Plan Review Notes
Plan Review Notes For Permit 06101118
Permit Number 06101118
Review Stop B
Sequence Number 1
Notes
Date Text
2006-11-27 13:23:14BUILDING PLAN REVIEW
 PERMIT: 06101118
 ADD: 5827 CORPORATE WAY SUITES 100/200
 CONT: BISHOP CONSTRUCTION
 TEL: (561)312-1024
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 2004 FLORIDA BUILDING CODE BUILDING
 2004 EXISTING BUILDING CODE BUILDING
 LEVEL OF ALTERATION?
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 PLEASE PROVIDE WHAT TYPE OF STOCK WILL BE STORED? IN
 CARDBOARD BOXES, WOOD CRATES?
 THE TYPE OF RACKS AND HEIGTH OF RACKS?
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 G ) NUMBER OF UNITS
 H ) NUMBER OF FLOORS
 ROOMS
 I) SQ. FT. FOOTPRINT
 I SQ. FT. UNDER ROOF (TOTAL)
 J ) FLOOD ZONE
 K) FLOOD ELEVATION
  
 4) PLEASE PROVIDE ADDITIONAL INFORMATION,
 106.1.2*IS THIS A SINGLE TENANT FOR THE BUILDING?
  
 5) PLANS DO NOT PROVIDE INFORMATION IF THE BUILDING IS
 FIRE SPRINKLERED?
 IF THE BUILDING IS NOT FIRE SPRINKLERED SHOW COMPLIANCE
 WITH;
 AREA OF RESCUE ASSISTANCE. AN AREA, WHICH HAS DIRECT
 ACCESS TO AN EXIT,
 THERE PEOPLE WHO ARE UNABLE TO USE STAIRS MAY REMAIN
 TEMPORARILY IN SAFETY TO
 AWAIT FURTHER INSTRUCTIONS OR ASSISTANCE DURING
 EMERGENCY EVACUATION.
 11-4.3.10 EGRESS.
 ACCESSIBLE ROUTES SERVING ANY ACCESSIBLE SPACE OR
 ELEMENT SHALL ALSO SERVE AS A MEANS OF EGRESS FOR
 EMERGENCIES OR CONNECT TO AN ACCESSIBLE AREA OF RESCUE
 ASSISTANCE.
  
 11-4.3.11 AREAS OF RESCUE ASSISTANCE.
  
 11-4.3.11.1 LOCATION AND CONSTRUCTION.
 AN AREA OF RESCUE ASSISTANCE SHALL BE ONE OF THE
 FOLLOWING:
 (1)A PORTION OF A STAIRWAY LANDING WITHIN A
 SMOKEPROOF ENCLOSURE (COMPLYING WITH LOCAL
 REQUIREMENTS).
 (2)A PORTION OF AN EXTERIOR EXIT BALCONY LOCATED
 IMMEDIATELY ADJACENT TO AN EXIT STAIRWAY WHEN THE
 BALCONY COMPLIES WITH LOCAL REQUIREMENTS FOR EXTERIOR
 EXIT BALCONIES. OPENINGS TO THE INTERIOR OF THE
 BUILDING LOCATED WITHIN 20 FEET (6 M) OF THE AREA OF
 RESCUE ASSISTANCE SHALL BE PROTECTED WITH FIRE
 ASSEMBLIES HAVING A ? HOUR FIRE PROTECTION RATING. (3)
 A PORTION OF A 1-HOUR FIRE-RESISTIVE CORRIDOR
 (COMPLYING WITH LOCAL REQUIREMENTS FOR FIRE-RESISTIVE
 CONSTRUCTION AND FOR OPENINGS) LOCATED IMMEDIATELY
 ADJACENT TO AN EXIT ENCLOSURE.
 (4)A VESTIBULE LOCATED IMMEDIATELY ADJACENT TO AN
 EXIT ENCLOSURE AND CONSTRUCTED TO THE SAME
 FIRE-RESISTIVE STANDARDS AS REQUIRED FOR CORRIDORS AND
 OPENINGS.
 (5)A PORTION OF A STAIRWAY LANDING WITHIN AN EXIT
 ENCLOSURE WHICH IS VENTED TO THE EXTERIOR AND IS
 SEPARATED FROM THE INTERIOR OF THE BUILDING WITH NOT
 LESS THAN 1-HOUR FIRE-RESISTIVE DOORS.
 (6)WHEN APPROVED BY THE APPROPRIATE LOCAL
 AUTHORITY, AN AREA OR A ROOM WHICH IS SEPARATED FROM
 OTHER PORTIONS OF THE BUILDING BY A SMOKE BARRIER.
 SMOKE BARRIERS SHALL HAVE A FIRE-RESISTIVE RATING OF
 NOT LESS THAN ONE HOUR AND SHALL COMPLETELY ENCLOSE THE
 AREA OR ROOM. DOORS IN THE SMOKE BARRIER SHALL BE
 TIGHT-FITTING SMOKE-AND-DRAFT CONTROL ASSEMBLIES HAVING
 A FIRE PROTECTION RATING OF NOT LESS THAN 20 MINUTES
 AND SHALL BE SELF-CLOSING OR AUTOMATIC CLOSING. THE
 AREA OR ROOM SHALL BE PROVIDED WITH AN EXIT DIRECTLY TO
 AN EXIT ENCLOSURE. WHERE THE ROOM OR AREA EXITS INTO AN
 EXIT ENCLOSURE WHICH IS REQUIRED TO BE OF MORE THAN
 1-HOUR FIRE-RESISTIVE CONSTRUCTION, THE ROOM OR AREA
 SHALL HAVE THE SAME FIRE-RESISTIVE CONSTRUCTION,
 INCLUDING THE SAME OPENING PROTECTION, AS REQUIRED FOR
 THE ADJACENT EXIT ENCLOSURE.
 (7)AN ELEVATOR LOBBY WHEN ELEVATOR SHAFTS AND
 ADJACENT LOBBIES ARE PRESSURIZED AS REQUIRED FOR
 SMOKEPROOF ENCLOSURES BY LOCAL REGULATIONS AND WHEN
 COMPLYING WITH REQUIREMENTS HEREIN FOR SIZE,
 COMMUNICATION, AND SIGNAGE. SUCH PRESSURIZATION SYSTEM
 SHALL BE ACTIVATED BY SMOKE DETECTORS ON EACH FLOOR
 LOCATED IN A MANNER APPROVED BY THE APPROPRIATE LOCAL
 AUTHORITY. PRESSURIZATION EQUIPMENT AND ITS DUCT WORK
 WITHIN THE BUILDING SHALL BE SEPARATED FROM OTHER
 PORTIONS OF THE BUILDING BY A MINIMUM 2-HOUR
 FIRE-RESISTIVE CONSTRUCTION.
  
 11-4.3.11.2 SIZE.
 EACH AREA OF RESCUE ASSISTANCE SHALL PROVIDE AT LEAST
 TWO ACCESSIBLE AREAS EACH BEING NOT LESS THAN 30 INCHES
 BY 48 INCHES (760 MM BY 1220 MM). THE AREA OF RESCUE
 ASSISTANCE SHALL NOT ENCROACH ON ANY REQUIRED EXIT
 WIDTH. THE TOTAL NUMBER OF SUCH 30-INCH BY 48-INCH (760
 MM BY 1220 MM) AREAS PER STORY SHALL BE NOT LESS THAN
 ONE FOR EVERY 200 PERSONS OF CALCULATED OCCUPANT LOAD
 SERVED BY THE AREA OF RESCUE ASSISTANCE. EXCEPTION: THE
 APPROPRIATE LOCAL AUTHORITY MAY REDUCE THE MINIMUM
 NUMBER OF 30-INCH BY 48-INCH (760 MM BY 1220 MM) AREAS
 TO ONE FOR EACH AREA OF RESCUE ASSISTANCE ON FLOORS
 WHERE THE OCCUPANT LOAD IS LESS THAN 200.
  
 11-4.3.11.3 STAIRWAY WIDTH.
 EACH STAIRWAY ADJACENT TO AN AREA OF RESCUE ASSISTANCE
 SHALL HAVE A MINIMUM CLEAR WIDTH OF 48 (1220 MM) INCHES
 BETWEEN HANDRAILS.
  
 11-4.3.11.4 TWO-WAY COMMUNICATION.
 A METHOD OF TWO-WAY COMMUNICATION, WITH BOTH VISIBLE
 AND AUDIBLE SIGNALS, SHALL BE PROVIDED BETWEEN EACH
 AREA OF RESCUE ASSISTANCE AND THE PRIMARY ENTRY. THE
 FIRE DEPARTMENT OR APPROPRIATE LOCAL AUTHORITY MAY
 APPROVE A LOCATION OTHER THAN THE PRIMARY ENTRY.
  
 11-4.3.11.5 IDENTIFICATION.
 EACH AREA OF RESCUE ASSISTANCE SHALL BE IDENTIFIED BY A
 SIGN, WHICH STATES ?AREA OF RESCUE ASSISTANCE? AND
 DISPLAYS THE INTERNATIONAL SYMBOL OF ACCESSIBILITY. THE
 SIGN SHALL BE ILLUMINATED WHEN EXIT SIGN ILLUMINATION
 IS REQUIRED. SIGNAGE SHALL ALSO BE INSTALLED AT ALL
 INACCESSIBLE EXITS AND WHERE OTHERWISE NECESSARY TO
 CLEARLY INDICATE THE DIRECTION TO AREAS OF RESCUE
 ASSISTANCE. IN EACH AREA OF RESCUE ASSISTANCE,
 INSTRUCTIONS ON THE USE OF THE AREA UNDER EMERGENCY
 CONDITIONS SHALL BE POSTED ADJOINING THE TWO-WAY
 COMMUNICATION SYSTEM.
  
 6) NOTE CODE VIOLATION, NO WORK BEING COMPLETED IN THE
 RESTROOMS, 1ST FLOOR & 2ND FLOOR RESTROOM DOORS
 11-4.13.7 DOORS IN SERIES.
  
 7) NEW DOOR# 4 TO WAREHOUSEDOESN'T MEET THE
 ACCESSIBILITY REQUIREMENTS:
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 8) SHEET A-3RETAIL AREA, ROOMS ARE NOT LABELED, DOOR
 IS LABELED EXISTING TO REMAIN, THEN NEXT LINE REMOVED?
  
 9)SHEET A-3 IN THE RECEIVING ROOM, SERVER ROOM
 SHIPPING ANG PACKING ROOM THE EXTERIOR WALLS INDICATE
 EXISTING DOOR OPENINGS ARE
 TO BE FRAMED IN, NO SECTIONS OR INFORMATION IS PROVIDED
 AS TO WHAT TYPE OF MATERIALS ARE TO BE USED? TABLE
 601.
  
 10A) A-3 THE RECEIVING ROOM INDICATES A EXTERIOR ROLL
 UP DOOR WILL BE INSTALLED, PLEASE PROVIDE THE FOLLOWING
 INFORMATION: FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) ROLL UP DOOR
  
 10B)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10C)W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 11) SHEET A-4 PRIVATE BATHROOM:
 11-4.1.3 (11) TOILET FACILITIES. IF TOILET ROOMS ARE
 PROVIDED,
 THEN EACH PUBLIC AND COMMON USE TOILET ROOM SHALL
 COMPLY
 WITH SECTION 11-4.22 . OTHER TOILET ROOMS PROVIDED FOR
 THE
 USE OF OCCUPANTS OF SPECIFIC SPACES (I.E., A PRIVATE
 TOILET
 ROOM FOR THE OCCUPANT OF A PRIVATE OFFICE) SHALL BE
 ADAPTABLE.
 IF BATHING ROOMS ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON
 USE BATHROOM SHALL COMPLY WITH SECTION 11-4.23 .
 ACCESSIBLE
 TOILET ROOMS AND BATHING FACILITIES SHALL BE ON AN
 ACCESSIBLE ROUTE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved