| Plan Review Notes For Permit 06101114 |
| Permit Number |
06101114 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-28 14:04:58 | ****DENIED**** | | | | | | | | | | | | 1.PLEASE VERIFY THE ADDRESS OF THIS BUILDING WITH | | | LILI URSA OF THECITY'S ADDRESSING DIVISION AT | | | 561-822-1239.THE NEW ADDRESS SHALL BE IN THE TITLE | | | BLOCK OF EACH SUBMITTED PLAN SHEET. | | | | | | 2.SHOW/DISPLAY THE NUMERICAL ADDRESS OF THE BUILDING | | | ON THE PROPER ELEVATION.AS PER WEST PALM BEACH CODE, | | | THOSE NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" | | | IN WIDTH.INDIVIDUAL APRTMENT/UNIT SHALL BE NO LESS | | | THAN 3" IN HEIGHT. | | | | | | 3..AS PER NFPA 101 - 10.2.8.1 -2003 EDITION, | | | INTERIOR FINISH FOR WALLS AND CEILINGS IN AN | | | UNSPRINKLERED BUILDING SHALL BE CLASS "A" OR CLASS | | | "B". | | | | | | 4.FIRE EXTINGUISHERS TO BE 2A-10BC RATED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|