| 2006-11-28 11:18:49 | BUILDING PLAN REVIEW |
| | PERMIT: 06101056 |
| | ADD: 501 VILLAGE BLVD |
| | CONT: MCGOWAN BUILDERS |
| | TEL: (646)533-0342 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3A)CORRECTION SHEET G1.1 BUILDING SUMMARY NOTES: 2004 |
| | FLORIDA BUILDING CODE WITH 2004 WEST PALM BEACH |
| | ADMINISTRATIVE AMENDMENTS |
| | 2004 EXISTING BUILDING CODE |
| | |
| | 3B) 2004 EXISTING BUILDING CODE WHAT LEVEL OF |
| | ALTERATIONS? |
| | |
| | 4) THE P & E TITLE BLOCKS HAVE WCW ENGINEERS, INC IN |
| | THE |
| | TITLEBLOCK BUT THERE IS NO CERTIFICATE OF AUTHORIZATION |
| | FOR THE FIRM.) 61G15-23.002(2)FL. ADMIN. CODE. |
| | PLANS SIGNED & SEALED BY A PROFESSIONAL |
| | ENGINEER SHALL INCLUDE EITHER THE NAME, |
| | ADDRESS AND LICENSE NUMBER OF THE |
| | ENGINEER OR, THE NAME AND LICENSE NUMBER |
| | OF THE ENGINEER AND THE NAME, ADDRESS |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS THROUGH |
| | WHICH THE ENGINEER IS PRACTICING |
| | (471.025 F.S. AND 471.023 F.S.). |
| | |
| | 5) SHEET A1.1 INDICATES THE USE OF A RAMP TO GAIN |
| | ENTRY |
| | |
| | INTO THE CARIDO AREA, BUT NO HANDRAILS ARE INDICATED. |
| | THERE IS A CUT SECTION |
| | DETAIL# 7 OF SHEET A6.2 BUT NO INDICATION OF |
| | HANDRAILS. |
| | 11.4.8.5. HANDRAILS: IF A RAMP HAS |
| | A RISE GREATER THAN 6" OR A HORIZONTAL |
| | PROJECTION GREATER THAN 72", THEN IT |
| | SHALL HAVE HANDRAILS ON BOTH SIDES. |
| | |
| | 6) SHEET A1.1 ALSO INDICATES THE USE OF A RAMP |
| | IN THE FREE WEIGHTS AREA, PLEASE INDICATE |
| | THE USE OF HANDRAILS, |
| | 11.4.8.5. HANDRAILS: IF A RAMP HAS |
| | A RISE GREATER THAN 6" OR A HORIZONTAL |
| | PROJECTION GREATER THAN 72", THEN IT |
| | SHALL HAVE HANDRAILS ON BOTH SIDES. |
| | |
| | 7)A1.1 RECEPTION DESK, PLANS DO NOT PROVIDE DETAILS |
| | FOR ACCESSIBILITY: |
| | 11-4.32.4 HEIGHT OF TABLES OR COUNTERS . |
| | THE TOPS OF ACCESSIBLE TABLES AND COUNTERS SHALL BE |
| | FROM 28 INCHES |
| | TO 34 INCHES (710 MM TO 865 MM) ABOVE THE FINISH FLOOR |
| | OR GROUND. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |