| 2006-11-26 10:43:35 | MERRY PLACE |
| | |
| | 1817 MERRY PLACE TYPE V BLDG. |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME |
| | NEW NOTES DUE TO PLANS NOW BEING SUBMITTED WITH SOME |
| | ADDITIONAL INFORMATION. |
| | |
| | ********** UNSAT ************* |
| | |
| | 1) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 FOR |
| | THE MINIMUM REQUIRED CIRCUITING AND LOADS FOR THE |
| | DINING ROOM CIRCUIT(S). PLEASE ALSO SEE THAT NO OTHER |
| | ELECTRICAL DEVICES SUCH AS LIGHTING MAY BE PLACED ON |
| | SAID CIRCUIT. |
| | MUST BE 20A AND #12 AND ON ONE OR MORE OF THE CIRCUITS |
| | AS NOTED IN CODES ABOVE. |
| | |
| | 2) NOTE: PLEASE BE SURE PLANS REFERENCE THE FOLLOWING |
| | CODES: NFPA-70 2002, NFPA-72 2002. THIS COULD NOT BE |
| | LOCATED ON PLANS AND IS REQUIRED. |
| | |
| | 3) NOTE: PLEASE SEE HOUSE LOADS WHICH SHALL INDICATE |
| | ALL CONTINUOUS LOADS SUCH AS LIGHTING AT 125%. 215.3, |
| | 230.42 ETC |
| | |
| | 4) NOTE:PLEASE SEE 410.8 FOR MINIMUM CLEARANCES |
| | PERMITTED IN STORAGE AREAS. |
| | (UNDER STAIRS) FIX TYPE "H". PLEASE KNOW, WHEN SHELVING |
| | IS NOT SHOWN, A MIN |
| | 18" IS ASSUMED AND THE LIGHT FIXTURE AS SHOWN AND TYPE |
| | DESIGNATED SHALL MEET THE MIN CLEARANCES REQUIRED. |
| | PLEASE ADJUST |
| | |
| | 5) NOTE: PLEASE SEE CALCULATIONS ALSO MENTIONS HEAT |
| | LOADS SHOWN AND BEING DONE AT 100%, YET THE KW RATINGS |
| | AS SHOWN DOES NOT CORRELATE WITH THE MECHANICAL PLANS |
| | OF 5KW? |
| | PLEASE ADJUST. |
| | 220.21 |
| | |
| | 6) NOTE: PLEASE SEE THE HOUSE PANEL ON E-311 IS BEING |
| | SHOWN AS 100MLO AND THE RISER SHOWS THIS AS 60A MLO. IT |
| | IS KNOWN THAT A 60A BREAKER IS FEEDING THIS PANEL. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| | DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |