| Date |
Text |
| 2006-11-27 13:23:14 | BUILDING PLAN REVIEW |
| | PERMIT: 06101118 |
| | ADD: 5827 CORPORATE WAY SUITES 100/200 |
| | CONT: BISHOP CONSTRUCTION |
| | TEL: (561)312-1024 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3)110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | 2004 FLORIDA BUILDING CODE BUILDING |
| | 2004 EXISTING BUILDING CODE BUILDING |
| | LEVEL OF ALTERATION? |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | PLEASE PROVIDE WHAT TYPE OF STOCK WILL BE STORED? IN |
| | CARDBOARD BOXES, WOOD CRATES? |
| | THE TYPE OF RACKS AND HEIGTH OF RACKS? |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | G ) NUMBER OF UNITS |
| | H ) NUMBER OF FLOORS |
| | ROOMS |
| | I) SQ. FT. FOOTPRINT |
| | I SQ. FT. UNDER ROOF (TOTAL) |
| | J ) FLOOD ZONE |
| | K) FLOOD ELEVATION |
| | |
| | 4) PLEASE PROVIDE ADDITIONAL INFORMATION, |
| | 106.1.2*IS THIS A SINGLE TENANT FOR THE BUILDING? |
| | |
| | 5) PLANS DO NOT PROVIDE INFORMATION IF THE BUILDING IS |
| | FIRE SPRINKLERED? |
| | IF THE BUILDING IS NOT FIRE SPRINKLERED SHOW COMPLIANCE |
| | WITH; |
| | AREA OF RESCUE ASSISTANCE. AN AREA, WHICH HAS DIRECT |
| | ACCESS TO AN EXIT, |
| | THERE PEOPLE WHO ARE UNABLE TO USE STAIRS MAY REMAIN |
| | TEMPORARILY IN SAFETY TO |
| | AWAIT FURTHER INSTRUCTIONS OR ASSISTANCE DURING |
| | EMERGENCY EVACUATION. |
| | 11-4.3.10 EGRESS. |
| | ACCESSIBLE ROUTES SERVING ANY ACCESSIBLE SPACE OR |
| | ELEMENT SHALL ALSO SERVE AS A MEANS OF EGRESS FOR |
| | EMERGENCIES OR CONNECT TO AN ACCESSIBLE AREA OF RESCUE |
| | ASSISTANCE. |
| | |
| | 11-4.3.11 AREAS OF RESCUE ASSISTANCE. |
| | |
| | 11-4.3.11.1 LOCATION AND CONSTRUCTION. |
| | AN AREA OF RESCUE ASSISTANCE SHALL BE ONE OF THE |
| | FOLLOWING: |
| | (1)A PORTION OF A STAIRWAY LANDING WITHIN A |
| | SMOKEPROOF ENCLOSURE (COMPLYING WITH LOCAL |
| | REQUIREMENTS). |
| | (2)A PORTION OF AN EXTERIOR EXIT BALCONY LOCATED |
| | IMMEDIATELY ADJACENT TO AN EXIT STAIRWAY WHEN THE |
| | BALCONY COMPLIES WITH LOCAL REQUIREMENTS FOR EXTERIOR |
| | EXIT BALCONIES. OPENINGS TO THE INTERIOR OF THE |
| | BUILDING LOCATED WITHIN 20 FEET (6 M) OF THE AREA OF |
| | RESCUE ASSISTANCE SHALL BE PROTECTED WITH FIRE |
| | ASSEMBLIES HAVING A ? HOUR FIRE PROTECTION RATING. (3) |
| | A PORTION OF A 1-HOUR FIRE-RESISTIVE CORRIDOR |
| | (COMPLYING WITH LOCAL REQUIREMENTS FOR FIRE-RESISTIVE |
| | CONSTRUCTION AND FOR OPENINGS) LOCATED IMMEDIATELY |
| | ADJACENT TO AN EXIT ENCLOSURE. |
| | (4)A VESTIBULE LOCATED IMMEDIATELY ADJACENT TO AN |
| | EXIT ENCLOSURE AND CONSTRUCTED TO THE SAME |
| | FIRE-RESISTIVE STANDARDS AS REQUIRED FOR CORRIDORS AND |
| | OPENINGS. |
| | (5)A PORTION OF A STAIRWAY LANDING WITHIN AN EXIT |
