Plan Review Notes
Plan Review Notes For Permit 06101113
Permit Number 06101113
Review Stop B
Sequence Number 2
Notes
Date Text
2007-01-03 16:06:44BUILDING REVIEW SECOND CHECKLIST:
 1- REVISE ENERGY CALCULATIONS:
 A) AS REQUESTED ON PREVIOUS CHECKLIST, CALCULATIONS
 NEED TO BE DONE FOR THE WHOLE BUILDING, NOT FOR EACH
 UNIT AS REQUIRED BY SEC. 13-600.0 METHOD A OF FBC
 2004.
  
  
 B) AS REQUESTED ON PREVIOUS CHECKLIST, ENGINEER TO
 PROVIDE ALL HIS INFORMATION AS REQUIREDBY CHAPTER 471
 FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE SEC.
 61G15-23.002.
  
 C) CALCULATIONS SUBMITTED FOR INDIVIDUAL UNITS HAVE
 THE FOLLOWING INCORRECT INFORMATION:
 * NUMBER OF BEDROOMS.
 ** SLAB ON GRADE TOTAL PERIMETER FEET.
 *** CLARIFY HOW ARE THESE CALCULATIONS DONE FOR
 WORST CASE SCENARIO IF THERE IS NOT SHEET SHOWING
 OPENINGS SUN EXPOSURE ORIENTATION.
  
 2- REVISION CLOUDS ON SHEET A004 DON'T ALLOW THE OTHER
 INFORMATION TO BE LEGIBLE.REVISE AS REQUIRED.
  
 3- SURVEY AND SITE PLAN SHOWN ON SHEETS A100, A101 AND
 A102 DON'T MATCH.ACCORDING TO THE RECORDED SURVEY,
 THERE IS AN ALLEY BY BUILDING C3. SITE PLAN SHOWS
 PARKING SPACES. REVISE AS REQUIRED. THIS COMMENT COULD
 NOT BE ADDREESED BEFORE BECASUE THIS IS THE FIRST TIME
 SURVEY IS SUBMITTED FOR REVIEW.
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) UNIT ENTRY DOOR: DRAWINGS SUBMITTED ARE FOR
 "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS.
  
 B) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.PROVIDE FLORIDA PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE CONNECTOR.
  
 C) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL
 ASSEMBLY U905.
  
 D) CEMENTITIOUS PANELS AT ENTRY OVERHANGS. SEE
 DETAIL 11/A705.
  
 E) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER
 HEATER.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 6- NEED TO CONTACT HAROLD PISKURA, INSPECTION SERVICES
 MANAGER (561)805-6711, TO COORDINATE SPECIAL INSPECTOR
 SERVICES.
  
 7- PLEASE MAKE SURE ENERGY CALCULATIONS MATCH
 CORRESPONDING BUILDING ADDRESS, BUILDING TYPE, PERMIT
 NUMBER ETC.
  
 8- PROVIDE ENERGY CALCULATIONS FOR COMMERCIAL AREA. AS
 REQUIRED BY CHAPTER 13 FBC 2004.
  
 9- PROJECT MANUAL SPECS NEED TO HAVE COMPLETE
 ENGINEERING FIRM AND ENGINEER'S INFORMATION AS REQUIRED
 BY BY CHAPTER 471 FLORIDA STATUTES AND FLORIDA
 ADMINISTRATIVE CODE SEC. 61G15-23.002 AND REQUESTED ON
 PREVIOUS CHECKLIST.
  
 10- THE INTENTION OF THE CODE IS TO DETERMINE THE
 MAXIMUM NUMBER OF PEOPLE EXPECTED TO OCCUPY THE
 BUILDING OR ROOMS OR SPACES WITHIN THE BUILDING AT ANY
 GIVEN TIME AND UNDER ALL PROBABLE CONDITIONS. THIS IS A
 SAFETY ISSUE BECAUSE DEPENDING ON THE NUMBER OF PEOPLE
 ALL EGRESS REQUIREMENTS SHALL BE MET.THEATRE ROOM
 HAS SPACE FOR STANDING PEOPLE AND THEY NEED TO BE
 COUNTED ALSO.CHAIRS NEED TO BE PART OF THE CONTRACT
 FOR PROPER INSPECTIONS.NEED TO PROVIDE AISLE
 DIMENSIONS AND ALL NECESSARY INFORMATION TO REVIEW FOR
 CHAPTER 11 OF FBC 2004. OCCUPANCY LOAD CALCULATIONS
 NEED TO BE ESTABLISHED BY THE LARGEST NUMBER COMPUTED
 IN ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH 1004.1.3.
 ACCORDING TO THIS SECTION TABLE 1004.1.2 FBC 2004 AND
 FLOOR PLANS, THE FLOOR AREA PER OCCUPANT SHALL BE
 CALCULATED FOR 5S.F. PROVIDE CALCULATIONS FOR NUMBER OF
 PEOPLE ON EACH ROOM OR SPACE TO VERIFY COMPLIANCE WITH
 TOTAL NUMBER OF PEOPLE.
  
 ***NOTE: ELECTRICAL PLANS CALL FOR CONFERENCE/MEETING
 ROOM. WHERE IS THIS ROOM LOCATED AT?.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712