Plan Review Notes
Plan Review Notes For Permit 06101113
Permit Number 06101113
Review Stop P
Sequence Number 2
Notes
Date Text
2006-12-29 08:36:45DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHTS P306, P403, AND FP306 SHOW CONFLICTING
 INFORMATION. SHT P306 INDICATES A 3" FIRE LINE ENTERING
 THE BUILDING AND CONNECTING TO THE DISTRIBUTION PIPING
 FOR THE BUILDING. SHT P403 BUILDING WATER RISER
 INDICATES THIS SAME LINE TO BE 1-1/2". SHT FP306
 INDICATES A SEPARATE FIRE SPRINKLER LINE AND STATES
 "FIRE LINE, SEE CIVIL FOR CONT.". PLEASE CLARIFY AND
 CORRELATE THE WATER RISER, THE FLOOR PLAN AND THE FIRE
 PROTECTION SHEETS.
  
 2. IF THE FIRE LINE IS TO BE CONNECTED TO THE
 DISTRIBUTION POTABLE WATER IN THE BUILDING, BACKFLOW
 PROTECTION IS REQUIRED UNDER SECTION 608. PLEASE
 INDICATE THE METHOD OF PROTECTION AND VERIFY
 ACCEPTABILITY OF THE SAME WITH THE FIRE PLAN REVIEWER.
  