2007-12-03 16:23:44TRUSS PACKAGE SECOND CHECKLIST:
  
 1- STRUCTURAL ENGINEER OF RECORD NEEDS TO REVISE PLANS
 AS REQUIRED TO SHOW THE DESIGN LOADS REQUIRED BY TABLE
 1607.1 FBC 2004.ALL FLOOR TRUSSES NEED TO BE DESIGNED
 FOR THE DISTRIBUTED AND CONCENTRATED LIVE LOADS.
 NEW REVISED DESIGN LOAD SCHEDULE PROVIDED BY THE
 STRUCTURAL ENGINEER SHOWSA TOTAL LIVE LOAD OF 50PSF
 (OFFICE USE). ACCORDING TO TABLE 1607.1 FBC 2004 NEED
 TO DESIGN FOR 80PSF LIVE LOAD AT CORRIDORS ABOVE FIRST
 FLOOR.ON THE OTHER HAND NEED TO CONSIDER THE 2,000
 LBS CONCENTRATED LOAD.
 IN ADDITION, STAIRS AND EXITS NEED TO BE DESIGNED FOR
 100 PSF. REVISE DESIGN LOAD SCHEDULEAS REQUIRED.
  
 2- RE-RUN CALCULATIONS ON TRUSS DRAWINGS SHOWING
 REVISED LOADINGS. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE COMPLETE
 REVISED TRUSS PACKAGE PRIOR TO SUBMITTAL TO THIS
 OFFICE.
  
 4- IF FLOOR TRUSSES ARE ALREADY INSTALLED, THEN
 ENGINEER ANALYSIS WILL BE REQUIRED TO SHOW COMPLIANCE
 WITH THE REVISED LOADING.SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 5- ROOF TRUSS LAYOUT AT THE END WINGS OF THE BUILDING
 IS DIFFERENT THAN THE ONE SHOWN ON SHEET S-2. REVISE
 EITHER ONE AS REQUIRED TO MATCH EACH OTHER. (REPEAT
 COMMENT NOT ADDRESSED AT ALL).
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712