| 2006-12-06 10:13:55 | BUILDING REVIEW CHECKLIST: |
| | 1- NOTICE OF COMMENCEMENT AND IMPACT FEES STAMPED |
| | DRAWINGS AND PAID RECEIPTS WILL BE SUBMITTED LATER. |
| | |
| | 2- REVISE ENERGY CALCULATIONS: |
| | A) CALCULATIONS NEED TO BE PERFORMED FOR THE WHOLE |
| | BUILDING, NOT FOR EACH UNIT. SEC. 13-600.0 METHOD A OF |
| | 2004 FBC. |
| | B) NAME AND LICENSE # OF ENGINEER AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTES. |
| | C) PROVIDE COMPLETE INFORMATION FOR ITEM #8, FLOOR |
| | TYPES. |
| | D) INSULATION R VALUE SPECIFIED IN PROJECT MANUAL |
| | SPECS SEC. 07200 TO MATCH ENERGY CALCULATIONS. |
| | E) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. NEED |
| | ADDRESS AND BUILDER NAME. |
| | F) OWNER/AGENT TO SIGN AND DATE ALL ENERGY FORMS. |
| | NOTE: THIS APPLIES TO ALL ENERGY FORMS FOR ALL |
| | BUILDINGS. CHECK ALL ENERGY FORMS TO BE SUBMITTED. |
| | |
| | 3- NEED SIGNED AND SEALED SURVEYS SHOWING EXACT |
| | LOCATIONS OF BUILDINGS IN RELATIONSHIP WITH THE |
| | PROPERTY LINES AND OTHER BUILDINGS TO VERIFY COMPLIANCE |
| | WITH TABLES601, 602 FOR FIRE RESISTANCE AND TABLE |
| | 704.8 FBC 2004 FOR OPENINGS ALLOWED.PROVIDE ALL |
| | DISTANCES BETWEEN BUILDINGS AND PROPERTY LINES AND MAKE |
| | SURE ALL BUILDINGS HAVE THE DIMENSIONS BETWEEN BUILDING |
| | SEPARATION FOR BUILDINGS ON SAME LOT. IF BUILDINGS ARE |
| | ON SAME LOT, THEN SPECIFY THE PROPOSED PROPERTY LINE |
| | BETWEEN THEM.BUILDINGS WITH IRREGULAR SHAPES NEED TO |
| | SHOW DIMENSIONS WITH CLOSEST DISTANCE TO ADJACENT |
| | BUILDINGS. EG: SOME BUILDINGS HAVE SETBACKS IN THE |
| | FOOTPRINT. MAKE SURE DISTANCES PROVIDED INCLUDE THE |
| | CLOSEST DISTANCE BETWEEN BUILDINGS. SITE PLAN SUBMITTED |
| | DOESN'T PROVIDE ALL THIS INFORMATION. |
| | |
| | 4- SHOW ACCESSIBLE ROUTE FROM PARKING SPACE TO ALL |
| | APARTMENT ENTRANCES, RECREATIONAL AREAS AND PUBLIC |
| | BUILDINGS.WHERE ARE THE DRAWINGS?. |
| | |
| | 5- INFORMATION REGARDING HANDICAPPED UNITS AND |
| | ADAPTABLE UNITS IS CONFUSING.ACCORDING TO FAIR |
| | HOUSING ACT,"ALL"GROUND FLOOR UNITS MUST BE |
| | "ACCESSIBLE"FROM THE PARKING SPACE TO THE UNIT |
| | ENTRANCE. THEN,ALL THE UNITS MUST BE "ADAPTABLE"PER |
| | FHA.INFORMATION ON SHEET A100 IS INDICATING THAT |
| | THERE ARE 9 ADAPTABLE UNITS ON ACCESSIBLE ROUTE.IF |
| | THE INTENTION IS TO GO BEYOND FHA AND TO HAVE FULLY |
| | HANDICAPPED UNITS, THEN CLARIFY THAT SUCH UNITS WILL BE |
| | FULLY HANDICAPPED UNITS, NOT ADAPTABLE. |
| | |
| | 6- SHEET A004: |
| | A) MISSING UNIT MODEL TYPE IN PROJECT TABULATION |
| | CHART. |
| | B) BUILDING AND UNIT AREAS DON'T MATCH. SEE SHEET |
| | A004 AND SHEETS A203, A204, A205 AND 305.REVISE AS |
| | REQUIRED.NEED CORRECT AREAS TO ESTIMATE BUILDING |
| | VALUATION. SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | PROVIDE PORCHES, BALCONIES AND BUILDING AREAS. |
| | |
| | 7- SHEET A101: |
| | A) HANDICAPPED PARKING FOR FAIR HOUSING UNITS AND |
| | CHAPTER 11 FBC 2004 CAN'T OVERLAP TO ACCOMPLISH TOTAL |
| | NUMBER OF REQUIRED PARKING SPACES.NEED TO PROVIDE |
| | SEPARATE HANDICAPPED PARKING FOR FAIR HOUSING UNITS AND |
| | PUBLIC ASSEMBLY AREAS.SEE TABLE ON SECTION 11-4.1.2 |
| | FOR REQUIRED NUMBER OF PARKING SPACES. THIS COMMENT |
| | APPLIES TO BUILDINGS F AND C FOR MIXED USE BUILDINGS. |
| | |
| | B) PROVIDE DRAWINGS SHOWING PARKING SIZES AND |
| | ACCESSIBLE ROUTES FROM PARKING SPACES TO RESIDENTIAL |
| | UNITS AND PUBLIC ASSEMBLY BUILDINGS TO VERIFY |
| | COMPLIANCE WITH FAIR HOUSING ACT AND CHAPTER 11 FBC |
| | 2004. |
| | |
| | C) SPECIFY IF PROVIDING VISITORS PARKING SPACES TO |
| | VERIFY COMPLIANCE WITH FAIR HOUSING ACT. |
| | |
| | 8- OWNER TO PROVIDE LETTER CERTIFYING THAT NO FEDERAL |
| | MONIES ARE USED FOR THIS PROJECT. OTHERWISE,PROJECT |
| | NEEDS TO BE REVIEWED FOR SECTION 504 OF THE |
| | REHABILITATION ACT COMPLIANCE. |
| | |
| | 9- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) SINGLE HUNG WINDOW. NOA 01-0629.08 IS EXPIRED. |
| | ALSO, NEED FLORIDA PRODUCT APPROVAL COVER PAGE. GO TO |
| | WWW.FLORIDABUILDING.ORG TO DOWNLOAD CORRESPONDING COVER |
| | PAGE. FLORIDA PRODUCT APPROVAL COVER PAGE APPLIES TO |
| | ALL PRODUCT APPROVALS. IF THERE IS NO FLORIDA PRODUCT |
| | APPROVAL, THEN SUBMIT THE DADE COUNTY NOA ONLY. |
| | |
| | B) UNIT ENTRY DOOR: DRAWINGS SUBMITTED ARE FOR |
| | "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS. |
| | |
| | C) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING SPECIFIC CONNECTOR. |
| | |
| | D) SLIDING GLASS DOORS. PROVIDE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE. |
| | |
| | E) ROOF SHINGLES. NEED FLORIDA PRODUCT APPROVAL |
| | COVER PAGE. |
| | |
| | F) RIDGE VENT. NEED FLORIDA PRODUCT APPROVAL COVER |
| | PAGE. |
| | |
| | G) 770-D ROOF LOUVER. NEED FLORIDA PRODUCT APPROVAL |
| | COVER PAGE. |
| | |
| | H) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL |
| | ASSEMBLYU905. |
| | |
| | I) CEMENTITIOUS PANELS FOR ENTRY OVERHANGS. SEE |
| | DETAIL 11/A705. |
| | |
| | J) FALSE SKYLIGHT. SEE ELEVATIONS. |
| | |
| | K) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER |
| | HEATER. |
| | |
| | 10- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 11- SHEET A103: |
| | A) REVISE DETAIL 19 TO MATCH DETAIL 7/700.1. SHELVES |
| | HEIGHT 48" MAX. |
| | |
| | B) PROVIDE DETAILS/SPECS FOR GRAB BARS |
