| Date |
Text |
| 2006-11-26 09:24:49 | MERRY PLACE |
| | |
| | 418 17TH ST BLDG TYPE 1 |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME |
| | NEW NOTES DUE TO PLANS NOW BEING SUBMITTED WITH SOME |
| | ADDITIONAL INFORMATION. |
| | |
| | ********** UNSAT ************* |
| | |
| | |
| | 1) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 FOR |
| | THE MINIMUM REQUIRED CIRCUITING AND LOADS FOR THE |
| | DINING ROOM CIRCUIT(S). PLEASE ALSO SEE THAT NO OTHER |
| | ELECTRICAL DEVICES SUCH AS LIGHTING MAY BE PLACED ON |
| | SAID CIRCUIT. |
| | MUST BE 20A AND #12 AND ON ONE OR MORE OF THE CIRCUITS |
| | AS NOTED IN CODES ABOVE. |
| | |
| | 2) NOTE: PLEASE BE SURE PLANS REFERENCE THE FOLLOWING |
| | CODES: NFPA-70 2002, NFPA-72 2002. THIS COULD NOT BE |
| | LOCATED ON PLANS AND IS REQUIRED. |
| | |
| | 3) NOTE: PLEASE SEE HOUSE LOADS WHICH SHALL INDICATE |
| | ALL CONTINUOUS LOADS SUCH AS LIGHTING AT 125%. 215.3, |
| | 230.42 ETC |
| | |
| | 4) NOTE:PLEASE SEE 410.8 FOR MINIMUM CLEARANCES |
| | PERMITTED IN STORAGE AREAS. |
| | (UNDER STAIRS) FIX TYPE "H". PLEASE KNOW, WHEN SHELVING |
| | IS NOT SHOWN, A MIN |
| | 18" IS ASSUMED AND THE LIGHT FIXTURE AS SHOWN AND TYPE |
| | DESIGNATED SHALL MEET THE MIN CLEARANCES REQUIRED. |
| | PLEASE ADJUST. |
| | |
| | |
| | 5) NOTE: PLEASE SEE METER CENTER FOR THIS BUILDING TYPE |
| | SEEMS TO INDICATE BEING 400A RATED AND THE SERVICE |
| | ENTRANCE CONDUCTORS ARE ONLY RATED FOR 350A'S PER |
| | 310.15B6. PLEASE EITHER INSTALL A MAIN BREAKER IN THE |
| | MC WHICH WILL LIMIT THE LOAD ON THE CONDUCTORS TO |
| | 350A'S OR ADJUST THE CONDUCTORS FOR THE 400A SERVICE |
| | PROVIDED. |
| | PLEASE KNOW IF ADJUSTING THE SEC'S AND INCREASING THE |
| | SIZE TO 400 MCM, THEN PLEASE SEE 250.66 FOR THE SIZING |
| | OF THE GROUNDING ELECTRODE CONDUCTOR WHICH WILL BE |
| | REQUIRED TO BE INCREASED TO A 1/0. 310.15B6, 250.66, |
| | 240.4, 240.6 |
| | |
| | 6) NOTE: PLEASE SEE E311 AS THE RATINGS FOR EQUIPMENT |
| | IS BEING NOTED AND BASED ON A MAIN RATING WITH SERIES |
| | RATED EQUIPMENT. |
| | PLEASE SEE SOME BUILDING TYPES WHICH ARE SHOWN AS BEING |
| | MLO? HOW WILL THE RATINGS BE AFFECTED THEN? |
| | PLEASE SEE 110.9, AND 240.12 FOR COORDINATION |
| | REQUIRED. |
| | |
| | 7) NOTE: PLEASE CLARIFY LOAD CALCULATIONS WHERE THE |
| | HEAT LOADS ARE NOTED AS BEING FIGURED AT 100%, YET THE |
| | 5KW WHICH IS ON MECH PLANS IS NOT WHAT IS SHOWN IN LOAD |
| | CALCULATIONS? |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. **IF |
| | THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE |
| | NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO |
| | NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |