| Plan Review Notes For Permit 06101065 |
| Permit Number |
06101065 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-16 11:11:01 | *****UNSAT***** | | | | | | | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.INTERIOR DEMOLITION AND BUILDOUT OPERATIONS SHALL | | | NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID | | | PROPERTY OR VICINITY THEREOF. | | | | | | 3.AS PER NFPA 101 - 2003 EDITION - CHAPTER 10, SINCE | | | THE STRUCTURE IS AN UNSPRINKLERED BUILDING ALL INTERIOR | | | FINISH SHALL BE CLASS "A" OR CLASS "B".(SEE SHEET A-1 | | | FINISH SCHEDULE NOTE #6) | | | | | | 4.FIRE EXTINGUISHER(S) SHALL BE RATED 2A-10BC. | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER HOW/WHERE EACH ITEM WAS | | | ADDRESSED. | | | | | | | | | CAPT. MICHAEL WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | |
|