| Plan Review Notes For Permit 06101118 |
| Permit Number |
06101118 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-06 13:30:27 | DENIED: | | | 1.THE ARCHITECTURAL PLANS DO NOT INDICATE WHAT THE | | | FIRE RESISTANCE RATING OF THE WALL PENETRATIONS INTO | | | THE "SERVER ROOM" . | | | | | | 2.PLAN SHEET M-1 PENETRATION INTO THE "SERVER ROOM" | | | DOES NOT INDICATE IF A FIRE DAMPER IS INSTALLED OR NOT. | | | PLEASE INDICATE ALL FIRE DAMPERS & ACCESS DOORS FOR NEW | | | AND EXISTING FIRE DAMPERS PER 2004 FMC 607.8. | | | | | | 3.NO COMBUSTIBLES ALLOWED ABOVE THE CEILING IN THE | | | RETURN AIR PLENUM. | | | | | | 4.PLEASE INDICATE IF ALL THE EQUIPMENT IS EXISTING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (5610805-6719 OR E-MAIL [email protected] |
|