| Plan Review Notes For Permit 06101081 |
| Permit Number |
06101081 |
|
| Review Stop |
FIRE |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-11-06 10:52:52 | *****DENIED***** | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE REVIEWS | | | STILL NEED TO BE REVIEWED | | | | | | | | | 1.LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. THE PLANS ARE TO BE SUBMITTED WITH NO INK, | | | PENCIL,OR BLACK/WHITE-OUTED MARKINS | | | | | | 2.CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS | | | SHALL COMPLY WITH NFPA 241.JOB SITE SHALL BE CLEANED | | | OF CONSTRUCTION DEBRIS DAILY.PLEASE ACKNOWLEDGE ON AN | | | APPROPIATE PLAN SHEET | | | | | | 4.PLEASE SEE ELECTRICAL REVIEW COMMENTS REGARDING | | | REQUIRED LIGHTING IN AREAS OF MEANS OF EGRESS. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|