| 2006-11-05 11:22:48 | **** UNSAT **** |
| | |
| | 1) NOTE: PLEASE INCLUDE THE FOLLOWING CODES ALSO |
| | RELEVANT TO DESIGN. |
| | 2003 NFPA-101 AND POSSIBLE NFPA-72 2002, 2002 NFPA-72. |
| | PLEASE SEE NOTES ON PLANS INDICATE A NFPA-92? BOCA, |
| | IBCC, ETC. |
| | PLEASE SEE THE SCOPE OF WORK FOR THIS LOCATION IS UNDER |
| | THE 2004 FBC. |
| | PLEASE ALSO SEE COVER SHEET REFERENCESBY THE CITY FOR |
| | 2001, PLEASE KNOW, THIS WOULD BE ACTUALLY THE 2004. |
| | PLEASE BE SURE TO ADJUST ALL NOTES ON ALL SHEETS. |
| | |
| | 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION |
| | REQUIRED ON TITLE BLOCKS FOR BOTH THE "P" AND "E" |
| | SHEETS. PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002 AND FLORIDA STATUTES 471.023.. |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE INDICATE THE NEW FA DEVICES OR EXISTING |
| | IN AREAS BEING REMODELED. PLEASE SEE FBC 11-4.28.1, .2 |
| | AND .3(4). PLEASE INDICATE THE MINIMUM AUDIBLE LEVELS |
| | AND LIGHTING LEVELS PER FBC. |
| | |
| | 4) NOTE: PLEASE SEE METHOD "C" AS INDICATED MENTIONS |
| | TOTAL SQ FT AND WHAT APPEARS TO BE TRADES -OFF-S. |
| | PLEASE SEE 13-415.2.ABC.1, WHICH MENTIONS TABLES |
| | 415.2.C.1 AS TRADE OFFS FOR SPACES ARE NOT PERMITTED. |
| | PLEASE CLARIFY THIS. |
| | |
| | 5) NOTE: PLEASE SEE NO PANEL SCHEDULES WERE SUBMITTED |
| | FOR ALL CIRCUITING AS SHOWN ON PLANS.NO REVIEW FOR |
| | CODE COMPLIANCE OF OVER CURRENT PROTECTION DEVICES, |
| | CONDUCTOR SIZES ETC CAN BE VERIFIED AT THIS TIME. |
| | 240.4, 310.16, 408.4. |
| | FBC ADMIN SECTION, 106.1.2, 106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE SEE SOME RECEPTS IN BATH AREAS WHICH |
| | SHOULD BE GFI PROTECTED WHICH DO NOT INDICATE THIS ON |
| | PLANS. PLEASE KNOW THERE ARE MANY WHICH SHOW GFI |
| | RECEPT, HOWEVER AS SOME OF THESE REFLECT BACK TO PANEL |
| | SCHEDULES IT MAY BE POSSIBLE THAT THE GFI PROTECTION IS |
| | ACTUALLY IN THE PANEL AT THE BREAKER. HOWEVER PLEASE |
| | KNOW AS THE PANEL SCHEDULE(S) HAVE NOT BEEN SUBMITTED |
| | THIS CAN NOT BE VERIFIED AT THIS TIME. |
| | 210.8B1 |
| | |
| | |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT THE ELECTRICAL PLANS AS SUBMITTED. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |