| Date |
Text |
| 2006-11-20 12:57:17 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | NOTE: 1ST REVIEW UNDER PERMIT |
| | |
| | **********FROM PREVIOUS REVIEW********** |
| | |
| | 1. SHEETS DELETED. WILL BE SUBMITTED AT THE TIME OF |
| | APPLICATION SUBMITTAL PER RESPONSE. |
| | |
| | 2. OK |
| | |
| | 3. SHT A104 DETAIL 06 SINKS SHALL COMPLY |
| | WITH SECTION 11-4.24.7 FAUCETS. PLEASE |
| | INDICATE COMPLIANCE ON DETAIL. |
| | ****RESPONSE NOTED. NOTE REFERENCED INDICATES |
| | COMPLIANCE WITH LAVS, BUT NOT SINKS. PLEASE INDICATE |
| | FAUCET TYPE TO BE SUBMITTED FOR BOTH THE LAVS AND THE |
| | SINKS. (LEVER- OPERATED, PUSH-TYPE ETC). |
| | |
| | 4. SHT A104 GENERAL NOTES II(5)(C) GRAB |
| | BAR HEIGHTS SHALL BE 33" MIN. TO 36" |
| | MAX. PAGE 6.5 FHA DESIGN MANUAL. |
| | ****RESPONSE NOTED. NOTE NOT CORRECTED. |
| | |
| | 5. OK. DELETED |
| | |
| | 6. SHT A104 GENERAL NOTES: II(4)(G) SINK |
| | SHALL HAVE FORWARD APPROACH PER SECTION |
| | 11-4.24.5. SHOW ON DETAIL. |
| | ****RESPONSE NOTED. COMMENT NOT ADDRESSED. |
| | |
| | 7. OK. NOT REQUIRED FOR THIS BUILDING. |
| | |
| | 8 SHTS A201 THRU A205 INDICATE |
| | SPECIFICATION "A" OR "B" AS REQUIRED ON |
| | PAGES 7.34 & 7.35 FHA DESIGN MANUAL. |
| | ****RESPONSE NOTED. NO ACTION TAKEN. |
| | |
| | 9.OK |
| | |
| | 10. SHT A203 AND A204 UNITS B1 & C1 |
| | LOWER FLOOR REQUIRED TO MEET FHA-98 |
| | DESIGN REQUIREMENTS 2ND BATHROOMS ARE |
| | EXEMPT ONLY FROM MANEUVERING AND CLEAR |
| | FLOOR SPACE IF SPECIFICATION "B" AND |
| | SHALL SHOW THE BACKING AS WELL AS THE |
| | SPACING FOR THE WATER CLOSET. (33" |
| | OPENING, 15"/18" BETWEEN THE FIXTURES). |
| | PLEASE SHOW ON PLANS. IF SPECIFICATION |
| | 'A" THEN BATHROOM SHALL COMPLY WITH ALL REQUIREMENTS OF |
| | FHA DESIGN MANUAL. |
| | ****RESPONSE NOTED. NO ACTION TAKEN. |
| | |
| | 11. SHT A205 ADCP ACCESSIBLE UNIT PLAN NOTES LEGEND |
| | SHALL CHANGE REFERENCE STANDARD TO FHA-98 AMENDMENTS. |
| | ****RESPONSE NOTED. THIS COMMENT WAS BECAUSE OF THE |
| | FHA-1996 NOTE AT THE BOTTOM OF THE LEGEND. RESPONSE IS |
| | CORRECT IN THE FACT THAT 7%, (10 REQUIRED, 9 SHOWN), OF |
| | THE UNITS ARE TO BE FULLY ACCESSIBLE. ACCESSIBLE DOES |
| | NOT MEAN ANY PORTION SHALL BE ADAPTABLE AS INDICATED IN |
| | SOME NOTES. ALL FIXTURES REQUIRED TO BE ACCESSIBLE |
| | SHALL BE ACCESSIBLE WHEN THE UNIT IS BUILT. NOTE |
| | DELETED. |
| | |
| | 12. SHT A205 HDCP ACCESS. UNIT PLAN |
| | NOTES LEGEND:NOTE #2 SINK SHALL BE |
| | ACCESSIBLE, NOT ADAPTABLE AS STATED. |
| | IF UNIT IS ACCESSIBLE, THEN IT SHALL BE |
| | BUILT ACCESSIBLE. SHOW CLEAR FLOOR |
| | SPACE. |
| | ****RESPONSE NOTED. BUT WE ARE TALKING ABOUT THE |
| | ACCESSIBLE UNITS, NOT THE ADAPTABLE UNITS IN THIS |
| | COMMENT. (SEE COMMENT 11 ABOVE). NOTE DELETED. |
| | |
| | 13. OK (UNIT LOCATION ONLY) |
| | 14. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 15. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 16. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 17. OK. NOT REQUIRED FOR THIS BUILDING. (CHANGE |
| | REFERENCE). |
| | 18. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 19. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 20. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 21. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 22. OK. NOT SHOWN THIS BUILDING. |
| | 23. OK. NOTE 7 DELETED |
| | 24. OK. (CHANGED FROM HB SUPPLY TO GAS PIPING) |
| | 25. OK. NOT REQUIRED FOR THIS BUILDING |
| | |
