| 2006-12-28 16:54:33 | BUILDING REVIEW SECOND CHECKLIST: |
| | 1- REVISE ENERGY CALCULATIONS: |
| | A) AS REQUESTED ON PREVIOUS CHECKLIST, CALCULATIONS |
| | NEED TO BE DONE FOR THE WHOLE BUILDING, NOT FOR EACH |
| | UNIT AS REQUIRED BY SEC. 13-600.0 METHOD A OF FBC |
| | 2004. |
| | |
| | |
| | B) AS REQUESTED ON PREVIOUS CHECKLIST, ENGINEER TO |
| | PROVIDE ALL HIS INFORMATION AS REQUIREDBY CHAPTER 471 |
| | FLORIDA STATUTES AND FLORIDA ADMINISTRATIVE CODE SEC. |
| | 61G15-23.002. |
| | |
| | C) CALCULATIONS SUBMITTED FOR INDIVIDUAL UNITS HAVE |
| | THE FOLLOWING INCORRECT INFORMATION: |
| | * NUMBER OF BEDROOMS. |
| | ** SLAB ON GRADE TOTAL PERIMETER FEET. |
| | *** CLARIFY HOW ARE THESE CALCULATIONS DONE FOR |
| | WORST CASE SCENARIO IF THERE IS NOT SHEET SHOWING |
| | OPENINGS SUN EXPOSURE ORIENTATION. |
| | |
| | 2-A) NORTH WALL 15%OPENINGS ALLOWED PER TABLE 704.8 |
| | FBC 2004AND SEC. 704.8.1 (AUTOMATIC SPRINKLER |
| | SYSTEM).NEED TO BE 2 HOURS WALL FIRE RESISTANCE. |
| | REVISE AS REQUIRED. SEE SURVEY FOR BUILDING SETBACK IN |
| | RELATIONSHIP TO PROPERTY LINE. TABLES 601, 602 AND |
| | 704.8 APPLY. DOES WHY I ASKED FOR THE SURVEY TO VERIFY |
| | COMPLIANCE WITH THESE TABLES. |
| | |
| | B) DOOR SWINGS OUT TO PUBLIC RIGHT OF WAY ON EAST |
| | WALL. NEED DOOR THAT SWINGS IN.SEC. 3202.2 FBC 2004. |
| | |
| | ***NOTE: PROVIDE PRODUCT APPROVAL FOR INSWING DOOR. |
| | DESIGNER OF RECORD TO REVIEW IT AND APPROVE IT. SEC. |
| | 106.3.3 CITY AMENDMENTS TO FBC 2004 |
| | |
| | C) NORTH ARROW IN SURVEY IS POINTING TO THE WRONG |
| | DIRECTION. REVISE AS REQUIRED. |
| | |
| | D) ARCHITECT TO CHECK RECORDED SURVEY AND CHANGE ALL |
| | DIMENSIONS AS REQUIRED. THIS APPLIES TO ALL BUILDINGS. |
| | RECORDED SURVEY IS THE OFFICIAL LEGAL DOCUMENT FOR |
| | PROPERTY LINES AND BUILDING SEPARATION. |
| | |
| | E) SURVEY SHOWS EAST WALL TO BERIGHT ON THE |
| | PROPERTY LINE. THIS BUILDING HAS ABOUT 6 " SETBACK IN |
| | THE FOOTPRINT.NONE OF THE ARCHITECTURAL OR STRUCTURAL |
| | DRAWINGS SHOW EXACT DIMENSION.PROVIDE EXACT DIMENSION |
| | AND SURVEY TO SHOW THAT BUILDING FOOTING IS NOT |
| | ENCROACHING INTO THE PUBLIC RIGHT OF WAY. |
| | |
| | 3- REVISION CLOUDS ON SHEET A004 DON'T ALLOW TO READ |
| | THE INFORMATION. |
| | |
| | 4- SURVEY AND SITE PLAN SHOWN ON SHEETS A100, A101 AND |
| | A102 DON'T MATCH. SEE PARKING SPACES FOR BUILDING C3. |
| | THERE IS AN ALLEY WHERE PARKING SPACES ARE SHOWN. |
| | REVISE AS REQUIRED. |
| | |
| | 5- PROVIDE ENERGY CALCULATIONS FOR COMMERCIAL AREA AS |
| | REQUIRED BY CHAPTER 13 FBC 2004. |
| | |
| | 6- PLEASE MAKE SURE ENERGY CALCULATIONS MATCH |
| | CORRESPONDING BUILDING ADDRESS, BUILDING TYPE, PERMIT |
| | NUMBER, ETC. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) UNIT ENTRY DOOR. DRAWINGS SUBMITTED ARE FOR |
| | "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOORS. |
| | |
| | B) ALL USP OR SIMPSON CONNECTORS SPECIFIED ON ALL |
| | PLANS AND DETAILS. (NOT JUST THE ONES LISTED IN THE |
| | TRUSS ANCHOR SCHEDULE). PROVIDE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIC |
| | CONNECTORS. |
| | |
| | C) 2 HOUR CONCRETE BLOCK AS REQUIRED BY UL WALL |
| | ASSEMBLY U905. |
| | |
| | D) EXTERIOR DOOR PANEL FOR RECESSED GAS WATER |
| | HEATER. |
| | |
| | E) FIXED WINDOWS. NEED PRODUCT APPROVAL FOR LARGE |
| | MISSILE IMPACT AS REQUIRED BY SEC. 1609.1.4. NOA |
| | 02-0123.03 SUBMITTED IS FOR SMALL MISSILE IMPACT. |
| | |
| | F) ALUMINUM TUBE MULLIONS. NEED PRODUCT APPROVAL FOR |
| | LARGE MISSILE IMPACT. NOA 02-0501.04 SUBMITTED HAS NOT |
| | RATING. |
| | ***INDICATE MULLION FASTENING. SECTION 1609FBC 2004 |
| | AND SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | G) FLAT ROOF: PROVIDE NAIL ENHANCING CALCULATIONS |
| | FOR PERIMETER AND CORNER AREAS USING RAS 117 STANDARD |
| | AS REQUIRED BY GENERAL LIMITATION #7 ON PAGE 32 OF 32 |
| | OF NOA #03-0501.02 SUBMITTED.CALCULATIONS TO CLEARLY |
| | IDENTIFY NOA AND SPECIFICSELECTED ASSEMBLY. |
| | |
| | |
| | 8) DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITTING |
| | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 9- THE INTENTION OF THE CODE IS TO DETERMINE THE |
| | MAXIMUM NUMBER OF PEOPLE EXPECTED TO OCCUPY THE |
| | BUILDING OR ROOMS OR SPACES WITHIN THE BUILDING AT ANY |
| | GIVEN TIME AND UNDER ALL PROBABLE CONDITIONS. THIS IS A |
| | SAFETY ISSUE BECAUSE DEPENDING ON THE NUMBER OF PEOPLE |
| | ALL EGRESS REQUIREMENTS SHALL BE MET. ROOMS COULD BE |
| | USED FOR ANY PURPOSE AT ANY TIME. PROOF OF THIS IS THAT |
| | OWNER CHANGED THE USE ALREADY. THAT'S WHY OCCUPANCY |
| | LOAD CALCULATIONS NEED TO BE ESTABLISHED BY THE LARGEST |
| | NUMBER COMPUTED IN ACCORDANCE WITH SECTIONS 1004.1.1 |
| | THROUGH 1004.1.3. ACCORDING TO THIS SECTION TABLE |
| | 1004.1.2 FBC 2004 AND FLOOR PLANS, THE FLOOR AREA PER |
| | OCCUPANT SHALL BE CALCULATED FOR 5S.F.. |
| | PROVIDE CALCULATIONS FOR NUMBER OF PEOPLE ON EACH ROOM |
| | OR SPACE TO VERIFY COMPLIANCE WITH TOTAL NUMBER OF |
| | PEOPLE. |
| | |
| | |
| | 10-SHEET S-1 ROOF FRAMING PLAN PLAN CALLS FOR METAL |
| | TRELLIS. PROVIDE COMPLETE DRAWINGS/DETAILS AND PRODUCT |
| | APPROVAL. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 AND |
| | SEC. 1609 FBC 2004. |
| | |
| | 11- NEED TO CONTACT HAROLD PISKURA, INSPECTION SERVICES |
| | MANAGER (561)805-6711, TO COORDINATE SPECIAL INSPECTOR |
| | SERVICES. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |