| 2007-01-05 18:34:09 | BUILDING REVIEW SECOND CHECKLIST: |
| | 1- REVISE ENERGY CALCULATIONS: |
| | A) AS REQUESTED ON PREVIOUS CHECKLIST, CALCULATIONS |
| | NEED TO BE DONE FOR THE WHOLE BUILDING, NOT FOR EACH |
| | UNIT AS REQUIRED BY SEC. 13-600.0 METHOD A OF FBC |
| | 2004. |
| | |
| | |
| | B) AS REQUESTED ON PREVIOUS CHECKLIST, ENGINEER TO |
| | PROVIDE ALL HIS INFORMATION AS REQUIREDBY CHAPTER 471 |
| | FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE SEC. |
| | 61G15-23.002. |
| | |
| | C) CALCULATIONS SUBMITTED FOR INDIVIDUAL UNITS HAVE |
| | THE FOLLOWING INCORRECT INFORMATION: |
| | * NUMBER OF BEDROOMS. |
| | ** SLAB ON GRADE TOTAL PERIMETER FEET. |
| | *** CLARIFY HOW ARE THESE CALCULATIONS DONE FOR |
| | WORST CASE SCENARIO IF THERE IS NOT SHEET SHOWING |
| | OPENINGS SUN EXPOSURE ORIENTATION. |
| | |
| | 2- REVISION CLOUDS ON SHEET A004 DON'T ALLOW THE OTHER |
| | INFORMATION TO BE LEGIBLE.REVISE AS REQUIRED. |
| | |
| | 3- SURVEY AND SITE PLAN SHOWN ON SHEETS A100, A101 AND |
| | A102 DON'T MATCH.ACCORDING TO THE RECORDED SURVEY, |
| | THERE IS AN ALLEY BY BUILDING C3. SITE PLAN SHOWS |
| | PARKING SPACES. REVISE AS REQUIRED. THIS COMMENT COULD |
| | NOT BE ADDREESED BEFORE BECASUE THIS IS THE FIRST TIME |
| | SURVEY IS SUBMITTED FOR REVIEW. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) UNIT ENTRY DOOR: DRAWINGS SUBMITTED ARE FOR |
| | "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS. |
| | |
| | B) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS.ONLY THE ONES SHOWN ON TRUSS ANCHOR |
| | SCHEDULE WERE PROVIDED AND THEY ARE MISSING THE PAGE |
| | SHOWING THE SPECIFIC CONNECTOR. PROVIDE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING EACH CONNECTOR. |
| | |
| | C) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL |
| | ASSEMBLY U905. |
| | |
| | D) CEMENTITIOUS PANELS AT ENTRY OVERHANGS. SEE |
| | DETAIL 11/A705. |
| | |
| | E) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER |
| | HEATER. |
| | |
| | 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 6- NEED TO CONTACT HAROLD PISKURA, INSPECTION SERVICES |
| | MANAGER (561)805-6711, TO COORDINATE SPECIAL INSPECTOR |
| | SERVICES. |
| | |
| | 7- PLEASE MAKE SURE ENERGY CALCULATIONS HAVE CORRECT |
| | ADDRESS, BUILDING TYPE, PERMIT NUMBER, ETC. |
| | |
| | 8- NORTH ARROW IN SURVEY IS POINTING TO THE WRONG |
| | DIRECTION. REVISE AS REQUIRED. |
| | |
| | 9- SURVEY TO INDICATE SETBACKS FROM ALL BUILDINGS TO |
| | ALL PROPERTY LINES FOR ACCURACY IN DETERMINATING PROPER |
| | PERCENTAGE OF OPENINGS.IT WILL ALSO HELP INSPECTOR |
| | WHEN CHECKING FORMBOARD SURVEY. |
| | THIS APPLIES TO ALL BUILDINGS IN THIS PROJECT. |
| | |