2007-02-09 07:42:36PASSED/PROVISO:
 DELETE THE CLEANOUT DOWNSTREAM OF THE FIRST (4S) RISER
 IN THE BUILDING. THIS CLEANOUT IS SHOWN INCORRECTLY AND
 DOES NOT GUIDE THE SEWAGE OR WASTE WITH THE FLOW AS
 REQUIRED IN SECTION 706.3. A REVISION WILL BE REQUIRED
 FOR SHEETS P308 AND P402.