Plan Review Notes
Plan Review Notes For Permit 06101056
Permit Number 06101056
Review Stop B
Sequence Number 1
Notes
Date Text
2006-11-28 11:18:49BUILDING PLAN REVIEW
 PERMIT: 06101056
 ADD: 501 VILLAGE BLVD
 CONT: MCGOWAN BUILDERS
 TEL: (646)533-0342
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3A)CORRECTION SHEET G1.1 BUILDING SUMMARY NOTES: 2004
 FLORIDA BUILDING CODE WITH 2004 WEST PALM BEACH
 ADMINISTRATIVE AMENDMENTS
 2004 EXISTING BUILDING CODE
  
 3B) 2004 EXISTING BUILDING CODE WHAT LEVEL OF
 ALTERATIONS?
  
 4) THE P & E TITLE BLOCKS HAVE WCW ENGINEERS, INC IN
 THE
 TITLEBLOCK BUT THERE IS NO CERTIFICATE OF AUTHORIZATION
 FOR THE FIRM.) 61G15-23.002(2)FL. ADMIN. CODE.
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
  
 5) SHEET A1.1 INDICATES THE USE OF A RAMP TO GAIN
 ENTRY
  
 INTO THE CARIDO AREA, BUT NO HANDRAILS ARE INDICATED.
 THERE IS A CUT SECTION
 DETAIL# 7 OF SHEET A6.2 BUT NO INDICATION OF
 HANDRAILS.
 11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 6) SHEET A1.1 ALSO INDICATES THE USE OF A RAMP
 IN THE FREE WEIGHTS AREA, PLEASE INDICATE
 THE USE OF HANDRAILS,
 11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 7)A1.1 RECEPTION DESK, PLANS DO NOT PROVIDE DETAILS
 FOR ACCESSIBILITY:
 11-4.32.4 HEIGHT OF TABLES OR COUNTERS .
 THE TOPS OF ACCESSIBLE TABLES AND COUNTERS SHALL BE
 FROM 28 INCHES
 TO 34 INCHES (710 MM TO 865 MM) ABOVE THE FINISH FLOOR
 OR GROUND.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  