Plan Review Notes
Plan Review Notes For Permit 06101053
Permit Number 06101053
Review Stop P
Sequence Number 2
Notes
Date Text
2006-12-28 15:22:23DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 NOTE: FIRST PLAN REVIEW FOR APPLICATION
  
 **********FROM PREVIOUS REVIEW**********
  
 1. SHEETS DELETED. WILL BE SUBMITTED AT THE TIME OF
 APPLICATION SUBMITTAL PER RESPONSE.
  
 2. OK
  
 3. OK
 4. OK
 5. DELETED
 6. OK
 7.OK NOT REQUIRED FOR THIS BUILDING.
 8.OK NOT REQUIRED FOR THIS BUILDING.
 9.OK NOT REQUIRED FOR THIS BUILDING.
 10. OK NOT REQUIRED THIS BUILDING.
 11. OK
 12. OK
 13. OK (UNIT LOCATION ONLY)
 14. OK
 15. OK
 16. OK. NOT REQUIRED FOR THIS BUILDING.
 17. OK
 18. OK
 19. OK. NOT REQUIRED FOR THIS BUILDING.
  
 20. SHTS A802 DETAILS 04 & 09 INDICATE
 THE CENTERLINE OF THE W/C 18" OFF THE
 WALL, AND THE CENTERLINE OF THE LAV TO
 BE MIN. 15" OFF THE WALL (TO BE CENTERED
 ON THE 30" WIDTH OF THE CLEAR FLOOR
 SPACE). SECTIONS 11-4.16.2, 11-4.19.3
 AND FIG. 28.
 ****RESPONSE NOTED, BUT THESE REQUIREMENTS ARE FOR
 CHAPTER 11 AS THE TOILET ROOM IS NOT FOR FAIR HOUSING.
 PLEASE INDICATE THE MEASUREMENTS AS REQUESTED ON THE
 DETAIL FOR THAT TOILET ROOM. ALSO SHOW THE CLEAR FLOOR
 SPACE REQUIRED IN SECTION 11-4.16..2.
 ****RESPONSE NOTED, BUT SHT A802 HAS NOT BEEN
 SUBMITTED.
  
 21. OK
 22. OK. NOT REQUIRED FOR THIS BUILDING.
 23 OK
 24. OK
 25. OK. NOT REQUIRED FOR THIS BUILDING
 26. OK
  
 27. SUBMIT A BUILDING DRAIN SANITARY
 RISER DIAGRAM ISOMETRIC THAT REFLECTS
 THE FLOOR PLAN FOR EACH BUILDING.
 SECTION 106.1.5.1.3. SHOW ALL PIPE
 SIZES, RISER LOCATIONS, TRAPS, VENTS,
 AND DFU'S AS THEY ACCUMULATE IN THE
 SYSTEM.
 ****RESPONSE NOTED. HORIZONTAL BUILDING DRAIN ISOMETRIC
 RISER DIAGRAM NOT SUBMITTED. ONLY RESIDENTIAL UNIT
 RISER DIAGRAMS FOUND.
 ****RESPONSE NOTED, BUT THE THE WASH MACHINES SHALL NOT
 DRAIN THRU THE HORIZONTAL WET VENT OF THE BATHROOM
 FIXTURES. THE WASH MACHINE SHALL DRAIN DOWNSTREAM OF
 THE THE BATHROOM FIXTURES. SECTION 909.1.-THE RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN AT THE LAV'S
 AND WASH MACHINES. IN THE RISER THE LAV ARMS AND THE
 WASH MACHINE BRANCH LINES ARE INDICATED AS ABOVE THE
 SLAB, WHERE AS THE PIPING FOR THE LAVS AND WASH
 MACHINES ARE INDICATED AS BELOW THE SLAB. PLEASE
 CORRELATE. SECTION 106.1.1.-THE WASH MACHINE SHALL
 DRAIN INTO A BRANCH LINE A MINIMUM OF 3". SECTION
 406.3.
  
 28. SUBMIT A WATER RISER DIAGRAM FOR
 EACH BUILDING. SHOW ALL PIPE SIZES,
 VALVES. RISER CONNECTIONS, AND INDICATE
 BLDG. SHUTOFF VALVE AS WELL AS INDICATE
 THE RPZV BACKFLOW REQUIRED FOR EACH
 BUILDING. SECTIONS 106.1.5.1.3 AND
 SECTION 608.13.2.
 ****RESPONSE NOTED. NO RISER FROM METER TO UNITS
 SUBMITTED. ONLY UNIT RISER SHOWN.
 ****RESPONSE NOTED, BUT A FULL OPEN VALVE IS REQUIRED
 ON ALL WATER DOWN-FEED LINES TO THE DRINKING FOUNTAIN,
 W/C & LAV, AND THE SINK. SECTION 606.1(4).
  
 29. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 SUBMIT ONE SET OF PLANS FROM FIRST
 REVIEW FOR COMPARISON TO EXPEDITE 2ND
 REVIEW.
  
 **************NEW COMMENTS**************
  
 1B. OK
 2B. OK
 3B. OK
 4B. OK - SEPARATE GAS PERMIT REQUIRED.-GAS
 PLANS/REQUIREMENTS SHALL BE SUBMITTED WITH GAS
 APPLICATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved