| 2006-12-26 17:29:10 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | NOTE: FIRST PLAN REVIEW FOR APPLICATION |
| | |
| | **********FROM PREVIOUS REVIEW********** |
| | |
| | 1. SHEETS DELETED. WILL BE SUBMITTED AT THE TIME OF |
| | APPLICATION SUBMITTAL PER RESPONSE. |
| | |
| | 2. OK |
| | |
| | 3. OK |
| | 4. OK |
| | 5. DELETED |
| | 6. OK. NOT REQUIRED THIS BUILDING. |
| | 7. OK |
| | 8.OK |
| | 9.OK |
| | 10. OK |
| | 11. OK. NOT REQUIRED THIS BUILDING. |
| | 12. OK. NOT REQUIRED THIS BUILDING. |
| | 13. OK. (UNIT LOCATION ONLY) |
| | 14. OK. NOT REQUIRED THIS BUILDING. |
| | 15. OK. NOT REQUIRED THIS BUILDING. |
| | 16. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 17. OK. NOT REQUIRED FOR THIS BUILDING. (CHANGE FINISH |
| | SCHEDULE) |
| | 18. OK. NOT REQUIRED FOR THIS BUILDING |
| | 19. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 20. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 21. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 22. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 23. OK |
| | 24. OK |
| | 25. OK. NOT REQUIRED FOR THIS BUILDING |
| | 26. OK |
| | |
| | 27. SUBMIT A BUILDING DRAIN SANITARY |
| | RISER DIAGRAM ISOMETRIC THAT REFLECTS |
| | THE FLOOR PLAN FOR EACH BUILDING. |
| | SECTION 106.1.5.1.3. SHOW ALL PIPE |
| | SIZES, RISER LOCATIONS, TRAPS, VENTS, |
| | AND DFU'S AS THEY ACCUMULATE IN THE |
| | SYSTEM. |
| | ****RESPONSE NOTED. SHOW CLEANOUTS REQUIRED BY SECTIONS |
| | 708.3.1, 708.3.3 7 & 708.3.4. RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. TWO RISERS SHOWN AS 2S ON THE |
| | FLOOR PLAN ARE SHOWN AS 3S ON THE RISER DIAGRAM. THE |
| | CLEANOUT DOWNSTREAM OF THE FIRST RISER DOES NOT MEET |
| | THE CODE SECTION 706.3 FITTING INSTALLATION REQUIRED TO |
| | GUIDE THE WASTE & SEWAGE IN THE DIRECTION OF FLOW. THE |
| | CLEANOUT ALSO DOES NOT REFLECT THE FLOOR PLAN. SECTION |
| | 106.1.1. |
| | ****RESPONSE NOTED, BUT THE TWO RISERS STILL DO NOT |
| | REFLECT THE FLOOR PLAN AND THE CLEANOUT STILL DOES NOT |
| | COMPLY WITH SECTION 706.3. NOW THE CLEANOUT WILL HAVE |
| | TO BE CHANGED ON THE FLOOR PLAN ALSO. SHT P308. |
| | |
| | 28. OK |
| | 29. OK. NOT REQUIRED THIS BUILDING |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | SUBMIT ONE SET OF PLANS FROM FIRST |
| | REVIEW FOR COMPARISON TO EXPEDITE 2ND |
| | REVIEW. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. OK |
| | 2B. OK |
| | 3B. OK |
| | 4B. OK |
| | 5B. OK |
| | 6B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING |
| | INFORMATION:ALL INFORMATION WIIL BE SUBMITTED AT THE |
| | TIME OF APPLICATION FOR THE GAS PERMIT. |
| | |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |