| Plan Review Notes For Permit 06101053 |
| Permit Number |
06101053 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-11-20 09:57:54 | *** DENIED *** | | | 1) AHU 5 AND CU 5 ARE NOT SHOWING IN THE A/C SCHEDULE | | | ON PAGE M401, PLEASE CORRECT. | | | | | | 2) NEED TO SHOW HOW MANY CFM'S OF OUTDOOR AIR IS GOING | | | TO AHU 5 ON FIRST FLOOR, PLEASE SEE 2004 FBC/M 401.2. | | | | | | 3) THE RETURN AIR GRILL IN THE MULTI PURPOSE ROOM IS | | | LOCATED IN A CLOSET AND IF THE DOOR IS CLOSED IT WILL | | | STOP THE RETURN AIR, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | | | | |
|