Plan Review Notes For Permit 06101065
Permit Number 06101065
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-11-16 11:11:01*****UNSAT*****
  
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.INTERIOR DEMOLITION AND BUILDOUT OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF.
  
 3.AS PER NFPA 101 - 2003 EDITION - CHAPTER 10, SINCE
 THE STRUCTURE IS AN UNSPRINKLERED BUILDING ALL INTERIOR
 FINISH SHALL BE CLASS "A" OR CLASS "B".(SEE SHEET A-1
 FINISH SCHEDULE NOTE #6)
  
 4.FIRE EXTINGUISHER(S) SHALL BE RATED 2A-10BC.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER HOW/WHERE EACH ITEM WAS
 ADDRESSED.
  
  
 CAPT. MICHAEL WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  