| | 26. SHT P403 ALL WATER RISER DIAGRAMS, |
| | AIR CHAMBERS ARE NOT APPROVED. PLEASE |
| | DELETE FROM RISER DIAGRAMS. WATER HAMMER |
| | ARRESTORS REQUIRED BY SECTION 604.9, |
| | (W/M'S, D/W'S, AND ICE MAKERS), SHALL BE |
| | SHOWN AND SHALL BE LOCATED NEAR THE |
| | FIXTURES IN AN "EFFECTIVE RANGE", NOT IN |
| | THE CEILING. PDI-WH 201 AND MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | ****RESPONSE NOTED. RISERFOR UNIT B1 DOES NOT REFLECT |
| | THE FLOOR PLAN FOR BATHROOM NEXT TO THE UTILITY ROOM. |
| | PLEASE CORRELATE SECTION 106.1.1. |
| | |
| | 27. SUBMIT A BUILDING DRAIN SANITARY |
| | RISER DIAGRAM ISOMETRIC THAT REFLECTS |
| | THE FLOOR PLAN FOR EACH BUILDING. |
| | SECTION 106.1.5.1.3. SHOW ALL PIPE |
| | SIZES, RISER LOCATIONS, TRAPS, VENTS, |
| | AND DFU'S AS THEY ACCUMULATE IN THE |
| | SYSTEM. |
| | ****RESPONSE NOTED. SHOW CLEANOUTS REQUIRED BY SECTION |
| | 708.3.3, CHANGE OF DIRECTIONGREATER THAN 45 DEGREES. |
| | RISER DOES NOT REFLECT THE FLOOR PLAN. TWO RISERS ARE |
| | INDICATED AS 1S RISERS ON THE RISER, BUT ARE INDICATED |
| | AS 2S RISERS ON THE FLOOR PLAN. PLEASE CORRELATE RISER |
| | DIAGRAM AND FLOOR PLAN. SECTION 106.1.1. |
| | |
| | 28. OK |
| | 29. OK. NOT REQUIRED THIS BUILDING. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | SUBMIT ONE SET OF PLANS FROM FIRST |
| | REVIEW FOR COMPARISON TO EXPEDITE 2ND |
| | REVIEW. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. SHTS A100 & A101 PLANS INDICATE 7% OF THE UNITS |
| | SHALL BE ACCESSIBLE. 130 UNITS PROVIDED. 7% IS 9.1 |
| | UNITS. ANY FRACTION OF UNITS SHALL BE ROUNDED OFF |
| | UPWARDS. 10 ACCESSIBLE UNITS REQUIRED. CHART INDICATES |
| | BLDG "D" 1 REQUIRED/1 PROVIDED, BUT 1 IS INDICATED IN |
| | BOTH BLDGS.D1/V & D2/VIII, PLEASE CLARIFY. BLDG "E" |
| | INDICATES 1 REQUIRED/1PROVIDED, BUT 1 IS INDICATED IN |
| | BOTHBLDGS. E1/V & E2/V. PLEASE CLARIFY. BLDG "F" |
| | INDICATES 2 REQUIRED/2PROVIDED, BUT ONLY SHOWS 1 |
| | PROVIDED. PLEASE CLARIFY.PLEASE CORRELATE |
| | INFORMATION, CORRECT AMOUNT OF UNITS AND CHART. SECTION |
| | 106.1.1. |
| | |
| | 2B. SHT A200 HANDICAP ACCESSIBLE UNIT PLANS NOTES |
| | LEGEND.NOTES 1, 2, 5,INDICATE "ADAPTABLE". IF UNITS |
| | ARE TO BE ACCESSIBLE, THEY SHALL BE FULLY ACCESSIBLE AT |
| | THE TIME THEY ARE BUILT. NOT ADAPTABLE IN THE FUTURE. |
| | IF THE UNITS ARE TO BE FHA-98 COMPLIANT, THE COMPLETE |
| | UNIT CAN BE ADAPTABLE. |
| | NOTE "B" AT THE BOTTOM READS FAIR HOUSING ACT OF 1996. |
| | PLEASE INDICATE 1998 AMENDMENTS. NOTE FUTHER STATES |
| | "UNITS HEREIN DESIGNATED AS ACCESSIBLE SHALL BE FULLY |
| | ADA ADAPTABLE IN ADDITION TO FAIR HOUSING COMPLIANT". |
| | THIS IS NOT CORRECT. A UNIT IS EITHER FHA-98 ADAPTABLE |
| | OR FULLY ACCESSIBLE. |
| | |
| | 3B. SHT A200UNIT PLANS GENERAL NOTES 6 INDICATES 7% |
| | TO BE FULLY "ADAPTABLE" PLEASE CLARIFY. |
| | |
| | 4B. SHTS A203, A204, A205 SHOW THE CLEAR FLOOR SPACE AS |
| | REQUIRED ON PAGE 7.43 FHA DESIGN MANUAL. |
| | |
| | 5B. SHT P402 SANT. RISER S1 DOES NOT REFLECT THE FLOOR |
| | PLAN. (LAV ON RIGHT, TUB ON LEFT). |
| | |
| | 6B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING |
| | INFORMATION: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. AN ISOMETRIC IS REQUIRED FOR EACH GAS |
| | SYSTEM SHOWING THE PIPING FROM THE METER TO THE MOST |
| | REMOTEAPPLIANCE FOR EACH UNIT. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | H. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |