2006-11-22 16:53:30BUILDING PLAN REVIEW
 PERMIT: 06101081
 ADD: 2905 45TH ST
 CONT: FIRST FLORIDA CONSTRUCTION
 TEL: (813)881-0607
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 4) 2004 FL EXISTING BLDG CODE WHAT LEVEL
 OF CONSTRUCTION IS BEING COMPLETED?
  
 5) PROVIDE THE OCCUPANT LOAD FOR THE
 MEZZANINE AREA? ALSO PROVIDE A LIFE SAFETY
 PLAN INDICATING THE NUMBER OF OCCUPANTS
 AND WHICH STAIRS THEY WILL BE USING.
 DEPENDING ON THE RESULTS OF THE QUESTIONS ABOVE THE
 MONUMENTAL STAIRS MAY HAVE ADDITIONAL COMMENTS.
  
 6) THE SECOND LEVEL OF THE MEZZANINE INDICATES VARIOUS
  
 CUBICLE ENCLOSURES, THE ENCLOSURES THAT ARE LOCATED
 NEXT
 TO THE TOP OF THE SHEET CUT OFF THE DIRECT ACCESS TO AN
 EXIT
 FROM THE MEZZANINE LEVEL.505.4(EXCEPTION# 2). A
 MEZZANINE
 HAVING TWO OR MORE MEANS OF EGRESS IS NOT REQUIRED TO
 BE OPEN
 TO THE ROOM IN WHICH THE MEZZANINE IS LOCATED, IF AT
 LEAST ONE OF
 THE MEANS OF EGRESS PROVIDES DIRECT ACCESS TO AN EXIT
 FROM THE
 MEZZANINE LEVEL.
  
 7) RAISED SEATING AREA BY THE NEW GLASS WALL, A NEW
 STAIR TO THIS AREA
 IS BEING ALTERED, 11-4.1.6(1)(B) ACCESSIBLE BUILDINGS,
 ALTERAATIONS:
 IF EXESTING ELEMENTS, SPACES, OR COMMON AREAS ARE
 ALTERED, THEN EACH
 SUCH ALTERED ELEMENT, SPACE, FEATURE,OR AREA SHALL
 COMPLY WITH THE APPLICABLE
 PROVISIONS OF 11-4.1.1 TO 11-4.1.3. MINIMUM
 REQUIREMENTS FOR NEW CONSTRUCTION.
 PROVIDE VERTICAL ACCESSIBILITY TO THE RAISED SEATING
 AREA.
 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 SSTRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIAABLE
 GRADE LEVEL.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  