| Date |
Text |
| 2006-12-28 15:22:23 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FHA-98 DESIGN MANUAL |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | NOTE: FIRST PLAN REVIEW FOR APPLICATION |
| | |
| | **********FROM PREVIOUS REVIEW********** |
| | |
| | 1. SHEETS DELETED. WILL BE SUBMITTED AT THE TIME OF |
| | APPLICATION SUBMITTAL PER RESPONSE. |
| | |
| | 2. OK |
| | |
| | 3. OK |
| | 4. OK |
| | 5. DELETED |
| | 6. OK |
| | 7.OK NOT REQUIRED FOR THIS BUILDING. |
| | 8.OK NOT REQUIRED FOR THIS BUILDING. |
| | 9.OK NOT REQUIRED FOR THIS BUILDING. |
| | 10. OK NOT REQUIRED THIS BUILDING. |
| | 11. OK |
| | 12. OK |
| | 13. OK (UNIT LOCATION ONLY) |
| | 14. OK |
| | 15. OK |
| | 16. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 17. OK |
| | 18. OK |
| | 19. OK. NOT REQUIRED FOR THIS BUILDING. |
| | |
| | 20. SHTS A802 DETAILS 04 & 09 INDICATE |
| | THE CENTERLINE OF THE W/C 18" OFF THE |
| | WALL, AND THE CENTERLINE OF THE LAV TO |
| | BE MIN. 15" OFF THE WALL (TO BE CENTERED |
| | ON THE 30" WIDTH OF THE CLEAR FLOOR |
| | SPACE). SECTIONS 11-4.16.2, 11-4.19.3 |
| | AND FIG. 28. |
| | ****RESPONSE NOTED, BUT THESE REQUIREMENTS ARE FOR |
| | CHAPTER 11 AS THE TOILET ROOM IS NOT FOR FAIR HOUSING. |
| | PLEASE INDICATE THE MEASUREMENTS AS REQUESTED ON THE |
| | DETAIL FOR THAT TOILET ROOM. ALSO SHOW THE CLEAR FLOOR |
| | SPACE REQUIRED IN SECTION 11-4.16..2. |
| | ****RESPONSE NOTED, BUT SHT A802 HAS NOT BEEN |
| | SUBMITTED. |
| | |
| | 21. OK |
| | 22. OK. NOT REQUIRED FOR THIS BUILDING. |
| | 23 OK |
| | 24. OK |
| | 25. OK. NOT REQUIRED FOR THIS BUILDING |
| | 26. OK |
| | |
| | 27. SUBMIT A BUILDING DRAIN SANITARY |
| | RISER DIAGRAM ISOMETRIC THAT REFLECTS |
| | THE FLOOR PLAN FOR EACH BUILDING. |
| | SECTION 106.1.5.1.3. SHOW ALL PIPE |
| | SIZES, RISER LOCATIONS, TRAPS, VENTS, |
| | AND DFU'S AS THEY ACCUMULATE IN THE |
| | SYSTEM. |
| | ****RESPONSE NOTED. HORIZONTAL BUILDING DRAIN ISOMETRIC |
| | RISER DIAGRAM NOT SUBMITTED. ONLY RESIDENTIAL UNIT |
| | RISER DIAGRAMS FOUND. |
| | ****RESPONSE NOTED, BUT THE THE WASH MACHINES SHALL NOT |
| | DRAIN THRU THE HORIZONTAL WET VENT OF THE BATHROOM |
| | FIXTURES. THE WASH MACHINE SHALL DRAIN DOWNSTREAM OF |
| | THE THE BATHROOM FIXTURES. SECTION 909.1.-THE RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN AT THE LAV'S |
| | AND WASH MACHINES. IN THE RISER THE LAV ARMS AND THE |
| | WASH MACHINE BRANCH LINES ARE INDICATED AS ABOVE THE |
| | SLAB, WHERE AS THE PIPING FOR THE LAVS AND WASH |
| | MACHINES ARE INDICATED AS BELOW THE SLAB. PLEASE |
| | CORRELATE. SECTION 106.1.1.-THE WASH MACHINE SHALL |
| | DRAIN INTO A BRANCH LINE A MINIMUM OF 3". SECTION |
| | 406.3. |
| | |
| | 28. SUBMIT A WATER RISER DIAGRAM FOR |
| | EACH BUILDING. SHOW ALL PIPE SIZES, |
| | VALVES. RISER CONNECTIONS, AND INDICATE |
| | BLDG. SHUTOFF VALVE AS WELL AS INDICATE |
| | THE RPZV BACKFLOW REQUIRED FOR EACH |
| | BUILDING. SECTIONS 106.1.5.1.3 AND |
| | SECTION 608.13.2. |
| | ****RESPONSE NOTED. NO RISER FROM METER TO UNITS |
| | SUBMITTED. ONLY UNIT RISER SHOWN. |
| | ****RESPONSE NOTED, BUT A FULL OPEN VALVE IS REQUIRED |
| | ON ALL WATER DOWN-FEED LINES TO THE DRINKING FOUNTAIN, |
| | W/C & LAV, AND THE SINK. SECTION 606.1(4). |
| | |
| | 29. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | SUBMIT ONE SET OF PLANS FROM FIRST |
| | REVIEW FOR COMPARISON TO EXPEDITE 2ND |
| | REVIEW. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. OK |
| | 2B. OK |
| | 3B. OK |
| | 4B. OK - SEPARATE GAS PERMIT REQUIRED.-GAS |
| | PLANS/REQUIREMENTS SHALL BE SUBMITTED WITH GAS |
| | APPLICATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |