| 2006-11-26 14:53:45 | MERRY PLACE |
| | |
| | 1820 MERRY PLACE TYPE VI BLDG. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME |
| | NEW NOTES DUE TO PLANS NOW BEING SUBMITTED WITH SOME |
| | ADDITIONAL INFORMATION. |
| | |
| | ********** UNSAT ************* |
| | |
| | 1) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 FOR |
| | THE MINIMUM REQUIRED CIRCUITING AND LOADS FOR THE |
| | DINING ROOM CIRCUIT(S). PLEASE ALSO SEE THAT NO OTHER |
| | ELECTRICAL DEVICES SUCH AS LIGHTING MAY BE PLACED ON |
| | SAID CIRCUIT. |
| | MUST BE 20A AND #12 AND ON ONE OR MORE OF THE CIRCUITS |
| | AS NOTED IN CODES ABOVE. |
| | PLEASE SEE THAT A DESIGNATED AREA AND THE LIKE SHALL BE |
| | INDICATED. |
| | |
| | 2) NOTE: PLEASE BE SURE PLANS REFERENCE THE FOLLOWING |
| | CODES: NFPA-70 2002, NFPA-72 2002. THIS COULD NOT BE |
| | LOCATED ON PLANS AND IS REQUIRED. |
| | |
| | 3) NOTE: PLEASE SEE HOUSE LOADS WHICH SHALL INDICATE |
| | ALL CONTINUOUS LOADS SUCH AS LIGHTING AT 125%. 215.3, |
| | 230.42 ETC |
| | PLEASE SEE THE LIGHTING LOADS AS SHOWN DO NOT CORRELATE |
| | WITH THE NUMBER OF FIXTURES ON PLANS OR THE WATTAGE ON |
| | THE FIXTURE SCHEDULE. THE LOADS BEING SHOWN FOR |
| | INSTANCE FOR THE EXTERIOR LIGHTS IS LISTED AT 1000 |
| | WATTS, HOWEVER AS THE FIXTURE TYPE ON PLANS SHOWS |
| | SEVENTEEN F-1 FIXTURES WHICH ARE 100 WATTS EACH THOSE |
| | ALONG EXCEED THE LOAD AS SHOWN ON PANEL SCHEDULE FOR |
| | THIS CIRCUIT. |
| | PLEASE SEE ALL INTERIOR LIGHTING FIXTURES AS SHOWN AND |
| | THE WATTAGE PER FIXTURE BASED ON FIXTURE SCHEDULE, THE |
| | NUMBER OF FIXTURES ON EACH CIRCUIT AND BE SURE ALL |
| | CORRELATE WITH THE PANEL SCHEDULE. PLEASE NOTE WITH |
| | RESPECT TO EMERGENCY AND/ EXITLIGHTS. |
| | |
| | 4) NOTE:PLEASE SEE 410.8 FOR MINIMUM CLEARANCES |
| | PERMITTED IN STORAGE AREAS. |
| | (UNDER STAIRS) FIX TYPE "H". PLEASE KNOW, WHEN SHELVING |
| | IS NOT SHOWN, A MIN |
| | 18" IS ASSUMED AND THE LIGHT FIXTURE AS SHOWN AND TYPE |
| | DESIGNATED SHALL MEET THE MIN CLEARANCES REQUIRED. |
| | PLEASE ADJUST |
| | |
| | 5) NOTE: PLEASE SEE CALCULATIONS ALSO MENTIONS HEAT |
| | LOADS SHOWN AND BEING DONE AT 100%, YET THE KW RATINGS |
| | AS SHOWN DOES NOT CORRELATE WITH THE MECHANICAL PLANS |
| | OF 5KW? |
| | PLEASE ADJUST. |
| | 220.21 |
| | |
| | 7) NOTE: PLEASE SEE E203 WHICH INDICATES A KEYNOTE #7, |
| | HOWEVER UNDER KEYNOTES, THERE IS NO #7? |
| | PLEASE SEE THIS APPEARS TO BE A DISPOSAL, HOWEVER THERE |
| | IS NOTHING LISTED ON PANEL SCHEDULES OR IN LOAD |
| | CALCULATIONS? |
| | PLEASE CLARIFY WHAT THIS IS? |
| | |
| | 8) NOTE: PLEASE INDICATE CIRCUITING FOR THE EM/EXT |
| | LIGHTS AS REQUIRED PER 700.12E. PLEASE SEE NOTE #3 |
| | ABOVE FOR LOADS. |
| | PLEASE BE SURE LIGHTING FIXTURES ARE WIRED AHEAD OF ANY |
| | LIGHTING CONTROL DEVICES. |
| | |
| | 9) NOTE: PLEASE SEE THE MINIMUM LIGHTING LEVELS FOR |
| | EGRESS UNDER EMERGENCY POWER IS 1FT CANDLE IN ALL |
| | EGRESS PATHS. PLEASE ADD AN ADDITIONAL FIXTURE IN THE |
| | ENTRY/HALL WAY AREA TO BRING THE LESS THAN 1FT CANDLE |
| | AVERAGE SHOWN ON PLANS UP TO THE MIN LEVEL. |
| | NFPA-101 7.8, 7.9 |
| | |
| | 10) NOTE: PLEASE SEE CONTROL FOR PIT LIGHTS COULD NOT |
| | BE FOUND TO CONTAIN ANY AUTOMATED SHUT OFF AS REQUIRED. |
| | |
| | 13-415.1.ABC.1.2 |
| | |
| | 11) NOTE: PLEASE SEE 13-415.1.AB.1, 13-415.2, |
| | 13-415.2.ABC.1, FOR MAXIMUM LIGHTING POWER DENSITIES |
| | PERMITTED. |
| | COULD NOT LOCATE ANY ENERGY CALCULATIONS SUBMITTED WITH |
| | PLANS? |
| | PLEASE SEE SECTIONS ABOVE FOR LPD'S, WHICH CAN BE DONE |
| | ON THE PLANS ON A SMALL TABLE. |
| | |
| | 12) NOTE: PLEASE 230.2, AT THIS TIME A SEPARATE SERVICE |
| | FOR THE ELEVATOR EQUIPMENT CAN NOT BE GRANTED AS THIS |
| | DOES NOT SEEM TO MEET THE EXCEPTIONS AS LISTED. |
| | PLEASE CLARIFY REQUIREMENTS FOR THIS, VOLTAGES, ETC. |
| | PLEASE KNOW, IF THE INFORMATION IS PROVIDED TO ALLOW |
| | THIS ADDITIONAL SERVICE, PLEASE BE SURE TO INDICATE THE |
| | BONDING AS REQUIRED TO THE MAIN SERVICE OF THE |
| | BUILDING. |
| | PLEASE KNOW WE ARE TAKING THIS IS A 3-PHASE SERVICE |
| | BASED ON THE 3-POLE MAIN AND CONDUCTORS AS LISTED, |
| | HOWEVER PLEASE INDICATE VOLTAGE ETC. |
| | |
| | 13) NOTE: PLEASE INDICATE THE MAXIMUM TIMES PERMITTED |
| | ON THE TYPE OVER-RIDE DEVICES CHOSEN. (30 MINS FOR OC |
| | SENSOR TYPE AND 4HRS MAX FOR TIMER TYPES). |
| | 13-415.1.ABC.1.1, .1.2 |
| | |
| | 14) NOTE: PLEASE SUBMIT AIC RATINGS FOR ALL SERVICE |
| | EQUIPMENT. 110.9, 240.12 |
| | (MAIN FOR ELEVATOR SERVICE, IF PERMITTED) |
| | |
| | 15) NOTE: PLEASE SEE THE ADDRESS ASSIGNED TO THE |
| | BUILDING AT ITS LOCATION HAS BEEN 1820; HOWEVER PLANS |
| | INDICATE 1824, PLEASE ADJUST AS REQUIRED. |
| | FAC 61G1-16.004 |
| | |
| | *** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| | DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |