Plan Review Notes
Plan Review Notes For Permit 06101053
Permit Number 06101053
Review Stop M
Sequence Number 1
Notes
Date Text
2006-11-20 09:57:54*** DENIED ***
 1) AHU 5 AND CU 5 ARE NOT SHOWING IN THE A/C SCHEDULE
 ON PAGE M401, PLEASE CORRECT.
  
 2) NEED TO SHOW HOW MANY CFM'S OF OUTDOOR AIR IS GOING
 TO AHU 5 ON FIRST FLOOR, PLEASE SEE 2004 FBC/M 401.2.
  
 3) THE RETURN AIR GRILL IN THE MULTI PURPOSE ROOM IS
 LOCATED IN A CLOSET AND IF THE DOOR IS CLOSED IT WILL
 STOP THE RETURN AIR, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  