| 2006-12-04 12:45:17 | ****DENIED***** |
| | |
| | |
| | |
| | 1.NFPA 101 - 2003 EDITION AND THE FLORIDA FIRE |
| | PREVENTION CODE - 2004 EDITION SHALL BE REFERENCED. |
| | |
| | 2.CONSTRUCTION OPERATIONS SHALL NOT INTERFERE OR |
| | HINDER EMERGENCY ACCESS TO THE SAID PROPERTY OR |
| | VICINITY THEREOF |
| | |
| | 3.ON THE APPROPIATE ELEVATION DETAIL, SHOW/DISPLAY |
| | THE NUMERICAL ADDRESS OF THIS BUILDING FRONTING MERRY |
| | PLACE.AS PER WEST PALM BEACH CODE, THOSE NUMBERS |
| | SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH. |
| | INDIVIDUAL APARTMENT/UNIT SHALL BE NO LESS THAN 3" IN |
| | HEIGHT.VERIFY WITH LILI URSA, MIS - GIS SUPPORT |
| | SPECIALIST, THAT THE NEW ADDRESS WILL BE 1825 MERRY |
| | PLACE. |
| | |
| | 4.THE ADDRESS OF THE STRUCTURE SHALL BE IN THE TITLE |
| | BLOCK OF EACH SUBMITTED PLAN SHEET. |
| | |
| | 5.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE |
| | FIRE SPRINKLER SYSTEM. |
| | |
| | 6.FIRE SPRINKLER SYSTEM SHALL BE MONITORED. |
| | |
| | 7.SHOW DETAIL OF THE FIRE DEPARTMENT CONNECTION |
| | (FDC).THE FDC SHALL BE NO GREATER THAN 150 FEET TO |
| | THE NEAREST FIRE HYDRANT. |
| | |
| | 8.IN ADDITION TO THE KNOX BOX ENTRY SYTEM FOR THE |
| | BUILDING AS NOTED ON SHEET A801-DETAIL 17,KNOX |
| | LOCKING CAPS ARE REQUIRED FOR NEW FIRE DEPARTMENT |
| | CONNECTIONS. |
| | |
| | 9.INDICATE THE LOCATION OF THE 2A:10BC RATED FIRE |
| | EXTINGUISHERS FOR THE LEASING OFFICE. |
| | |
| | 10. WILL THIS BUILDING HAVE A FIRE ALARM SYSTEM IN |
| | CONJUNCTION WITH THE FIRE SPRINKLER SYSTEM? |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. |
| | |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |