| 2007-10-27 11:47:45 | ** DENIED REVISION 3RD TIME ** |
| | |
| | 1) NOTE: PLEASE SEE THERE ARE STILL COMMENTS FROM THE |
| | *TWO* PREVIOUS REVIEWS WHICH ARE THE SAME. |
| | PLEASE KNOW THAT QUOTING THE CODE ON PLANS IN LIEU OF |
| | SHOWING CODE COMPLIANCE DETAILS IS NOT PERMITTED. |
| | ** THE PLANS WERE LOOKED OVER BEFORE SUBMITTING WITH |
| | THE GC AND WERE TOLD THE PLANS HAD NOT BEEN CORRECTED. |
| | THE PLANS WERE SUBMITTED FOR REVIEW ANYWAY FOR CODE |
| | COMPLIANCE REVIEW. |
| | |
| | 2) NOTE: PLEASE SEE PLANS ARE STILL DO NOT INDICATE THE |
| | LIGHTING CONTROLS AS REQUIRED PER 13-415.1.ABC .1.1, |
| | AND 13-415.1.ABC .1.2. 13-103 |
| | PLEASE KNOW THAT QUOTING THE CONTROLS ARE TO MEET CODE |
| | IS NOT PROVIDING THE INFORMATION AS NEEDED. |
| | |
| | 3) NOTE: PLEASE SEE THE PLANS STILL INDICATE DIMMERS ON |
| | THE EGRESS LIGHTING PATHS. PLEASE SEE THAT NO |
| | INFORMATION WAS SUBMITTED ON HOW THE MINIMUM LIGHTING |
| | LEVELS WILL BE MAINTAINED. PLEASE SEE THE PLANS DO NOT |
| | INDICATE ANY LIGHTING LEVELS AS PREVIOUSLY REQUESTED. |
| | THESE ARE ALL *MINIMUM* LIGHTING LEVELS REQUIRED FOR |
| | LIFE SAFETY UNDER NORMAL AND EMERGENCY CONDITIONS. |
| | PLEASE SEE THE 2003 LIFE SAFETY CODE NFPA-101 7.8 AND |
| | 7.9. |
| | PLEASE SHOW THE PHOTO-METRIC LEVELS BASED ON FIXTURES |
| | TO BE INSTALLED. |
| | PLEASE PROVIDE DETAILED INFORMATION WHICH WILL |
| | SPECIFICALLY SHOW HOW THE MINIMUM LIGHTING LEVELS ARE |
| | MET. |
| | |
| | 4) NOTE: PLEASE SEE THAT AS THESE COMMENTS WHICH WERE |
| | ON BOTH PREVIOUS REVIEWS. IF THESE COMMENTS ARE NOT |
| | ADDRESSED ON THE FOLLOWING REVIEW, THIS OFFICE IS BEING |
| | LEFT WITH NO CHOICE BUT TO FORWARD DOCUMENTS/PLANS TO |
| | THE FLORIDA BOARD OF ARCHITECTS AND STATE BOARD OF |
| | ARCHITECTS LEGAL COUNSEL FOR REVIEW. |
| | AS STATED ON ALL PREVIOUS REVIEWS, IF THERE ARE ANY |
| | QUESTIONS TO PLEASE CONTACT THIS OFFICE TO GO OVER THE |
| | COMMENTS IF THEY ARE NOT UNDERSTOOD. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |