2007-01-05 18:34:09BUILDING REVIEW SECOND CHECKLIST:
 1- REVISE ENERGY CALCULATIONS:
 A) AS REQUESTED ON PREVIOUS CHECKLIST, CALCULATIONS
 NEED TO BE DONE FOR THE WHOLE BUILDING, NOT FOR EACH
 UNIT AS REQUIRED BY SEC. 13-600.0 METHOD A OF FBC
 2004.
  
  
 B) AS REQUESTED ON PREVIOUS CHECKLIST, ENGINEER TO
 PROVIDE ALL HIS INFORMATION AS REQUIREDBY CHAPTER 471
 FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE SEC.
 61G15-23.002.
  
 C) CALCULATIONS SUBMITTED FOR INDIVIDUAL UNITS HAVE
 THE FOLLOWING INCORRECT INFORMATION:
 * NUMBER OF BEDROOMS.
 ** SLAB ON GRADE TOTAL PERIMETER FEET.
 *** CLARIFY HOW ARE THESE CALCULATIONS DONE FOR
 WORST CASE SCENARIO IF THERE IS NOT SHEET SHOWING
 OPENINGS SUN EXPOSURE ORIENTATION.
  
 2- REVISION CLOUDS ON SHEET A004 DON'T ALLOW THE OTHER
 INFORMATION TO BE LEGIBLE.REVISE AS REQUIRED.
  
 3- SURVEY AND SITE PLAN SHOWN ON SHEETS A100, A101 AND
 A102 DON'T MATCH.ACCORDING TO THE RECORDED SURVEY,
 THERE IS AN ALLEY BY BUILDING C3. SITE PLAN SHOWS
 PARKING SPACES. REVISE AS REQUIRED. THIS COMMENT COULD
 NOT BE ADDREESED BEFORE BECASUE THIS IS THE FIRST TIME
 SURVEY IS SUBMITTED FOR REVIEW.
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) UNIT ENTRY DOOR: DRAWINGS SUBMITTED ARE FOR
 "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS.
  
 B) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.ONLY THE ONES SHOWN ON TRUSS ANCHOR
 SCHEDULE WERE PROVIDED AND THEY ARE MISSING THE PAGE
 SHOWING THE SPECIFIC CONNECTOR. PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING EACH CONNECTOR.
  
 C) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL
 ASSEMBLY U905.
  
 D) CEMENTITIOUS PANELS AT ENTRY OVERHANGS. SEE
 DETAIL 11/A705.
  
 E) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER
 HEATER.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 6- NEED TO CONTACT HAROLD PISKURA, INSPECTION SERVICES
 MANAGER (561)805-6711, TO COORDINATE SPECIAL INSPECTOR
 SERVICES.
  
 7- PLEASE MAKE SURE ENERGY CALCULATIONS HAVE CORRECT
 ADDRESS, BUILDING TYPE, PERMIT NUMBER, ETC.
  
 8- NORTH ARROW IN SURVEY IS POINTING TO THE WRONG
 DIRECTION. REVISE AS REQUIRED.
  
 9- SURVEY TO INDICATE SETBACKS FROM ALL BUILDINGS TO
 ALL PROPERTY LINES FOR ACCURACY IN DETERMINATING PROPER
 PERCENTAGE OF OPENINGS.IT WILL ALSO HELP INSPECTOR
 WHEN CHECKING FORMBOARD SURVEY.
 THIS APPLIES TO ALL BUILDINGS IN THIS PROJECT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712