| | ENCLOSURE WHICH IS VENTED TO THE EXTERIOR AND IS |
| | SEPARATED FROM THE INTERIOR OF THE BUILDING WITH NOT |
| | LESS THAN 1-HOUR FIRE-RESISTIVE DOORS. |
| | (6)WHEN APPROVED BY THE APPROPRIATE LOCAL |
| | AUTHORITY, AN AREA OR A ROOM WHICH IS SEPARATED FROM |
| | OTHER PORTIONS OF THE BUILDING BY A SMOKE BARRIER. |
| | SMOKE BARRIERS SHALL HAVE A FIRE-RESISTIVE RATING OF |
| | NOT LESS THAN ONE HOUR AND SHALL COMPLETELY ENCLOSE THE |
| | AREA OR ROOM. DOORS IN THE SMOKE BARRIER SHALL BE |
| | TIGHT-FITTING SMOKE-AND-DRAFT CONTROL ASSEMBLIES HAVING |
| | A FIRE PROTECTION RATING OF NOT LESS THAN 20 MINUTES |
| | AND SHALL BE SELF-CLOSING OR AUTOMATIC CLOSING. THE |
| | AREA OR ROOM SHALL BE PROVIDED WITH AN EXIT DIRECTLY TO |
| | AN EXIT ENCLOSURE. WHERE THE ROOM OR AREA EXITS INTO AN |
| | EXIT ENCLOSURE WHICH IS REQUIRED TO BE OF MORE THAN |
| | 1-HOUR FIRE-RESISTIVE CONSTRUCTION, THE ROOM OR AREA |
| | SHALL HAVE THE SAME FIRE-RESISTIVE CONSTRUCTION, |
| | INCLUDING THE SAME OPENING PROTECTION, AS REQUIRED FOR |
| | THE ADJACENT EXIT ENCLOSURE. |
| | (7)AN ELEVATOR LOBBY WHEN ELEVATOR SHAFTS AND |
| | ADJACENT LOBBIES ARE PRESSURIZED AS REQUIRED FOR |
| | SMOKEPROOF ENCLOSURES BY LOCAL REGULATIONS AND WHEN |
| | COMPLYING WITH REQUIREMENTS HEREIN FOR SIZE, |
| | COMMUNICATION, AND SIGNAGE. SUCH PRESSURIZATION SYSTEM |
| | SHALL BE ACTIVATED BY SMOKE DETECTORS ON EACH FLOOR |
| | LOCATED IN A MANNER APPROVED BY THE APPROPRIATE LOCAL |
| | AUTHORITY. PRESSURIZATION EQUIPMENT AND ITS DUCT WORK |
| | WITHIN THE BUILDING SHALL BE SEPARATED FROM OTHER |
| | PORTIONS OF THE BUILDING BY A MINIMUM 2-HOUR |
| | FIRE-RESISTIVE CONSTRUCTION. |
| | |
| | 11-4.3.11.2 SIZE. |
| | EACH AREA OF RESCUE ASSISTANCE SHALL PROVIDE AT LEAST |
| | TWO ACCESSIBLE AREAS EACH BEING NOT LESS THAN 30 INCHES |
| | BY 48 INCHES (760 MM BY 1220 MM). THE AREA OF RESCUE |
| | ASSISTANCE SHALL NOT ENCROACH ON ANY REQUIRED EXIT |
| | WIDTH. THE TOTAL NUMBER OF SUCH 30-INCH BY 48-INCH (760 |
| | MM BY 1220 MM) AREAS PER STORY SHALL BE NOT LESS THAN |
| | ONE FOR EVERY 200 PERSONS OF CALCULATED OCCUPANT LOAD |
| | SERVED BY THE AREA OF RESCUE ASSISTANCE. EXCEPTION: THE |
| | APPROPRIATE LOCAL AUTHORITY MAY REDUCE THE MINIMUM |
| | NUMBER OF 30-INCH BY 48-INCH (760 MM BY 1220 MM) AREAS |
| | TO ONE FOR EACH AREA OF RESCUE ASSISTANCE ON FLOORS |
| | WHERE THE OCCUPANT LOAD IS LESS THAN 200. |
| | |
| | 11-4.3.11.3 STAIRWAY WIDTH. |
| | EACH STAIRWAY ADJACENT TO AN AREA OF RESCUE ASSISTANCE |
| | SHALL HAVE A MINIMUM CLEAR WIDTH OF 48 (1220 MM) INCHES |
| | BETWEEN HANDRAILS. |
| | |
| | 11-4.3.11.4 TWO-WAY COMMUNICATION. |
| | A METHOD OF TWO-WAY COMMUNICATION, WITH BOTH VISIBLE |
| | AND AUDIBLE SIGNALS, SHALL BE PROVIDED BETWEEN EACH |
| | AREA OF RESCUE ASSISTANCE AND THE PRIMARY ENTRY. THE |
| | FIRE DEPARTMENT OR APPROPRIATE LOCAL AUTHORITY MAY |
| | APPROVE A LOCATION OTHER THAN THE PRIMARY ENTRY. |
| | |
| | 11-4.3.11.5 IDENTIFICATION. |
| | EACH AREA OF RESCUE ASSISTANCE SHALL BE IDENTIFIED BY A |
| | SIGN, WHICH STATES ?AREA OF RESCUE ASSISTANCE? AND |
| | DISPLAYS THE INTERNATIONAL SYMBOL OF ACCESSIBILITY. THE |
| | SIGN SHALL BE ILLUMINATED WHEN EXIT SIGN ILLUMINATION |
| | IS REQUIRED. SIGNAGE SHALL ALSO BE INSTALLED AT ALL |
| | INACCESSIBLE EXITS AND WHERE OTHERWISE NECESSARY TO |
| | CLEARLY INDICATE THE DIRECTION TO AREAS OF RESCUE |
| | ASSISTANCE. IN EACH AREA OF RESCUE ASSISTANCE, |
| | INSTRUCTIONS ON THE USE OF THE AREA UNDER EMERGENCY |
| | CONDITIONS SHALL BE POSTED ADJOINING THE TWO-WAY |
| | COMMUNICATION SYSTEM. |
| | |
| | 6) NOTE CODE VIOLATION, NO WORK BEING COMPLETED IN THE |
| | RESTROOMS, 1ST FLOOR & 2ND FLOOR RESTROOM DOORS |
| | 11-4.13.7 DOORS IN SERIES. |
| | |
| | 7) NEW DOOR# 4 TO WAREHOUSEDOESN'T MEET THE |
| | ACCESSIBILITY REQUIREMENTS: |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARANCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARANCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 8) SHEET A-3RETAIL AREA, ROOMS ARE NOT LABELED, DOOR |
| | IS LABELED EXISTING TO REMAIN, THEN NEXT LINE REMOVED? |
| | |
| | 9)SHEET A-3 IN THE RECEIVING ROOM, SERVER ROOM |
| | SHIPPING ANG PACKING ROOM THE EXTERIOR WALLS INDICATE |
| | EXISTING DOOR OPENINGS ARE |
| | TO BE FRAMED IN, NO SECTIONS OR INFORMATION IS PROVIDED |
| | AS TO WHAT TYPE OF MATERIALS ARE TO BE USED? TABLE |
| | 601. |
| | |
| | 10A) A-3 THE RECEIVING ROOM INDICATES A EXTERIOR ROLL |
| | UP DOOR WILL BE INSTALLED, PLEASE PROVIDE THE FOLLOWING |
| | INFORMATION: FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) ROLL UP DOOR |
| | |
| | 10B)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 10C)W P B ADMINISTRTIVE CODE 106.3.3* |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 11) SHEET A-4 PRIVATE BATHROOM: |
| | 11-4.1.3 (11) TOILET FACILITIES. IF TOILET ROOMS ARE |
| | PROVIDED, |
| | THEN EACH PUBLIC AND COMMON USE TOILET ROOM SHALL |
| | COMPLY |
| | WITH SECTION 11-4.22 . OTHER TOILET ROOMS PROVIDED FOR |
| | THE |
| | USE OF OCCUPANTS OF SPECIFIC SPACES (I.E., A PRIVATE |
| | TOILET |
| | ROOM FOR THE OCCUPANT OF A PRIVATE OFFICE) SHALL BE |
| | ADAPTABLE. |
| | IF BATHING ROOMS ARE PROVIDED, THEN EACH PUBLIC AND |
| | COMMON |
| | USE BATHROOM SHALL COMPLY WITH SECTION 11-4.23 . |
| | ACCESSIBLE |
| | TOILET ROOMS AND BATHING FACILITIES SHALL BE ON AN |
| | ACCESSIBLE ROUTE. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |