2007-10-30 12:48:12TRUSS PACKAGE BUILDING REVIEW CHECKLIST.
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72FOR STRUCTURAL CONNECTORS HU214-3AND HU210-2
 ATTACHED DIRECTLY TO MASONRY WALL TO VERIFY COMPLIANCE
 WITH THE CALCULATED LOADS FOR GIRDER TRUSS FG06.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.ENGINEER OF
 RECORD TO REVIEW AND APPROVE IN WRITING PRODUCT
 APPROVAL PRIOR TO SUBMITTAL TO THIS OFFICE. SEC.
 106.3.3 CITY AMENDMENTSTO FBC 2004.
  
 2- TRUSSES FG01 AND FG05 WERE DESIGNED FOR 10PSF LOAD
 AT TCDL.STRUCTURAL PLANS CALL FOR 20PSF DEAD LOAD.
 REVISE AS REQUIRED.
  
 3- REVISED TRUSS PACKAGE TO BE REVIEWED AND APPROVED BY
 THE ENGINEER OF RECORD PRIOR TO SUBMITTAL TO THIS
 OFFICE.
  
 4- IF PROVIDING COVER OR INDEX SHEET TO AVOID SIGNING
 AND SEALING ALL INDIVIDUAL TRUSSES, THEN ALL
 INFORMATION REQUIRED BY SEC. 61G15-31003 SHALL BE
 SUBMITTED. THIS PACKAGE IS MISSING STRUCTURAL ENGINEER
 OF RECORD INFORMATION, PROPER IDENTIFICATION OF PROJECT
 (AND ADDRESS SHOWN IS NOT CORRECT) AND A CLEARNAMING
 AND NUMBERING SYSTEM.INDIVIDUAL SHEETS ARE NOT
 NUMBERED, WHICH ALLOWS TO MATCH INDEX SHEET.
  
 5- TRUSS LAYOUT IS NOT SIGNED AND SEALED AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 6- CLARIFY WHY THE ATTIC LIVE LOAD IS NONCONCURRENT
 WITH ANY OTHER LIVE LOADS IF FBC 2004 TABLE 1607.1
 REQUIRES ALL MINIMUM LIVE LOADS TO BE INCLUDED IN THE
 DESIGN.CLARIFY WHICH ARE THE OTHER NONCONCURRENT LIVE
 LOADS.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 7- THIS PROJECT HAS A RESIDENT INSPECTOR, THEREFORE 3
 COMPLETE SETS OF TRUSS DRAWINGS ARE REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712