| 2006-12-11 12:30:14 | *****DENIED***** |
| | |
| | |
| | |
| | 1.THEADDRESSED STRUCTURE 5827 CORPORATE WAY IS |
| | REFERENCED IN THE TITLE BLOCK OF THE PLANS AS PALM |
| | BEACH COUNTY.THE CORRECT JURISDICTION IS THE CITY OF |
| | WEST PALM BEACH. |
| | |
| | 2.NFPA 101-2003 EDITION AND THE FLORIDA FIRE |
| | PREVENTION CODE-2004 EDITION CODE SHALL BE REFERENCED. |
| | |
| | 3.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS |
| | SHALL COMPLY WITH NFPA 241.COMBUSTIBLE WASTE, DUST , |
| | AND DEBRIS SHALL BE REMOVED FROM THE SITE DAILY OR MORE |
| | FREQUENTLY AS NECESSARY FOR SAFE OPERATIONS. |
| | |
| | 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| | PROPERTY OR VICINITY THEROF. |
| | |
| | 5.IN ORDER TO CONDUCT A COMPLETE FIRE PLAN REVIEW, |
| | THE FOLLOWING INFORMATION IS NEEDED:A) BUILDING |
| | CONSTRUCTION, B) TYPE OF OCCUPANCY, C) NUMBER OF |
| | FLOORS, D) INTERIOR FINISH CLASSIFICATION, E)THE |
| | BUILDING'S FIRE PROTECTION SYSTEMS I.E. FIRE ALARM |
| | AND/OR FIRE SPRINKLER SYSTEMANDF) ANY OTHER |
| | PERTINENT INFORMATION |
| | |
| | 6.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM |
| | IS/ARE MODIFIED DUE TO THE SCOPE OF WORK, SUBMIT |
| | SEPARATE SHOP DRAWINGS. |
| | |
| | 7.PROVIDE A LIFE SAFETY PLAN SHEET TO INCLUDE ALL |
| | COMMON PATHS OF TRAVEL TO THE EXITS AND THE LOCATION OF |
| | THE FIRE EXTINGUSHERS AT DISTANCES WHICH SATISFY THE |
| | 75' TRAVEL DISTANCE REQUIREMENT. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |