Plan Review Notes
Plan Review Notes For Permit 06101056
Permit Number 06101056
Review Stop E
Sequence Number 2
Notes
Date Text
2007-03-06 07:28:47*** UNSAT 2ND REVIEW ***
  
  
 1) NOTE: PLEASE INCLUDE THE FOLLOWING CODES ALSO
 RELEVANT TO DESIGN.
 NFPA-70 2002, 2002 NFPA-72.
 RESPONSE MENTIONS THAT THE CODES WERE ADDED HOWEVER
 COULD NOT LOCATE THESE ON THE REVISED SHEETS. PLEASE
 SEE THAT THE ELECTRICAL SHEETS ALSO SHOULD STATE THESE
 CODES.
 .
  
 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION
 REQUIRED ON TITLE BLOCKS FOR THE "P" SHEETS. PLEASE SEE
 THAT A CERTIFICATE OF AUTHORIZATION NUMBER WAS ADDED TO
 THE ELECTRICAL SHEETS HOWEVER THE NUMBER WHICH WAS
 ADDED TO THE PLUMBING SHEETS IS IN FACT THE FLORIDA
 CORPORATION NUMBER WHICH IS NOT THE SAME AS THE CA
 NUMBER. PLEASE CHECK WITH THE DEPARTMENT OF BUSINESS
 AND PROFESSIONAL REGULATION AS THEY WILL BE ABLE TO
 HELP THROUGH THE PROCESS IN OBTAINING A FIRM LICENSE
 NUMBER. IF THE COMPANY HAS A CA NUMBER, PLEASE ADD TO
 TITLE BLOCKS. PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 AND FLORIDA STATUTES 471.023.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE ELECTRICAL SHEETS HAVE NOW COME
 BACK WITHOUT A RAISED SEAL AS REQUIRED IN THE STATE OF
 FLORIDA. FS 471.025, FAC 61G15-23.001
 A PRINT OF THE SEAL IS OK AS LONG AS THE RAISED SEAL IS
 ALSO PRESENT, CLEAR AND VISIBLE WITH ALL INFORMATION ON
 SAID SEAL.
  
 4) NOTE: PLEASE SEE THE FA DEVICES SEE TO BE CROSSED.
 PLEASE SEE THE *A* WHICH IS BEING ASSUMED FOR THE
 AUDIBLE DEVICE INDICATES THE VISUAL LEVELS AS 95CD AND
 THE *V* FOR VISUAL DEVICE INDICATES 95 DB ? PLEASE
 VERIFY BOTH OF THESE. THE PREVIOUS COMMENT REFERENCED
 THE FBC AS NOTED AND LEVELS FOR VISUAL DEVICES WERE
 75CD MINIMUM. PLEASE CLARIFY
 PLEASE SEE FBC 11-4.28.1, .2 AND .3(4). PLEASE
 INDICATE THE MINIMUM AREAS WILL FALL INTO THESE
 EXCEPTIONS.
  
  
 AUDIBLE LEVELS AND LIGHTING LEVELS PER FBC.
  
 5) NOTE: PLEASE KNOW THAT ANY *NEW* LIGHTING AREAS AND
 CONTROLS NOT FOR OPERATION 24HRS A DAY WILL REQUIRE
 AUTOMATED SHUT OFF FOR LIGHTING PER 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 THIS IS FOR AREAS OF ALL NEW INSTALLATION ONLY AND NOT
 24/7 OPERATIONS.
 THIS IS BEING NOTED ONLY, HOWEVER PLEASE RESPOND IN
 LETTER IF ANY OF THESE
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]