| Plan Review Notes For Permit 06101053 |
| Permit Number |
06101053 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-04-11 12:57:34 | PASSED/PROVISO | | | | | | REVISION REQUIRED FOR SHEET P402. REVISION SHALL BE | | | SUBMITTED WITHIN 60 OF THE DATE THEPERMIT IS USSUED. | | | THE RISER DIAGRAM INDICATES THE LAVS AS "S" TRAPS. 3" | | | IS REQUIRED TO THE W/M'S. THE TRAP FOR THE W/M IS NOT | | | VENTED AS DRAWN.BOTH W/M'S SHALL BE SHOWN AS BEING | | | LOCATED ACROSS THE ROOM FROM THE BATHROOM FIXTURES. | | | | | | KENNETH H. STEVENS | | | PLUMBING PLAN REVIEW | | | WEST PALM BEACH | | | PH. (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL - [email protected] |
|