| Date |
Text |
| 2007-06-19 15:06:17 | *** UNSAT 3RD REVIEW *** |
| | |
| | 1) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE NOW |
| | SUBMITTED WITHOUT THE INPUT DATA REPORTS SHEETS WHICH |
| | ARE REQUIRED. PLEASE SEE STATEMENT ON COVER SHEET EVEN |
| | MENTIONS THIS. |
| | FBC 113-415.1.C. |
| | |
| | 2) NOTE: PLEASE SEE THE FA NOTE NOW MENTIONS THE CODE |
| | SECTION HOWEVER IT DOES INDICATE THE MINIMUM LEVELS AS |
| | NEEDED. MAY NOT QUOTE THE CODE IN LIEU OF THE SPECIFIC |
| | REQUIREMENT. |
| | FBC 11-4.28.1,.2, AND .3(4). |
| | |
| | 3) NOTE: PLEASE SEE PLANS NOW INDICATE A NEW 6-POLE |
| | CONTACTOR AND LIGHTING CONTROLS HOWEVER NO DETAILS FOR |
| | THIS IS SHOWN ON PLANS. NO TIME FOR SCHEDULING, NO |
| | TIMES FOR OVER RIDE DEVICES, NO TIMES ON DEVICES WHERE |
| | COMPLIANCE WITH FBC CHAPTER 13 IS BEING NOTED. |
| | PLEASE CLARIFY AND PROVIDE MORE INFORMATION. |
| | |
| | 4) NOTE: PLEASE SEE THE PREVIOUS TITLE BLOCKS CONTAINED |
| | PRINTED NAME AND PRINTED LICENSE NUMBER OF THE ENGINEER |
| | HOWEVER IT WAS IN THE *PRINTED SEAL* WHICH WAS PLACED |
| | ON PLANS IN LIEU OF THE RAISED SEAL. NOW PLANS ARE |
| | COMING BACK WITHOUT THE PRINTED SEAL AND ONLY THE |
| | PRINTED NAME IS SHOWN. PLEASE BE SURE THE PRINTED |
| | LICENSE NUMBER IS ON PLANS. FAC 61G15-23.002 |
| | PLEASE ALSO CLARIFY WHY THE EXPIRATION DATE FROM FEB 07 |
| | IS BEING SHOWN ON TITLE BLOCKS UNDER ENGINEERS SEAL. AS |
| | THE EXPIRATION DATE HAS SINCE PAST THIS WOULD NOT BE |
| | VALID. THIS LICENSE HAS BEEN VERIFIED WITH THE STATE AS |
| | NOT EXPIRED ON THIS DATE AS NOTED. |
| | |
| | |
| | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |