Plan Review Notes
Plan Review Notes For Permit 06101053
Permit Number 06101053
Review Stop B
Sequence Number 2
Notes
Date Text
2006-12-28 16:54:33BUILDING REVIEW SECOND CHECKLIST:
 1- REVISE ENERGY CALCULATIONS:
 A) AS REQUESTED ON PREVIOUS CHECKLIST, CALCULATIONS
 NEED TO BE DONE FOR THE WHOLE BUILDING, NOT FOR EACH
 UNIT AS REQUIRED BY SEC. 13-600.0 METHOD A OF FBC
 2004.
  
  
 B) AS REQUESTED ON PREVIOUS CHECKLIST, ENGINEER TO
 PROVIDE ALL HIS INFORMATION AS REQUIREDBY CHAPTER 471
 FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE SEC.
 61G15-23.002.
  
 C) CALCULATIONS SUBMITTED FOR INDIVIDUAL UNITS HAVE
 THE FOLLOWING INCORRECT INFORMATION:
 * NUMBER OF BEDROOMS.
 ** SLAB ON GRADE TOTAL PERIMETER FEET.
 *** CLARIFY HOW ARE THESE CALCULATIONS DONE FOR
 WORST CASE SCENARIO IF THERE IS NOT SHEET SHOWING
 OPENINGS SUN EXPOSURE ORIENTATION.
  
 2-A) NORTH WALL 15%OPENINGS ALLOWED PER TABLE 704.8
 FBC 2004AND SEC. 704.8.1 (AUTOMATIC SPRINKLER
 SYSTEM).NEED TO BE 2 HOURS WALL FIRE RESISTANCE.
 REVISE AS REQUIRED. SEE SURVEY FOR BUILDING SETBACK IN
 RELATIONSHIP TO PROPERTY LINE. TABLES 601, 602 AND
 704.8 APPLY. DOES WHY I ASKED FOR THE SURVEY TO VERIFY
 COMPLIANCE WITH THESE TABLES.
  
 B) DOOR SWINGS OUT TO PUBLIC RIGHT OF WAY ON EAST
 WALL. NEED DOOR THAT SWINGS IN.SEC. 3202.2 FBC 2004.
  
 ***NOTE: PROVIDE PRODUCT APPROVAL FOR INSWING DOOR.
 DESIGNER OF RECORD TO REVIEW IT AND APPROVE IT. SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004
  
 C) NORTH ARROW IN SURVEY IS POINTING TO THE WRONG
 DIRECTION. REVISE AS REQUIRED.
  
 D) ARCHITECT TO CHECK RECORDED SURVEY AND CHANGE ALL
 DIMENSIONS AS REQUIRED. THIS APPLIES TO ALL BUILDINGS.
 RECORDED SURVEY IS THE OFFICIAL LEGAL DOCUMENT FOR
 PROPERTY LINES AND BUILDING SEPARATION.
  
 E) SURVEY SHOWS EAST WALL TO BERIGHT ON THE
 PROPERTY LINE. THIS BUILDING HAS ABOUT 6 " SETBACK IN
 THE FOOTPRINT.NONE OF THE ARCHITECTURAL OR STRUCTURAL
 DRAWINGS SHOW EXACT DIMENSION.PROVIDE EXACT DIMENSION
 AND SURVEY TO SHOW THAT BUILDING FOOTING IS NOT
 ENCROACHING INTO THE PUBLIC RIGHT OF WAY.
  
 3- REVISION CLOUDS ON SHEET A004 DON'T ALLOW TO READ
 THE INFORMATION.
  
 4- SURVEY AND SITE PLAN SHOWN ON SHEETS A100, A101 AND
 A102 DON'T MATCH. SEE PARKING SPACES FOR BUILDING C3.
 THERE IS AN ALLEY WHERE PARKING SPACES ARE SHOWN.
 REVISE AS REQUIRED.
  
 5- PROVIDE ENERGY CALCULATIONS FOR COMMERCIAL AREA AS
 REQUIRED BY CHAPTER 13 FBC 2004.
  
 6- PLEASE MAKE SURE ENERGY CALCULATIONS MATCH
 CORRESPONDING BUILDING ADDRESS, BUILDING TYPE, PERMIT
 NUMBER, ETC.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) UNIT ENTRY DOOR. DRAWINGS SUBMITTED ARE FOR
 "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS.
  
 B) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON ALL
 PLANS AND DETAILS. (NOT JUST THE ONES LISTED IN THE
 TRUSS ANCHOR SCHEDULE). PROVIDE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIC
 CONNECTORS.
  
 C) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL
 ASSEMBLY U905.
  
 D) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER
 HEATER.
  
 E) FIXED WINDOWS. NEED PRODUCT APPROVAL FOR LARGE
 MISSILE IMPACT AS REQUIRED BY SEC. 1609.1.4. NOA
 02-0123.03 SUBMITTED IS FOR SMALL MISSILE IMPACT.
  
 F) ALUMINUM TUBE MULLIONS. NEED PRODUCT APPROVAL FOR
 LARGE MISSILE IMPACT. NOA 02-0501.04 SUBMITTED HAS NOT
 RATING.
 ***INDICATE MULLION FASTENING. SECTION 1609FBC 2004
 AND SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 G) FLAT ROOF: PROVIDE NAIL ENHANCING CALCULATIONS
 FOR PERIMETER AND CORNER AREAS USING RAS 117 STANDARD
 AS REQUIRED BY GENERAL LIMITATION #7 ON PAGE 32 OF 32
 OF NOA #03-0501.02 SUBMITTED.CALCULATIONS TO CLEARLY
 IDENTIFY NOA AND SPECIFICSELECTED ASSEMBLY.
  
  
 8) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITTING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 9- THE INTENTION OF THE CODE IS TO DETERMINE THE
 MAXIMUM NUMBER OF PEOPLE EXPECTED TO OCCUPY THE
 BUILDING OR ROOMS OR SPACES WITHIN THE BUILDING AT ANY
 GIVEN TIME AND UNDER ALL PROBABLE CONDITIONS. THIS IS A
 SAFETY ISSUE BECAUSE DEPENDING ON THE NUMBER OF PEOPLE
 ALL EGRESS REQUIREMENTS SHALL BE MET. ROOMS COULD BE
 USED FOR ANY PURPOSE AT ANY TIME. PROOF OF THIS IS THAT
 OWNER CHANGED THE USE ALREADY. THAT'S WHY OCCUPANCY
 LOAD CALCULATIONS NEED TO BE ESTABLISHED BY THE LARGEST
 NUMBER COMPUTED IN ACCORDANCE WITH SECTIONS 1004.1.1
 THROUGH 1004.1.3. ACCORDING TO THIS SECTION TABLE
 1004.1.2 FBC 2004 AND FLOOR PLANS, THE FLOOR AREA PER
 OCCUPANT SHALL BE CALCULATED FOR 5S.F..
 PROVIDE CALCULATIONS FOR NUMBER OF PEOPLE ON EACH ROOM
 OR SPACE TO VERIFY COMPLIANCE WITH TOTAL NUMBER OF
 PEOPLE.
  
  
 10-SHEET S-1 ROOF FRAMING PLAN PLAN CALLS FOR METAL
 TRELLIS. PROVIDE COMPLETE DRAWINGS/DETAILS AND PRODUCT
 APPROVAL. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 AND
 SEC. 1609 FBC 2004.
  
 11- NEED TO CONTACT HAROLD PISKURA, INSPECTION SERVICES
 MANAGER (561)805-6711, TO COORDINATE SPECIAL INSPECTOR
 SERVICES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712