Plan Review Notes
Plan Review Notes For Permit 06101057
Permit Number 06101057
Review Stop E
Sequence Number 1
Notes
Date Text
2006-11-26 09:24:49MERRY PLACE
  
 418 17TH ST BLDG TYPE 1
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME
 NEW NOTES DUE TO PLANS NOW BEING SUBMITTED WITH SOME
 ADDITIONAL INFORMATION.
  
 ********** UNSAT *************
  
  
 1) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 FOR
 THE MINIMUM REQUIRED CIRCUITING AND LOADS FOR THE
 DINING ROOM CIRCUIT(S). PLEASE ALSO SEE THAT NO OTHER
 ELECTRICAL DEVICES SUCH AS LIGHTING MAY BE PLACED ON
 SAID CIRCUIT.
 MUST BE 20A AND #12 AND ON ONE OR MORE OF THE CIRCUITS
 AS NOTED IN CODES ABOVE.
  
 2) NOTE: PLEASE BE SURE PLANS REFERENCE THE FOLLOWING
 CODES: NFPA-70 2002, NFPA-72 2002. THIS COULD NOT BE
 LOCATED ON PLANS AND IS REQUIRED.
  
 3) NOTE: PLEASE SEE HOUSE LOADS WHICH SHALL INDICATE
 ALL CONTINUOUS LOADS SUCH AS LIGHTING AT 125%. 215.3,
 230.42 ETC
  
 4) NOTE:PLEASE SEE 410.8 FOR MINIMUM CLEARANCES
 PERMITTED IN STORAGE AREAS.
 (UNDER STAIRS) FIX TYPE "H". PLEASE KNOW, WHEN SHELVING
 IS NOT SHOWN, A MIN
 18" IS ASSUMED AND THE LIGHT FIXTURE AS SHOWN AND TYPE
 DESIGNATED SHALL MEET THE MIN CLEARANCES REQUIRED.
 PLEASE ADJUST.
  
  
 5) NOTE: PLEASE SEE METER CENTER FOR THIS BUILDING TYPE
 SEEMS TO INDICATE BEING 400A RATED AND THE SERVICE
 ENTRANCE CONDUCTORS ARE ONLY RATED FOR 350A'S PER
 310.15B6. PLEASE EITHER INSTALL A MAIN BREAKER IN THE
 MC WHICH WILL LIMIT THE LOAD ON THE CONDUCTORS TO
 350A'S OR ADJUST THE CONDUCTORS FOR THE 400A SERVICE
 PROVIDED.
 PLEASE KNOW IF ADJUSTING THE SEC'S AND INCREASING THE
 SIZE TO 400 MCM, THEN PLEASE SEE 250.66 FOR THE SIZING
 OF THE GROUNDING ELECTRODE CONDUCTOR WHICH WILL BE
 REQUIRED TO BE INCREASED TO A 1/0. 310.15B6, 250.66,
 240.4, 240.6
  
 6) NOTE: PLEASE SEE E311 AS THE RATINGS FOR EQUIPMENT
 IS BEING NOTED AND BASED ON A MAIN RATING WITH SERIES
 RATED EQUIPMENT.
 PLEASE SEE SOME BUILDING TYPES WHICH ARE SHOWN AS BEING
 MLO? HOW WILL THE RATINGS BE AFFECTED THEN?
 PLEASE SEE 110.9, AND 240.12 FOR COORDINATION
 REQUIRED.
  
 7) NOTE: PLEASE CLARIFY LOAD CALCULATIONS WHERE THE
 HEAT LOADS ARE NOTED AS BEING FIGURED AT 100%, YET THE
 5KW WHICH IS ON MECH PLANS IS NOT WHAT IS SHOWN IN LOAD
 CALCULATIONS?
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. **IF
 THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE
 NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO
 NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]