Plan Review Notes
Plan Review Notes For Permit 06101081
Permit Number 06101081
Review Stop E
Sequence Number 6
Notes
Date Text
2007-12-03 16:43:58 
 ** DENIED REVIEW **
  
 ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING ALONG WITH NEW
 NOTES.
  
  
  
 1) NOTE: PLEASE SEE THE PLANS ARE STILL QUOTING
 LIGHTING CONTROLS ARE TO MEET CHAPTER 13 IN LIEU OF
 ACTUAL DETAILS REQUIRED.
 13-415.1.ABC.1.2.
  
 2) NOTE: PLEASE SEE THE ELECTRICAL PLANS DO NOT SHOW
 THE NEW LIGHTING, CIRCUITING, OR CONTROLS FOR STAIR
 LIGHTS AND EMERGENCY LIGHTING WHICH ARE ON PHOTO-METRIC
 SHEET PROVIDED.
 PLEASE CORRELATE ELECTRICAL FOR ALL LIGHTING.
 PLEASE SHOW CONTROLS AND CIRCUITING. PLEASE BE SURE TO
 SEE NEC 700.12E FOR CIRCUITING OF EMERGENCY LIGHTING
 FIXTURES.
 FBC 106.3.5.1.2, 106.1.2
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.