Plan Review Notes
Plan Review Notes For Permit 06101053
Permit Number 06101053
Review Stop B
Sequence Number 7
Notes
Date Text
2007-10-02 09:16:29BUILDING C-3 RAMP REVISION BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW DONE UNDER FBC 2004.
  
 1- PRODUCT APPROVAL FL5267 SUBMITTEDIS A "HOLLOW
 METAL FRAME" ASSEMBLY ONLY.NEED TO PROVIDE THE
 PRODUCT APPROVAL FOR THE DOOR TO BE USED AS REQUIRED BY
 GENERAL NOTE #2 SHOWN ON SHEET 1 OF 4 OF DRAWING
 FL-640.
  
 2-"HOLLOW METAL FRAME ANCHORING" SYSTEM SUBMITTED
 DOESN'T MEET THE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER. SEESHEET 1 OF 4 OFDRAWING FL-640
 SUBMITTED AND THE DESIGN PRESSURES CALCULATED BY THE
 ENGINEER.SUBMIT PRODUCT APPROVAL THAT MEETS OR
 EXCEEDS CALCULATED DESIGN PRESSURES.
  
 REMAINDER:
 DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING ALL
 PRODUCT APPROVALS PRIOR TO SUBMITTAL. SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 3-HANDICAPPED RAMP REQUIRES A MINIMUM LENGTH OF 15'-4
 1/2" TO ACHIEVE THE MAXIMUM RATIO OF 1:12FOR A HEIGHT
 OF 1'-3 3/8".SEC. 11-4.8.2 FBC 2004. REVISE
 DIMENSIONS AS REQUIRED OR PROVIDE COMPLETE CALCULATIONS
 SHOWING HOW THE 15'-4 3/8" WAS ACHIEVED. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 4- RE-SUBMITTAL FORM SAYS THAT NUMBER OF REVISED PAGES
 ARE SIX.ACTUAL NUMBER OF REVISED PAGES SUBMITTED ARE
 16. THEREFORE OWES $100 FOR CORRECT NUMBER OF REVISED
 PAGES.
  
  