| Plan Review Notes For Permit 06101113 |
| Permit Number |
06101113 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-12-29 08:36:45 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHTS P306, P403, AND FP306 SHOW CONFLICTING | | | INFORMATION. SHT P306 INDICATES A 3" FIRE LINE ENTERING | | | THE BUILDING AND CONNECTING TO THE DISTRIBUTION PIPING | | | FOR THE BUILDING. SHT P403 BUILDING WATER RISER | | | INDICATES THIS SAME LINE TO BE 1-1/2". SHT FP306 | | | INDICATES A SEPARATE FIRE SPRINKLER LINE AND STATES | | | "FIRE LINE, SEE CIVIL FOR CONT.". PLEASE CLARIFY AND | | | CORRELATE THE WATER RISER, THE FLOOR PLAN AND THE FIRE | | | PROTECTION SHEETS. | | | | | | 2. IF THE FIRE LINE IS TO BE CONNECTED TO THE | | | DISTRIBUTION POTABLE WATER IN THE BUILDING, BACKFLOW | | | PROTECTION IS REQUIRED UNDER SECTION 608. PLEASE | | | INDICATE THE METHOD OF PROTECTION AND VERIFY | | | ACCEPTABILITY OF THE SAME WITH THE FIRE PLAN REVIEWER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|