2007-10-30 08:08:49TRUSS PACKAGE BUILDING REVIEW CHECKLIST.
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72FOR STRUCTURAL CONNECTORS HU214-3AND HU210-2
 ATTACHED DIRECTLY TO MASONRY WALL TO VERIFY COMPLIANCE
 WITH THE CALCULATED LOADS FOR GIRDER TRUSS FG02,FG09
 (NOTE: FG09 IS A 5 PLY TRUSS), FG10 (NOTE: FG10IS A 4
 PLY TRUSS).FG06 (SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.ENGINEER OF RECORD TO REVIEW AND APPROVE IN
 WRITING ALL PRODUCT APPROVALS PRIOR TO SUBMITTAL TO
 THIS OFFICE. SEC. 106.3.3 CITY AMENDMENTSTO FBC
 2004.
  
 2- STRUCTURAL ENGINEER OF RECORD NEEDS TO REVISE PLANS
 AS REQUIRED TO SHOW THE DESIGN LOADS REQUIRED BY TABLE
 1607.1 FBC 2004 FOR ASSEMBLY PART OF THE BUILDING,
 INCLUDING THE BALCONY AREA.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 3- ALLFLOOR TRUSSES NEED TO BE DESIGNED PER TABLE
 1607.1 FBC 2004 FOR DISTRIBUTED AND CONCENTRATED LIVE
 LOADS FOR ASSEMBLY PORTION OF THE BUILDING. AND, FOR
 BALCONY AREAS. REVISE AS REQUIRED. NOTE: VERIFY THAT
 SPECIFIEDCONNECTORS MEET THE CALCULATED LOADS TO
 AVOID DELAYS OR CONFLICTS.
  
 4- IF FLOOR TRUSSES ARE ALREADY INSTALLED, THEN
 ENGINEER NEEDS TO PROVIDE COMPLETE ENGINEERING PACKAGE
 TO SHOW HOW TRUSSES ARE REINFORCED TO RESIST ALL LOADS
 REQUIRED BY TABLE 1607.1 FBC 2004.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 5- REVISED TRUSS PACKAGE TO BE REVIEWED AND APPROVED BY
 THE ENGINEER OF RECORD PRIOR TO SUBMITTAL TO THIS
 OFFICE.
  
 6- IF PROVIDING COVER OR INDEX SHEET TO AVOID SIGNING
 AND SEALING ALL INDIVIDUAL TRUSSES, THEN ALL
 INFORMATION REQUIRED BY SEC. 61G15-31003 SHALL BE
 SUBMITTED. THIS PACKAGE IS MISSING STRUCTURAL ENGINEER
 OF RECORD INFORMATION, PROPER IDENTIFICATION OF PROJECT
 (AND ADDRESS SHOWN IS NOT CORRECT) AND A CLEARNAMING
 AND NUMBERING SYSTEM.INDIVIDUAL SHEETS ARE NOT
 NUMBERED, WHICH ALLOWS TO MATCH INDEX SHEET.
  
 7- TRUSS LAYOUT IS NOT SIGNED AND SEALED AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 8- CLARIFY WHY THE ATTIC LIVE LOAD IS NONCONCURRENT
 WITH ANY OTHER LIVE LOADS IF FBC 2004 TABLE 1607.1
 REQUIRES ALL MINIMUM LIVE LOADS TO BE INCLUDED IN THE
 DESIGN.CLARIFY WHICH ARE THE OTHER NONCONCURRENT LIVE
 LOADS.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 9- THIS PROJECT HAS A RESIDENT INSPECTOR, THEREFORE 3
 COMPLETE SETS OF TRUSS DRAWINGS ARE REQUIRED.
  
 10- PROVIDE COMPLETE ENGINEERING SPECS FOR BOLTING
 CRITERIA OF 4 AND 5 PLY GIRDERS AS REQUIRED ON TRUSS
 LAYOUT NOTES. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 11- ROOF TRUSSLAYOUTAT THE END WINGS OF THE
 BUILDING IS DIFFERENTTHAN THAT ONE SHOWN ON SHEET
 S-2. REVISE AS REQUIRED.
  
 12- UNABLE TO READ TRUSS HANGER FOR GIRDER TRUSS C15GA,
 C13 AND C11 TO VERIFY COMPLIANCE OF CONNECTOR WITH
 CALCULATED LOADS. PROVIDE CLEAR SPECIFICATIONS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712