2006-12-01 09:34:54*****DENIED*****
  
  
  
  
 1.ON THE APPROPIATE ELEVATION DETAIL, SHOW/DISPLAY
 THE NUMERICAL ADDRESS OF THIS BUILDING FRONTING LILAC
 COURT.AS PER WEST PALM BEACH CODE, THOSE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH.
 INDIVIDUAL APARTMENT/UNIT SHALL BE NO LESS THAN 3" IN
 HEIGHT.
  
 2.THE ADDRESS OF THE STRUCTURE SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 3.FIRE EXTINGUISHERS ARE TO BE 2A-10BC RATED.
  
 4.AS PER NFPA 101 - 10.2.8.1 -2003 EDITION,
 INTERIOR FINISH FOR WALLS AND CEILINGS IN AN
 UNSPRINKLERED BUILDING SHALL BE CLASS "A" OR CLASS
 "B".
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722