Notes
Date Text
2006-11-17 14:05:36*** PROVISO ***
 1) UNITS(B1) UPPER AND LOWER, AND (C1) UPPER AND
 LOWER, RETURN AIR TRANSFER GRILLS TO MASTER BEDROOM
 SUITE NEED TO BE 14"X 8", SEE 2004 FBC/M 601.4.
  
 2) CLOTHES DRYER VENTS MAY NOT EXCEED THE
 MANUFACTURER'S SPECIFICATION'S, PLANS SHOW THAT UNIT
 (B1) UPPER, LOWER, AND ACCESSIBLE MAY EXCEED.
  
 3) AHU CLOSET DOORS NEED TO BE LOUVERED OR GRILLS NEED
 TO BE INSTALLED FOR RETURN AIR, SEE 2004 FBC/M 601.4.
  
 4) LAUNDRY ROOM DOORS NEED TO BE LOUVERED OR GRILLS
 NEED TO BE INSTALLED FOR COMBUSTION AIR, SEE 2004 FBC/M
 701.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.