| | REINFORCEMENT. MATERIAL AND INSTALLATION. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | 12- SHEET A104: |
| | A) CLARIFY COMMON USE FACILITIES NOTE # 2A. WHAT'S |
| | THE QUESTION MARK FOR?. |
| | B) REVISE RESTROOMS NOTE # 5C. SEE FIGURE 30 ON |
| | CHAPTER 11 FBC 2004. |
| | |
| | 13- SHEET 110: |
| | A) DETAIL 20: CLARIFY QUESTION MARKS ON CONCRETE |
| | BLOCK THICKNESS. |
| | B) DETAIL 18: REQUIRES 2X10 JOISTS AT 16" OC. REVISE |
| | UNDER STAIRS DETAILS TO MATCH THIS ASSEMBLY. |
| | C) UPDATE ASSEMBLY AND PENETRATIONS SCHEDULE. |
| | REFERENCE UL 2004, NOT UL 1999. |
| | |
| | 14- SHEET A203: |
| | A) SPECIFY DOOR SIZE FOR DOOR LEADING TO MASTER |
| | BEDROOM. |
| | |
| | B) CLARIFY SQUARE FOOTAGE FOR UPPER FLOOR UNIT. |
| | ALSO, COORDINATE ALL THESE AREAS WITH GENERAL AREA |
| | TABULATION ON SHEET A004. |
| | |
| | C) PANTRIESWITH NARROW DOORS TO HAVE 18" MAX. |
| | DEPTH. SEE PAGE 7.17 FAIR HOUSING ACT.THIS COMMENT |
| | APPLIES TO ALL GROUND UNITS THROUGHOUT ENTIRE PROJECT. |
| | REVISE AS REQUIRED. |
| | |
| | D) BEDROOM # 2 CLOSET DOOR NEEDS TO COMPLY WITH FAIR |
| | HOUSING ACT. NEED WIDER DOORS TO REACH AT THE ENDS OF |
| | CLOSET. SEE PAGE 3.14 FAIR HOUSING ACT AND REVISE AS |
| | REQUIRED. |
| | |
| | 15- SHEET A204: |
| | A) CLOSET DOORS FOR SECONDARY BEDROOMS DON'T COMPLY |
| | WITH FAIR HOUSING ACT. SEE PAGE 3.15 OF FHA. NEED WIDER |
| | DOORS TO ALLOW REACH AT THE ENDS OF CLOSET. ALSO, DOOR |
| | TYPE SPECIFIED DON'T MATCH DOOR SCHEDULE. |
| | |
| | B) REVISESQUARE FOOTAGE AREAS. THEY CAN'T BE THE |
| | SAME.COORDINATE AREAS WITH TABULATION ON SHEET A004. |
| | |
| | C) PANTRIES WITH NARROW DOORS TO HAVE 18" MAX. |
| | DEPTH. SEE PAGE 7.17 FAIR HOUSING ACT. THIS APPLIES TO |
| | ALL GROUND FLOOR UNITS AND ALL UNIT TYPES. |
| | |
| | 16- SHEET A205: |
| | A) UNIT C1: CLOSET DOORS FOR SECONDARY BEDROOMS |
| | DON'T COMPLY WITH FAIR HOUSING ACT. SEE PAGE 3.15 OF |
| | FHA. NEED WIDER DOORS TO ALLOW REACH AT THE ENDS OF THE |
| | CLOSET. THIS ALSO APPLIES TO B1 UNIT AND ALL UNITS IN |
| | GROUND FLOOR. REVISE ALL CLOSET DOORS AS REQUIRED. |
| | |
| | B) REVISE SQUARE FOOTAGE AREAS. THEY CAN'T BE THE |
| | SAME. COORDINATE WITH CHART ON SHEET A004. |
| | |
| | C) PROVIDE COMPLETE DETAILS AND SPECS FOR ROLL-IN |
| | SHOWERS. |
| | |
| | D) PANTRIES WITH NARROW DOORS TO HAVE 18" DEPTH. |
| | TYP. ALL GROUND FLOOR UNITS. |
| | |
| | 17- SHEET A305: |
| | A) VENTILATION CALCULATIONS: COORDINATE SIZE OF |
| | RIDGE VENT. SEE RIDGE VENT PRODUCT APPROVAL FOR |
| | REQUIRED OPENING. REVISE CALCULATIONS AS REQUIRED. |
| | REVISE DETAIL 16/A705 AS REQUIRED. |
| | |
| | B) GENERAL ROOF NOTE #2 CALLS FOR DETAIL 14/A705. |
| | MISSING THAT DETAIL. |
| | |
| | 18- SHEET A400: |
| | A) ALL DETAILS TO SPECIFY PRESSURE TREATED WOOD (OR |
| | ANY OTHER APPROVED METHOD TO ISOLATE WOOD WHEN IN |
| | CONTACT WITH CONCRETE OR CONCRTE BLOCK). SEC. 2304.11 |
| | FBC 2004. |
| | |
| | B) ENLARGED ELEVATIONS DON'T CORRESPOND TO THIS |
| | BUILDING. REVISE AS REQUIRED. |
| | |
| | 19- SHEET A500: |
| | A) SECTION 17: FLOOR ASSEMBLYL-521 AND INFORMATION |
| | ON TYPICAL FLOOR CONSTRUCTION ON SAME DRAWING DON'T |
| | MATCH. REVISE AS REQUIRED. ALSO, INFORMATION DOESN'T |
| | MATCH SPECIFICATION SHOWN ON SHEET A111. |
| | B) REVISEINFORMATION ON UL L-521 ON SHEET A111. |
| | SEE 2004 UL BOOK AND REVISE SPECS TO MATCH SUCH |
| | LISTING. |
| | C) SPECS ON WALL ASSEMBLY U905 DOESN'T MATCH |
| | INFORMATION SHOWN ON SAME DRAWING POINTING TO WALL |
| | AREAS. REVISE AS REQUIRED. |
| | |
| | D) PROVIDE INFORMATION THAT ADDRESSES MINIMUM LABELS |
| | OF SOUND INSULATION AS REQUIRED BY SEC. 1207.2 AND |
| | 1207.3. |
| | |
| | E) PROVIDE FIREBLOCKING AT ROOF ASSEMBLY |
| | INTERSECTION. FLOOR ASSEMBLY NOTE ON DETAIL 17 CLEARLY |
| | SPECIFIES TO SEAL JOINTS AT WALL . THIS IS NOT |
| | SPECIFIED AT CEILING AREA.SEC. 717 FBC 2004. |
| | |
| | 20- SHEET A501:MISSING DETAIL 14/ A705 SPECIFIED ON |
| | WALL SECTION 16 AND 18. |
| | |
| | 21- SHEET A701.1:DETAIL 01: HOW IS THE FASTENER |
| | EMBEDED 1-1/4" IN TO THE BUCK IF THE BUCK IS ONLY 1X |
| | THICK. REVISE AS REQUIRED. |
| | |
| | 22- SHEET A703: WOOD IN CONTACT WITH CONCRETE BLOCK TO |
| | BE PRESSURE TREATED. REVISE DETAILS 01 AND 06 AS |
| | REQUIRED. |
| | |
| | 23- SHEET A705: |
| | A) DETAIL 02: REVISE FLASHING FASTENER SPACING AS |
| | REQUIRED BY ROOFING APPLICATION STANDARD RAS 111. |
| | |
| | B) REVISE DETAIL 16. SEE RIDGE VENT PRODUCT APPROVAL |
| | FOR RIDGE CUT OUT DIMENSION. |
| | |
| | C) PROVIDE COMPLETE STRUCTURAL DETAIL SHOWING |
| | INSTALLATION OF FALSE SKYLIGHT TO COMPLY WITH SEC. 1609 |
| | FBC 2004. |
| | |
| | 24- SHEET A706.1: |
| | A) DETAIL 00 (?): CHECK VENT HOOD SPECIFICATIONS FOR |
| | MIN. CLEARANCE REQUIRED FROM THE RANGE. PROVIDE VENT |
| | HOOD SPECS AND REVISE DETAIL AS REQUIRED. |
| | |
| | 25- SHEET S-1:FOUNDATION PLAN STILL SHOWS A DROP AT |
| | THE ENTRANCE TO UNITS. ALL GROUND FLOOR UNITS NEED TO |
| | COMPLY WITH FAIR HOUSING ACT. REVISE AS REQUIRED. |
| | |
| | 26- SHEET S-4: TRUSS TIE DOWN SCHEDULE. REVISE NOTE #6 |
| | FOR CONNECTOR C (SIMPSON MGT). NEED 12" EMBEDMENT. SEE |
| | SIMPSON CATALOGUE. |
| | |
| | 27- PROVIDE COMPLETE DETAILS AND SPECS FOR INSTALLATION |
| | OF RECESSED GAS WATER HEATER. PROVIDE DETAILS AND SPECS |
| | FOR WALL SEPARATING WATER HEATER AND AIR HANDLER UNIT. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |