Plan Review Notes
Plan Review Notes For Permit 06101113
Permit Number 06101113
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-26 14:53:45MERRY PLACE
  
 1820 MERRY PLACE TYPE VI BLDG.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME
 NEW NOTES DUE TO PLANS NOW BEING SUBMITTED WITH SOME
 ADDITIONAL INFORMATION.
  
 ********** UNSAT *************
  
 1) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 FOR
 THE MINIMUM REQUIRED CIRCUITING AND LOADS FOR THE
 DINING ROOM CIRCUIT(S). PLEASE ALSO SEE THAT NO OTHER
 ELECTRICAL DEVICES SUCH AS LIGHTING MAY BE PLACED ON
 SAID CIRCUIT.
 MUST BE 20A AND #12 AND ON ONE OR MORE OF THE CIRCUITS
 AS NOTED IN CODES ABOVE.
 PLEASE SEE THAT A DESIGNATED AREA AND THE LIKE SHALL BE
 INDICATED.
  
 2) NOTE: PLEASE BE SURE PLANS REFERENCE THE FOLLOWING
 CODES: NFPA-70 2002, NFPA-72 2002. THIS COULD NOT BE
 LOCATED ON PLANS AND IS REQUIRED.
  
 3) NOTE: PLEASE SEE HOUSE LOADS WHICH SHALL INDICATE
 ALL CONTINUOUS LOADS SUCH AS LIGHTING AT 125%. 215.3,
 230.42 ETC
 PLEASE SEE THE LIGHTING LOADS AS SHOWN DO NOT CORRELATE
 WITH THE NUMBER OF FIXTURES ON PLANS OR THE WATTAGE ON
 THE FIXTURE SCHEDULE. THE LOADS BEING SHOWN FOR
 INSTANCE FOR THE EXTERIOR LIGHTS IS LISTED AT 1000
 WATTS, HOWEVER AS THE FIXTURE TYPE ON PLANS SHOWS
 SEVENTEEN F-1 FIXTURES WHICH ARE 100 WATTS EACH THOSE
 ALONG EXCEED THE LOAD AS SHOWN ON PANEL SCHEDULE FOR
 THIS CIRCUIT.
 PLEASE SEE ALL INTERIOR LIGHTING FIXTURES AS SHOWN AND
 THE WATTAGE PER FIXTURE BASED ON FIXTURE SCHEDULE, THE
 NUMBER OF FIXTURES ON EACH CIRCUIT AND BE SURE ALL
 CORRELATE WITH THE PANEL SCHEDULE. PLEASE NOTE WITH
 RESPECT TO EMERGENCY AND/ EXITLIGHTS.
  
 4) NOTE:PLEASE SEE 410.8 FOR MINIMUM CLEARANCES
 PERMITTED IN STORAGE AREAS.
 (UNDER STAIRS) FIX TYPE "H". PLEASE KNOW, WHEN SHELVING
 IS NOT SHOWN, A MIN
 18" IS ASSUMED AND THE LIGHT FIXTURE AS SHOWN AND TYPE
 DESIGNATED SHALL MEET THE MIN CLEARANCES REQUIRED.
 PLEASE ADJUST
  
 5) NOTE: PLEASE SEE CALCULATIONS ALSO MENTIONS HEAT
 LOADS SHOWN AND BEING DONE AT 100%, YET THE KW RATINGS
 AS SHOWN DOES NOT CORRELATE WITH THE MECHANICAL PLANS
 OF 5KW?
 PLEASE ADJUST.
 220.21
  
 7) NOTE: PLEASE SEE E203 WHICH INDICATES A KEYNOTE #7,
 HOWEVER UNDER KEYNOTES, THERE IS NO #7?
 PLEASE SEE THIS APPEARS TO BE A DISPOSAL, HOWEVER THERE
 IS NOTHING LISTED ON PANEL SCHEDULES OR IN LOAD
 CALCULATIONS?
 PLEASE CLARIFY WHAT THIS IS?
  
 8) NOTE: PLEASE INDICATE CIRCUITING FOR THE EM/EXT
 LIGHTS AS REQUIRED PER 700.12E. PLEASE SEE NOTE #3
 ABOVE FOR LOADS.
 PLEASE BE SURE LIGHTING FIXTURES ARE WIRED AHEAD OF ANY
 LIGHTING CONTROL DEVICES.
  
 9) NOTE: PLEASE SEE THE MINIMUM LIGHTING LEVELS FOR
 EGRESS UNDER EMERGENCY POWER IS 1FT CANDLE IN ALL
 EGRESS PATHS. PLEASE ADD AN ADDITIONAL FIXTURE IN THE
 ENTRY/HALL WAY AREA TO BRING THE LESS THAN 1FT CANDLE
 AVERAGE SHOWN ON PLANS UP TO THE MIN LEVEL.
 NFPA-101 7.8, 7.9
  
 10) NOTE: PLEASE SEE CONTROL FOR PIT LIGHTS COULD NOT
 BE FOUND TO CONTAIN ANY AUTOMATED SHUT OFF AS REQUIRED.
  
 13-415.1.ABC.1.2
  
 11) NOTE: PLEASE SEE 13-415.1.AB.1, 13-415.2,
 13-415.2.ABC.1, FOR MAXIMUM LIGHTING POWER DENSITIES
 PERMITTED.
 COULD NOT LOCATE ANY ENERGY CALCULATIONS SUBMITTED WITH
 PLANS?
 PLEASE SEE SECTIONS ABOVE FOR LPD'S, WHICH CAN BE DONE
 ON THE PLANS ON A SMALL TABLE.
  
 12) NOTE: PLEASE 230.2, AT THIS TIME A SEPARATE SERVICE
 FOR THE ELEVATOR EQUIPMENT CAN NOT BE GRANTED AS THIS
 DOES NOT SEEM TO MEET THE EXCEPTIONS AS LISTED.
 PLEASE CLARIFY REQUIREMENTS FOR THIS, VOLTAGES, ETC.
 PLEASE KNOW, IF THE INFORMATION IS PROVIDED TO ALLOW
 THIS ADDITIONAL SERVICE, PLEASE BE SURE TO INDICATE THE
 BONDING AS REQUIRED TO THE MAIN SERVICE OF THE
 BUILDING.
 PLEASE KNOW WE ARE TAKING THIS IS A 3-PHASE SERVICE
 BASED ON THE 3-POLE MAIN AND CONDUCTORS AS LISTED,
 HOWEVER PLEASE INDICATE VOLTAGE ETC.
  
 13) NOTE: PLEASE INDICATE THE MAXIMUM TIMES PERMITTED
 ON THE TYPE OVER-RIDE DEVICES CHOSEN. (30 MINS FOR OC
 SENSOR TYPE AND 4HRS MAX FOR TIMER TYPES).
 13-415.1.ABC.1.1, .1.2
  
 14) NOTE: PLEASE SUBMIT AIC RATINGS FOR ALL SERVICE
 EQUIPMENT. 110.9, 240.12
 (MAIN FOR ELEVATOR SERVICE, IF PERMITTED)
  
 15) NOTE: PLEASE SEE THE ADDRESS ASSIGNED TO THE
 BUILDING AT ITS LOCATION HAS BEEN 1820; HOWEVER PLANS
 INDICATE 1824, PLEASE ADJUST AS REQUIRED.
 FAC 61G1-16.004
  
 *** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  