, HOWEVER SEE NEW NOTES DUE TO REVISED
 RISER.
  
 9) NOTE: NO, PLEASE SEE LOADS ARE BEING SHOWN FOR SOME
 OF THE EXISTING AS NOTE ON E-7, HOWEVER PLEASE SEE ALL
 NEW LOADS ARE SHOWN BEING ADDED TO EXISTING. PLEASE SEE
 MISSING LIGHTING ETC. PLEASE SEE NEW NOTES DUE TO
 REVISED PLANS AND RISER SUBMITTED.
 215.5, 220.10, 220.3, 220.11, 220.13, CONTINUOUS LOADS
 PER 215.3, 230.42 ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT AND COMPLETE LOAD CALCULATIONS. PLEASE
 SEE MDP WHICH DOES NOT INDICATE ALL LOADS, ONLY THE TWO
 NEW PANELS. THE LOAD SUMMARY ON THE RISER SHEET WAS
 NOTED, HOWEVER ALL LOADS FOR NEW AND EXISTING SHOULD BE
 INCLUDE ON THE NEW PROPOSED MDP.
 220, 215.3, 230.42 ETC.
  
 10) NOTE: NO, SAME AS NOTED IN NOTE #9 ABOVE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
  
 11) NOTE: OK, SEE NEW NOTES.
  
 12) NOTE:NO, PLEASE SEE ALL ROOMS AND AREAS WITH
 DESIGNATIONS SHOULD CORRELATE TO THE CIRCUIT
 DESIGNATIONS AND PANEL SCHEDULE(S).
 WAREHOUSE/LUNCHROOM, KITCHEN ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ALL ROOM AND AREA DESIGNATIONS ON
 ELECTRICAL PLANS. PLEASE CORRELATE WITH CIRCUITING ON
 PANEL SCHEDULES. ROOM "X", CIRCUIT # 23, ETC. FCB
 106.1.2, NEC 408.4, ETC
  
 13) NOTE: OK/NO, PLEASE SEE THE PANEL SCHEDULES WERE
 REVISED HOWEVER PLEASE CLARIFY IF ALL THESE WILL BE
 FEEDING NON-LINEAR LOADS.
 PLEASE SEE AS AN IT/SERVER ROOM IS SHOWN PLEASE
 CLARIFY THE SIZING OF THE NEUTRAL CONDUCTORS.
 A) PLEASE PROVIDE CALCULATIONS ON NEUTRAL CONDUCTORS
 FOR ALL NON-LINEAR CIRCUITS. PLEASE SEE ALL CIRCUITS
 WHICH CONTAIN THESE LOADS SHALL MEET THE SIZING
 REQUIREMENTS TO HANDLE AND ALLEVIATE THE OVER LOADING
 OF THE NEUTRAL ON A 3-PHASE 4-WIRE SYSTEM WITH
 PREDOMINATELY OR ACTUALLY IN MANY CASES ALL NON-LINEAR
 LOADS. PLEASE SEE THIS CAN BE DONE BY USING MANY
 METHODS. THE K-RATED TRANSFORMERS WERE REMOVED FROM THE
 DESIGN AS ON PREVIOUS PLANS, SO PLEASE SEE THE REQUEST
 FOR FULL NEUTRAL LOAD CALCULATION OR THE SIZING OF THE
 NEUTRAL AT 200%.
 PLEASE SEE THE RISK OF FIRE AND CAUSE TO PROPERTY
 DAMAGE IS OF CONCERN PLEASE SEE STUDIES IN WHITE PAPERS
 WHICH INDICATE AS MUCH AS 1.7 TIMES THE RATED LOAD OF
 THE CONDUCTOR.
 PLEASE SEE THE FOLLOWING CODES: THIS OFFICE IS AWARE OF
 WHAT A FPN MEANS, HOWEVER SEE SECTIONS GIVEN WHICH DO
 NOT CONTAIN FPN.PLEASE SEE 210.4A (FPN), 220.22
 (FPN(2), 310.10, 310.15B4(C), 400.5, 520.44, 408.16,
 AND FBC 104.6 ADMINISTRATIVE SECTION AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE VERIFY MODULAR FURNITURE BEING SHOWN WITH
 50A OCP ON #6 AWG?? PLEASE SUPPLY MANUFACTURE SPECS/CUT
 SHEETS FOR THESE AS THIS TYPE OF FURNITURE AT THIS SIZE
 AND LOAD AHS NOT BEEN SEEN BEFORE. PLEASE SEE
 210.21(B)3.
  
 14) NOTE: OK, NO FA SYSTEM IS BEING SHOWN, HOWEVER IF
 ONE IS REQUIRED THE PREVIOUS NOTES WILL APPLY.
  
 15) NOTE: OK, SEE NEW NOTES.
  
 16) NOTE: NO, PLEASE SEE THE VALUE FOR COMPLETE SCOPE
 OF WORK HAS NOT BEEN CHANGED OR ADJUSTED ON PERMIT
 APPLICATION. PLEASE KNOW BASED ON THE SQ FT, THE
 ELECTRICAL EQUIPMENT AND SYSTEMS BEING INSTALLED A
 VALUE WILL BE ASSESSED ON THE NEXT REVIEW IF ONE IS NOT
 ADJUSTED.
 PLEASE ADDRESS THIS COMMENT AS THE VALUE ON APPLICATION
 IS LOW.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK SEEMS LOW.
 THIS VALUE SHALL BE BASED ON ALL LABOR AND MATERIALS
 EVEN IF ANY MATERIALS OR EQUIPMENT IS BEING OWNER
 SUPPLIED. PLEASE KNOW, IF AN APPROPRIATE VALUE IS NOT
 ADJUSTED, ONE WILL BE ADJUSTED BY THE TABLES FROM THE
 FBC.
 FBC 108.3 ADMIN SECTION AS ADOPTED BY THE CITY OF WEST
 PALM BEACH USING THE MARSHAL'S & SWIFT GUIDE AT A MIN
 AND TABLES AS SET-FORTH IN THE BLDG CODE.
  
 17) NOTE: OK, SEE NEW NOTES.
  
 18) NOTE: OK, SIX BREAKERS SHOWN.
  
  
 *** NEW NOTES 2ND REVIEW ***
  
 19) NOTE: PLEASE SEE NEW MDP WHICH INDICATES AIC
 RATINGS AT 100K. IS THIS FOR ALL BREAKERS AS SHOWN AS
 NO MCB IS BEING SHOWN ON THIS MLO EQUIPMENT? PLEASE SEE
 THE COST RELATE TO EACH OF THESE AT 100K MAY OUTWEIGH
 THE COST OF A SINGLE MAIN AND SERIES RATED BRANCH
 BREAKERS?
 THIS IS ONLY BEING NOTED, IF SHOWN AT 100K THEN, 100K
 RATED BREAKERS WILL BE REQUIRED.
  
 20) NOTE: PLEASE CLARIFY HOW THE LIGHTING PANELS ARE
 FED. PLEASE SEE RISER DOES NOT INDICATE HOW AND WHERE
 THESE ARE FED FROM. PLEASE SEE PANELS 1F AND 2F DO NOT
 INDICATE ANY CIRCUITS TO THESE PANELS. ??
 PLEASE CLARIFY WHERE THE LOADS ARE BEING ASSIGNED AS
 THE LOADS ON THE MDP DO NOT INDICATE ANY OF THE
 LIGHTING.
 220/215/215.3/230.42 ETC.
 PLEASE SEE THIS IS EXPANDED FROM PREVIOUS NOTE ABOVE
 NOTE #9.
  
 21) NOTE: PLEASE SEE SUBMITTED ELECTRICAL PLANS ARE
 ALSO IN SETS WHICH ARE DONE BY THIS ARCHITECT? PLEASE
 CLARIFY WHICH PLANS ARE TO BE REVIEWED AS THESE ARE NOT
 THE SAME AND ONLY THE DESIGNER OF RECORD FOR ELECTRICAL
 SHOULD BE SUBMITTING THESE.
 FBC 106.1
  
 22) NOTE: PLEASE SEE 210.8B3 WHICH WAS NOT NOTED ON
 PREVIOUS REVIEW; HOWEVER PREVIOUS REVIEWED PLANS WERE
 NOT SUBMITTED BACK FOR REVIEW OF REFERENCE AS
 PREVIOUSLY REQUESTED ON THE FIRST REVIEW, SO IT IS NOT
 KNOW IF THE PREVIOUS PLANS SHOWED COMPLIANCE WITH THIS.
 PLEASE SEE AND OUTLET IS BEING SHOWN AS 220V WHICH
 APPEARS TO BE FOR A STOVE.
 PLEASE INDICATE IF THE EXISTING RECEPTACLES IN THIS
 ROOM MEET THE REQUIREMENTS FOR GFI PROTECTION OR IF NEW
 DEVICES WILL BE INSTALLED.
  
 23) NOTE: PLEASE SEE AS NOTE ABOVE IN PREVIOUS REVIEW
 NOTE #9, PLEASE SEE THE NEW MDP, SHOW LOADS FOR THE
 600A MLO, HOUSE PANEL AND "? PANEL" AS BLANK FOR THE
 LOADS. THE LOADS ON THE MDP DIFFER FROM THE LOADS ON
 E-7
 106.1.2, 106.3.5.1.2 ADMIN SECTION OF THE FBC FOR
 ADDITIONAL INFORMATION NEEDED.
  
 24) NOTE: PLESE SEEFS 553.80(2)(B), THIS IS ONLY
 GIVEN AS A NOTICE AT THIS TIME.
  
 ** ONCE AGAIN, PLEASE KNOW AT THIS TIME, THERE ARE
 ITEMS NOT YET SHOWN WHICH CAN NOT BE REVIEWED AT THIS
 TIME WHICH MAY CREATE NEW COMMENTS ON NEXT REVIEW.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH