| Plan Review Notes For Permit 06101053 |
| Permit Number |
06101053 |
|
| Review Stop |
B |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2007-10-02 09:16:29 | BUILDING C-3 RAMP REVISION BUILDING REVIEW SECOND | | | CHECKLIST. | | | REVIEW DONE UNDER FBC 2004. | | | | | | 1- PRODUCT APPROVAL FL5267 SUBMITTEDIS A "HOLLOW | | | METAL FRAME" ASSEMBLY ONLY.NEED TO PROVIDE THE | | | PRODUCT APPROVAL FOR THE DOOR TO BE USED AS REQUIRED BY | | | GENERAL NOTE #2 SHOWN ON SHEET 1 OF 4 OF DRAWING | | | FL-640. | | | | | | 2-"HOLLOW METAL FRAME ANCHORING" SYSTEM SUBMITTED | | | DOESN'T MEET THE DESIGN PRESSURES CALCULATED BY THE | | | ENGINEER. SEESHEET 1 OF 4 OFDRAWING FL-640 | | | SUBMITTED AND THE DESIGN PRESSURES CALCULATED BY THE | | | ENGINEER.SUBMIT PRODUCT APPROVAL THAT MEETS OR | | | EXCEEDS CALCULATED DESIGN PRESSURES. | | | | | | REMAINDER: | | | DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING ALL | | | PRODUCT APPROVALS PRIOR TO SUBMITTAL. SEC. 106.3.3 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | 3-HANDICAPPED RAMP REQUIRES A MINIMUM LENGTH OF 15'-4 | | | 1/2" TO ACHIEVE THE MAXIMUM RATIO OF 1:12FOR A HEIGHT | | | OF 1'-3 3/8".SEC. 11-4.8.2 FBC 2004. REVISE | | | DIMENSIONS AS REQUIRED OR PROVIDE COMPLETE CALCULATIONS | | | SHOWING HOW THE 15'-4 3/8" WAS ACHIEVED. SEC. 106.1.2 | | | CITY AMENDMENTS TO FBC 2004. | | | | | | 4- RE-SUBMITTAL FORM SAYS THAT NUMBER OF REVISED PAGES | | | ARE SIX.ACTUAL NUMBER OF REVISED PAGES SUBMITTED ARE | | | 16. THEREFORE OWES $100 FOR CORRECT NUMBER OF REVISED | | | PAGES. | | | | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|