2007-10-24 14:40:31PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) SEE PLAN PAGES M202, M203, AND M204. NEED THE
 CORRECT JOB ADDRESS IN THE TITLE BLOCK (455 CHEERFUL
 CT.), SEE W.P.B. AMEND. 106.1.3.
  
 2)SEE PLAN PAGES M202, M203, AND M204. KITCHEN
 EXHAUST HOOD MAY NOT DISCHARGE AT THE FRONT DOOR, SEE
 F.B.C./R R303.6 AND F.B.C./M 501.2.
  
 3)SEE PLAN PAGES M202 AND M203. BEDROOM SHOWS A
 "CROWN MODEL "SK" PASSIVE RETURN AIR SLEEVE". PLEASE
 SHOW SIZE OF OPENING AND SUBMIT MANUFACTURER'S
 SPECIFICATION'S. SEE F.B.C./M 601.4.
  
 4) SEE PLAN PAGE M203 (B1) LOWER FLOOR PLAN. 12X10
 SUPPLY AIR DUCT SHOWS A FIRE DAMPER NEAR THE AIR
 HANDLER, PLEASE EXPLAIN OR CORRECT. IF FIRE DAMPER IS
 TO BE INSTALLED SHOW A DETAIL ON PLAN FOR FIRE DAMPER
 INSTALLATION, SEE F.B.C./M 607.5.3.
  
 5) SEE PLAN PAGE M204. SHOWS ALL RETURN AIR TRANSFER
 GRILLS IN THE WRONG LOCATIONS AND THE CLOTHES DRYER
 VENT IN A CLOSET NOT NEAR THE DRYER (SEE YELLOW HIGH
 LIGHT ON PLANS), PLEASE CORRECT. SEE F.B.C. 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]