| 2007-01-03 16:06:44 | BUILDING REVIEW SECOND CHECKLIST: |
| | 1- REVISE ENERGY CALCULATIONS: |
| | A) AS REQUESTED ON PREVIOUS CHECKLIST, CALCULATIONS |
| | NEED TO BE DONE FOR THE WHOLE BUILDING, NOT FOR EACH |
| | UNIT AS REQUIRED BY SEC. 13-600.0 METHOD A OF FBC |
| | 2004. |
| | |
| | |
| | B) AS REQUESTED ON PREVIOUS CHECKLIST, ENGINEER TO |
| | PROVIDE ALL HIS INFORMATION AS REQUIREDBY CHAPTER 471 |
| | FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE SEC. |
| | 61G15-23.002. |
| | |
| | C) CALCULATIONS SUBMITTED FOR INDIVIDUAL UNITS HAVE |
| | THE FOLLOWING INCORRECT INFORMATION: |
| | * NUMBER OF BEDROOMS. |
| | ** SLAB ON GRADE TOTAL PERIMETER FEET. |
| | *** CLARIFY HOW ARE THESE CALCULATIONS DONE FOR |
| | WORST CASE SCENARIO IF THERE IS NOT SHEET SHOWING |
| | OPENINGS SUN EXPOSURE ORIENTATION. |
| | |
| | 2- REVISION CLOUDS ON SHEET A004 DON'T ALLOW THE OTHER |
| | INFORMATION TO BE LEGIBLE.REVISE AS REQUIRED. |
| | |
| | 3- SURVEY AND SITE PLAN SHOWN ON SHEETS A100, A101 AND |
| | A102 DON'T MATCH.ACCORDING TO THE RECORDED SURVEY, |
| | THERE IS AN ALLEY BY BUILDING C3. SITE PLAN SHOWS |
| | PARKING SPACES. REVISE AS REQUIRED. THIS COMMENT COULD |
| | NOT BE ADDREESED BEFORE BECASUE THIS IS THE FIRST TIME |
| | SURVEY IS SUBMITTED FOR REVIEW. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) UNIT ENTRY DOOR: DRAWINGS SUBMITTED ARE FOR |
| | "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS. |
| | |
| | B) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS.PROVIDE FLORIDA PRODUCT APPROVAL COVER |
| | PAGE AND PAGE SHOWING THE CONNECTOR. |
| | |
| | C) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL |
| | ASSEMBLY U905. |
| | |
| | D) CEMENTITIOUS PANELS AT ENTRY OVERHANGS. SEE |
| | DETAIL 11/A705. |
| | |
| | E) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER |
| | HEATER. |
| | |
| | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 6- NEED TO CONTACT HAROLD PISKURA, INSPECTION SERVICES |
| | MANAGER (561)805-6711, TO COORDINATE SPECIAL INSPECTOR |
| | SERVICES. |
| | |
| | 7- PLEASE MAKE SURE ENERGY CALCULATIONS MATCH |
| | CORRESPONDING BUILDING ADDRESS, BUILDING TYPE, PERMIT |
| | NUMBER ETC. |
| | |
| | 8- PROVIDE ENERGY CALCULATIONS FOR COMMERCIAL AREA. AS |
| | REQUIRED BY CHAPTER 13 FBC 2004. |
| | |
| | 9- PROJECT MANUAL SPECS NEED TO HAVE COMPLETE |
| | ENGINEERING FIRM AND ENGINEER'S INFORMATION AS REQUIRED |
| | BY BY CHAPTER 471 FLORIDA STATUTES AND FLORIDA |
| | ADMINISTRATIVE CODE SEC. 61G15-23.002 AND REQUESTED ON |
| | PREVIOUS CHECKLIST. |
| | |
| | 10- THE INTENTION OF THE CODE IS TO DETERMINE THE |
| | MAXIMUM NUMBER OF PEOPLE EXPECTED TO OCCUPY THE |
| | BUILDING OR ROOMS OR SPACES WITHIN THE BUILDING AT ANY |
| | GIVEN TIME AND UNDER ALL PROBABLE CONDITIONS. THIS IS A |
| | SAFETY ISSUE BECAUSE DEPENDING ON THE NUMBER OF PEOPLE |
| | ALL EGRESS REQUIREMENTS SHALL BE MET.THEATRE ROOM |
| | HAS SPACE FOR STANDING PEOPLE AND THEY NEED TO BE |
| | COUNTED ALSO.CHAIRS NEED TO BE PART OF THE CONTRACT |
| | FOR PROPER INSPECTIONS.NEED TO PROVIDE AISLE |
| | DIMENSIONS AND ALL NECESSARY INFORMATION TO REVIEW FOR |
| | CHAPTER 11 OF FBC 2004. OCCUPANCY LOAD CALCULATIONS |
| | NEED TO BE ESTABLISHED BY THE LARGEST NUMBER COMPUTED |
| | IN ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH 1004.1.3. |
| | ACCORDING TO THIS SECTION TABLE 1004.1.2 FBC 2004 AND |
| | FLOOR PLANS, THE FLOOR AREA PER OCCUPANT SHALL BE |
| | CALCULATED FOR 5S.F. PROVIDE CALCULATIONS FOR NUMBER OF |
| | PEOPLE ON EACH ROOM OR SPACE TO VERIFY COMPLIANCE WITH |
| | TOTAL NUMBER OF PEOPLE. |
| | |
| | ***NOTE: ELECTRICAL PLANS CALL FOR CONFERENCE/MEETING |
| | ROOM. WHERE IS THIS ROOM LOCATED AT?. |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |