| Plan Review Notes For Permit 06101066 |
| Permit Number |
06101066 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-17 08:27:54 | *** PROVISO *** | | | 1) UNITS (A1) UPPER AND LOWER, RETURN AIR TRANSFER | | | GRILLS TO MASTER BEDROOM SUITE NEED TO BE 14"X 8", SEE | | | 2004 FBC/M 601.4. | | | | | | 2) CLOTHES DRYER VENTS MAY NOT EXCEED THE | | | MANUFACTURER'S SPECIFICATION'S. | | | | | | 3) AHU CLOSET DOORS NEED TO BE LOUVERED OR GRILLS NEED | | | TO BE INSTALLED FOR RETURN AIR, SEE 2004 FBC/M 601.4. | | | | | | 4) LAUNDRY ROOM DOORS NEED TO BE LOUVERED OR GRILLS | | | NEED TO BE INSTALLED FOR COMBUSTION AIR, SEE 2004 FBC/M | | | 701.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|