| 2006-10-30 08:41:17 | PROVISO: | | | PLEASE NOTE, PER 2004 FMC 606.2.1, DUCT SMOKE DETECTORS | | | REQUIRED IN SYSTEMS WITH THE DESIGN CAPACITY GREATER | | | THAN 2,000 CFM.FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE IN NORMALLY | | | OCCUPIED AREAS IN ACCORDANCE WITH 2002 NFPA 90A SECTION | | | 6.4.4.3 (1). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OR E-MAIL [email protected]. |
|