| 2006-12-29 14:26:54 | *****DENIED***** |
| | |
| | |
| | |
| | 1. NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE |
| | PREVENTION CODE (2004) EDITION) SHALL BE REFERENCED. |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| | NOT INTERFERE OR HINDER EMERGENCY RESPONSE ACCESS TO |
| | THE SAID PROPERTY OR VICINITY THEREOF (INCLUDING FIRE |
| | LANES). |
| | |
| | 4.PLEASE INDICATE IF THE BUILDING OR PORTIONS OF THE |
| | BUILDING WILL BE OCCUPIED DURING THE PROPOSED SCOPE OF |
| | WORK.IF SO,THIS WILL BE PERMITTED ONLY WHERE |
| | REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION |
| | FEATURES ARE IN PLACE AND MAINTAINED, OR WHERE |
| | ALTERNATIVE LIFE SAFETY MEASURES ACCEPTABLE TO THE AHJ |
| | ARE IN PLACE. |
| | |
| | 5.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL |
| | BE CLASS A OR CLASS B IN ALL CORRIDORS AND LOBBIES, |
| | CLASS A OR CLASS B IN GENERAL ASSEMBLY AREAS HAVING AN |
| | OCCUPANT LOAD OF MORE THAN 300, AND SHALL BE CLASS A, |
| | CLASS B, OR CLASS C IN ASSEMBLY AREAS HAVING AN |
| | OCCUPANT LOADS OF 300 OR FEWER. |
| | |
| | 6.SEE BUILDING PLAN REVIEW COMMENT #5 IN REFERENCE |
| | TO HANDRAILS FOR THE RAMP.PROVIDE THE PRESCIPTIVE |
| | STRENGHT FOR THE HANDRAILS. |
| | |
| | 7.ALL FIRE DOORS SHALL COMPLY WITH NFPA 80. |
| | |
| | 8.ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM AN |
| | AREA HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS |
| | SHALL BE PROVIDE WITH PANIC HARDWARE OR FIRE EXIT |
| | HARWARE, UNLESS OTHERWISE THEY ARE DELAYED-EGRESS LOCKS |
| | OR ACCESS-CONTROLLED EGRESS LOCKS PERMITTED AND |
| | APPROVED BY THE AHJ. |
| | |
| | 9.PLEASE INDICATE LOCATION OF FIRE EXTINGUISHERS, |
| | EXIT LIGHT, EMERGENCY LIGHTS, FIRE PROTECTION SYSTEM |
| | DEVICES, ETC.HOW WILL THEY BE AFFECTED BY THE SCOPE |
| | OF WORK? |
| | |
| | 10.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM |
| | IS/ARE MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE |
| | PLANS AND PERMIT WILL BE REQUIRED. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RE-SUBMITTING, |
| | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH |
| | ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |