Plan Review Notes
Plan Review Notes For Permit 06101118
Permit Number 06101118
Review Stop M
Sequence Number 1
Notes
Date Text
2006-11-06 13:30:27DENIED:
 1.THE ARCHITECTURAL PLANS DO NOT INDICATE WHAT THE
 FIRE RESISTANCE RATING OF THE WALL PENETRATIONS INTO
 THE "SERVER ROOM" .
  
 2.PLAN SHEET M-1 PENETRATION INTO THE "SERVER ROOM"
 DOES NOT INDICATE IF A FIRE DAMPER IS INSTALLED OR NOT.
 PLEASE INDICATE ALL FIRE DAMPERS & ACCESS DOORS FOR NEW
 AND EXISTING FIRE DAMPERS PER 2004 FMC 607.8.
  
 3.NO COMBUSTIBLES ALLOWED ABOVE THE CEILING IN THE
 RETURN AIR PLENUM.
  
 4.PLEASE INDICATE IF ALL THE EQUIPMENT IS EXISTING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (5610805-6719 OR E-MAIL [email protected]