Plan Review Notes
Plan Review Notes For Permit 06101112
Permit Number 06101112
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-26 10:43:35MERRY PLACE
  
 1817 MERRY PLACE TYPE V BLDG.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME
 NEW NOTES DUE TO PLANS NOW BEING SUBMITTED WITH SOME
 ADDITIONAL INFORMATION.
  
 ********** UNSAT *************
  
 1) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 FOR
 THE MINIMUM REQUIRED CIRCUITING AND LOADS FOR THE
 DINING ROOM CIRCUIT(S). PLEASE ALSO SEE THAT NO OTHER
 ELECTRICAL DEVICES SUCH AS LIGHTING MAY BE PLACED ON
 SAID CIRCUIT.
 MUST BE 20A AND #12 AND ON ONE OR MORE OF THE CIRCUITS
 AS NOTED IN CODES ABOVE.
  
 2) NOTE: PLEASE BE SURE PLANS REFERENCE THE FOLLOWING
 CODES: NFPA-70 2002, NFPA-72 2002. THIS COULD NOT BE
 LOCATED ON PLANS AND IS REQUIRED.
  
 3) NOTE: PLEASE SEE HOUSE LOADS WHICH SHALL INDICATE
 ALL CONTINUOUS LOADS SUCH AS LIGHTING AT 125%. 215.3,
 230.42 ETC
  
 4) NOTE:PLEASE SEE 410.8 FOR MINIMUM CLEARANCES
 PERMITTED IN STORAGE AREAS.
 (UNDER STAIRS) FIX TYPE "H". PLEASE KNOW, WHEN SHELVING
 IS NOT SHOWN, A MIN
 18" IS ASSUMED AND THE LIGHT FIXTURE AS SHOWN AND TYPE
 DESIGNATED SHALL MEET THE MIN CLEARANCES REQUIRED.
 PLEASE ADJUST
  
 5) NOTE: PLEASE SEE CALCULATIONS ALSO MENTIONS HEAT
 LOADS SHOWN AND BEING DONE AT 100%, YET THE KW RATINGS
 AS SHOWN DOES NOT CORRELATE WITH THE MECHANICAL PLANS
 OF 5KW?
 PLEASE ADJUST.
 220.21
  
 6) NOTE: PLEASE SEE THE HOUSE PANEL ON E-311 IS BEING
 SHOWN AS 100MLO AND THE RISER SHOWS THIS AS 60A MLO. IT
 IS KNOWN THAT A 60A BREAKER IS FEEDING THIS PANEL.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]