Plan Review Notes
Plan Review Notes For Permit 06101117
Permit Number 06101117
Review Stop P
Sequence Number 2
Notes
Date Text
2006-12-26 17:29:10DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 NOTE: FIRST PLAN REVIEW FOR APPLICATION
  
 **********FROM PREVIOUS REVIEW**********
  
 1. SHEETS DELETED. WILL BE SUBMITTED AT THE TIME OF
 APPLICATION SUBMITTAL PER RESPONSE.
  
 2. OK
  
 3. OK
 4. OK
 5. DELETED
 6. OK. NOT REQUIRED THIS BUILDING.
 7. OK
 8.OK
 9.OK
 10. OK
 11. OK. NOT REQUIRED THIS BUILDING.
 12. OK. NOT REQUIRED THIS BUILDING.
 13. OK. (UNIT LOCATION ONLY)
 14. OK. NOT REQUIRED THIS BUILDING.
 15. OK. NOT REQUIRED THIS BUILDING.
 16. OK. NOT REQUIRED FOR THIS BUILDING.
 17. OK. NOT REQUIRED FOR THIS BUILDING. (CHANGE FINISH
 SCHEDULE)
 18. OK. NOT REQUIRED FOR THIS BUILDING
 19. OK. NOT REQUIRED FOR THIS BUILDING.
 20. OK. NOT REQUIRED FOR THIS BUILDING.
 21. OK. NOT REQUIRED FOR THIS BUILDING.
 22. OK. NOT REQUIRED FOR THIS BUILDING.
 23. OK
 24. OK
 25. OK. NOT REQUIRED FOR THIS BUILDING
 26. OK
  
 27. SUBMIT A BUILDING DRAIN SANITARY
 RISER DIAGRAM ISOMETRIC THAT REFLECTS
 THE FLOOR PLAN FOR EACH BUILDING.
 SECTION 106.1.5.1.3. SHOW ALL PIPE
 SIZES, RISER LOCATIONS, TRAPS, VENTS,
 AND DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM.
 ****RESPONSE NOTED. SHOW CLEANOUTS REQUIRED BY SECTIONS
 708.3.1, 708.3.3 7 & 708.3.4. RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. TWO RISERS SHOWN AS 2S ON THE
 FLOOR PLAN ARE SHOWN AS 3S ON THE RISER DIAGRAM. THE
 CLEANOUT DOWNSTREAM OF THE FIRST RISER DOES NOT MEET
 THE CODE SECTION 706.3 FITTING INSTALLATION REQUIRED TO
 GUIDE THE WASTE & SEWAGE IN THE DIRECTION OF FLOW. THE
 CLEANOUT ALSO DOES NOT REFLECT THE FLOOR PLAN. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT THE TWO RISERS STILL DO NOT
 REFLECT THE FLOOR PLAN AND THE CLEANOUT STILL DOES NOT
 COMPLY WITH SECTION 706.3. NOW THE CLEANOUT WILL HAVE
 TO BE CHANGED ON THE FLOOR PLAN ALSO. SHT P308.
  
 28. OK
 29. OK. NOT REQUIRED THIS BUILDING
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 SUBMIT ONE SET OF PLANS FROM FIRST
 REVIEW FOR COMPARISON TO EXPEDITE 2ND
 REVIEW.
  
 **************NEW COMMENTS**************
  
 1B. OK
 2B. OK
 3B. OK
 4B. OK
 5B. OK
 6B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING
 INFORMATION:ALL INFORMATION WIIL BE SUBMITTED AT THE
 TIME OF APPLICATION FOR THE GAS PERMIT.
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]