| Date |
Text |
| 2006-12-29 15:04:56 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | NOTE: 1ST REVIEW UNDER PERMIT |
| | |
| | **********FROM PREVIOUS REVIEW********** |
| | |
| | 1. SHEETS DELETED. WILL BE SUBMITTED AT THE TIME OF |
| | APPLICATION SUBMITTAL PER RESPONSE. |
| | |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. DELETED |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | 9.OK NOT REQUIRED FOR THIS BUILDING. |
| | 10. OK NOT REQUIRED THIS BUILDING. |
| | 11. OK |
| | 12. OK |
| | 13. OK (UNIT LOCATION ONLY) |
| | 14. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 15. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 16. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 17. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 18. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 19. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 20. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 21. OK. NOT REQUIRED FOR THIS BUILDING. |
| | |
| | 22. SHTS P201 & P202 PLAN KEY NOTE #2 INDICATES |
| | KITCHEN SINK ARM IS RUN UNDER THE SLAB, |
| | BUT THE 3S RISER DIAGRAM ON SHT P402 |
| | INDICATES THE SINK ARM IS ABOVE THE SLAB |
| | PLEASE CLARIFY AND CORRELATE THE NOTES, |
| | FLOOR PLAN, AND RISER DIAGRAM. SECTION |
| | 106.1.1. |
| | ****RESPONSE NOTED. NO ACTION TAKEN. |
| | ****NO RESPONSE, NOT ADDRESSED |
| | |
| | 23. OK |
| | 24. OK. (GAS NOTE) |
| | 25. OK. NOT REQUIRED FOR THIS BUILDING |
| | 26. OK |
| | |
| | 27. SUBMIT A BUILDING DRAIN SANITARY |
| | RISER DIAGRAM ISOMETRIC THAT REFLECTS |
| | THE FLOOR PLAN FOR EACH BUILDING. |
| | SECTION 106.1.5.1.3. SHOW ALL PIPE |
| | SIZES, RISER LOCATIONS, TRAPS, VENTS, |
| | AND DFU'S AS THEY ACCUMULATE IN THE |
| | SYSTEM. |
| | ****RESPONSE NOTED. RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN. CLEANOUT AT THE BACK OF THE BUILDING NOT |
| | SHOWN. SHOW CLEANOUTS REQUIRED BY SECTION 708.3.3, |
| | CHANGE OF DIRECTIONGREATER THAN 45 DEGREES. |
| | ****RESPONSE NOTED, BUT THE CLEANOUT AT THE BACK OF THE |
| | BUILDING SHOWN ON THE FLOOR PLAN IS STILL NOT SHOWN ON |
| | THE RISER DIAGRAM. |
| | |
| | 28. OK |
| | 29. OK. NOT REQUIRED THIS BUILDING. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | SUBMIT ONE SET OF PLANS FROM FIRST |
| | REVIEW FOR COMPARISON TO EXPEDITE 2ND |
| | REVIEW. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. OK |
| | 2B. OK |
| | 3B. OK |
| | |
| | 4B. SEPARATE GAS PERMIT REQUIRED. SUBMIT THE FOLLOWING |
| | INFORMATION: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. AN ISOMETRIC IS REQUIRED FOR EACH GAS |
| | SYSTEM SHOWING THE PIPING FROM THE METER TO THE MOST |
| | REMOTEAPPLIANCE FOR EACH UNIT. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | H. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | |
| | ****RESPONSE NOTED, ALL INFORMATION/PLANS TO BE |
| | SUBMITTED WITH GAS PERMIT APPLICATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |